icsa-23-278-01
Vulnerability from csaf_cisa
Published
2023-10-05 06:00
Modified
2023-10-05 06:00
Summary
Hitachi Energy AFS65x,AFF66x, AFS67x, and AFR67x Series Products
Notes
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities by an attacker could have a high impact on availability, integrity, and confidentiality of the targeted devices.
Critical infrastructure sectors
Energy
Countries/areas deployed
Worldwide
Company headquarters location
Switzerland
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Recommended Practices
Do not click web links or open attachments in unsolicited email messages.
Recommended Practices
Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.
Recommended Practices
Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.
Recommended Practices
No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.
{ "document": { "acknowledgments": [ { "organization": "Hitachi Energy", "summary": "reporting these vulnerabilities to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities by an attacker could have a high impact on availability, integrity, and confidentiality of the targeted devices.", "title": "Risk evaluation" }, { "category": "other", "text": "Energy", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Switzerland", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:", "title": "Recommended Practices" }, { "category": "general", "text": "Do not click web links or open attachments in unsolicited email messages.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Recognizing and Avoiding Email Scams for more information on avoiding email scams.", "title": "Recommended Practices" }, { "category": "general", "text": "Refer to Avoiding Social Engineering and Phishing Attacks for more information on social engineering attacks.", "title": "Recommended Practices" }, { "category": "general", "text": "No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.", "title": "Recommended Practices" } ], "publisher": { "category": "coordinator", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-23-278-01 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2023/icsa-23-278-01.json" }, { "category": "self", "summary": "ICSA Advisory ICSA-23-278-01 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-278-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/publications/emailscams0905.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ncas/tips/ST04-014" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Hitachi Energy AFS65x,AFF66x, AFS67x, and AFR67x Series Products", "tracking": { "current_release_date": "2023-10-05T06:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-23-278-01", "initial_release_date": "2023-10-05T06:00:00.000000Z", "revision_history": [ { "date": "2023-10-05T06:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "Initial Publication" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c= 03.0.02", "product": { "name": "AFF66X FW: \u003c= 03.0.02", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "AFF66X FW" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "AFS66X-S: vers:all/*", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "AFS66X-S" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "AFS660-C: vers:all/*", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "AFS660-C" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "AFS66X-B: vers:all/*", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "AFS66X-B" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "AFS670-V20: vers:all/*", "product_id": "CSAFPID-0005" } } ], "category": "product_name", "name": "AFS670-V20" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "AFS65X: vers:all/*", "product_id": "CSAFPID-0006" } } ], "category": "product_name", "name": "AFS65X" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "AFS67X: vers:all/*", "product_id": "CSAFPID-0007" } } ], "category": "product_name", "name": "AFS67X" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "AFR677: vers:all/*", "product_id": "CSAFPID-0008" } } ], "category": "product_name", "name": "AFR677" } ], "category": "vendor", "name": "Hitachi Energy" } ] }, "vulnerabilities": [ { "cve": "CVE-2021-45960", "cwe": { "id": "CWE-682", "name": "Incorrect Calculation" }, "notes": [ { "category": "summary", "text": "In Expat (aka libexpat) before 2.4.3, a left shift by 29(or more) places in the storeAtts function in xmlparse.c can lead to realloc misbehavior (e.g., allocating too few bytes, or only freeing memory).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-45960" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2021-46143", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "In doProlog in xmlparse.c in Expat (aka libexpat) before 2.4.3, an integer overflow exists for m_groupSize.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-46143" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 7.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-22822", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "Vulnerable code using addBinding in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-22822" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-22823", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "Vulnerable code using build_model in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-22823" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-22824", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "Vulnerable code using defineAttribute in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-22824" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-22825", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "The lookup in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-22825" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-22826", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "Vulnerable code using nextScaffoldPart in xmlparse.c in Expat (aka libexpat) before 2.4.3 has an integer overflow", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-22826" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 8.8, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-22827", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "An insecure direct object reference for the file-download URL in Synametrics SynaMan before 5.0 allows a remote attacker to access unshared files via a modified base64-encoded filename string.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-22827" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-25314", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "In Expat (aka libexpat) before 2.4.5, there is an integer overflow in copyString.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-25314" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-25315", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "In Expat (aka libexpat) before 2.4.5, there is an integer overflow in storeRawNames", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-25315" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-25235", "cwe": { "id": "CWE-116", "name": "Improper Encoding or Escaping of Output" }, "notes": [ { "category": "summary", "text": "Vulnerable code in xmltok_impl.c in Expat (aka libexpat) before 2.4.5 lacks certain validation of encoding, such as checks for whether a UTF-8 character is valid in a certain context.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-25235" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-25236", "cwe": { "id": "CWE-668", "name": "Exposure of Resource to Wrong Sphere" }, "notes": [ { "category": "summary", "text": "Vulnerable code in xmlparse.c in Expat (aka libexpat) before 2.4.5 allows attackers to insert namespace-separator characters into namespace URIs.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-25236" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-23852", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "Expat (aka libexpat) before 2.4.4 has a signed integer overflow in XML_GetBuffer, for configurations with a nonzero XML_CONTEXT_BYTES", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-23852" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] }, { "cve": "CVE-2022-23990", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "Expat (aka libexpat) before 2.4.4 has an integer overflow in the doProlog function.", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-23990" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Hitachi energy recommends the following actions:", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "vendor_fix", "details": "AFF66X FW 03.0.02 and earlier: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFF66X 04.x.xx FW when released.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "vendor_fix", "details": "AFS66X-S, AFS660-C, AFS66X-B, AFS670-V20 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to upcoming AFS66X, AFS670-V20 7.1.08 FW when released. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server or restrict access to IEC61850-MMS to trusted IP addresses.", "product_ids": [ "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005" ] }, { "category": "vendor_fix", "details": "AFS65X, AFS67X, AFR677 devices: For all vulnerabilities, apply mitigation strategy as described in Hitachi Energy\u0027s general mitigation factors below or update to AFS65X, AFS67X, AFR677 09.1.08 FW. Disable HTTP/HTTPS server or restrict access to HTTP/HTTPS to trusted IP addresses. Disable IEC61850-MMS server.", "product_ids": [ "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Hitachi Energy\u0027s general mitigation factors:Security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For more information, please visit Hitachi Energy\u0027s Advisory.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ], "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000165\u0026DocumentRevisionId=B\u0026languageCode=en\u0026Preview=true" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ] } ] }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.