CERTFR-2019-AVI-615
Vulnerability from certfr_avis
De multiples vulnérabilités ont été découvertes dans les produits Siemens. Certaines d'entre elles permettent à un attaquant de provoquer une exécution de code arbitraire à distance, un déni de service à distance et un contournement de la politique de sécurité.
Solution
Se référer au bulletin de sécurité de l'éditeur pour l'obtention des correctifs (cf. section Documentation).
NoneImpacted products
Vendor | Product | Description | ||
---|---|---|---|---|
Siemens | N/A | SPPA-T3000 MS3000 Migration Server | ||
Siemens | N/A | SiNVR 3 Central Control Server (CCS) | ||
Siemens | N/A | SIMATIC S7-1200 CPU | ||
Siemens | N/A | RUGGEDCOM ROS RSG9xx R/C | ||
Siemens | N/A | RUGGEDCOM ROS RMC8388 | ||
Siemens | N/A | EN100 Ethernet module Modbus TCP | ||
Siemens | N/A | SIMATIC WinCC OA | ||
Siemens | N/A | SIMATIC CP 1626 | ||
Siemens | N/A | SCALANCE W700 versions antérieures à V6.4 | ||
Siemens | N/A | SIMATIC NET PC | ||
Siemens | N/A | SIMATIC WinCC Runtime Professional | ||
Siemens | N/A | EN100 Ethernet module IEC 61850 versions antérieures à V4.37 | ||
Siemens | N/A | SPPA-T3000 Application Server versions antérieures à Service Pack R8.2 SP1 | ||
Siemens | N/A | SIMATIC WinCC Runtime Advanced | ||
Siemens | N/A | RUGGEDCOM ROS RSL910 | ||
Siemens | N/A | SIMATIC WinCC (TIA Portal) versions antérieures à V16 | ||
Siemens | N/A | Famille de commutateurs SCALANCE X-200IRT et les variantes SIPLUSNET versions antérieures à V5.4.2 | ||
Siemens | N/A | SIMATIC S7-200 SMART CPU | ||
Siemens | N/A | SIMATIC WinCC OA versions antérieures à 3.16 patch version 13 | ||
Siemens | N/A | SiNVR 3 Video Server | ||
Siemens | N/A | EN100 Ethernet module DNP3 | ||
Siemens | N/A | SCALANCE W1700 versions antérieures à V1.1 | ||
Siemens | N/A | RUGGEDCOM ROS RSG2488 | ||
Siemens | N/A | EN100 Ethernet module PROFINET IO | ||
Siemens | N/A | EN100 Ethernet module IEC104 | ||
Siemens | N/A | RUGGEDCOM ROS RSG920P | ||
Siemens | N/A | TIM 1531 IRC | ||
Siemens | N/A | XHQ versions antérieures à V6.0.0.2 | ||
Siemens | N/A | SIMATIC STEP 7 (TIA Portal) versions antérieures à V16 | ||
Siemens | N/A | RUGGEDCOM ROS RST2228 | ||
Siemens | N/A | SIMATIC HMI Panel | ||
Siemens | N/A | Famille de commutateurs SCALANCE X-200 et les variantes SIPLUSNET versions antérieures à V5.2.4 |
References
Title | Publication Time | Tags | |||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
{ "$ref": "https://www.cert.ssi.gouv.fr/openapi.json", "affected_systems": [ { "description": "SPPA-T3000 MS3000 Migration Server", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SiNVR 3 Central Control Server (CCS)", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC S7-1200 CPU", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "RUGGEDCOM ROS RSG9xx R/C", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "RUGGEDCOM ROS RMC8388", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "EN100 Ethernet module Modbus TCP", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC WinCC OA", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC CP 1626", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SCALANCE W700 versions ant\u00e9rieures \u00e0 V6.4", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC NET PC", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC WinCC Runtime Professional", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "EN100 Ethernet module IEC 61850 versions ant\u00e9rieures \u00e0 V4.37", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SPPA-T3000 Application Server versions ant\u00e9rieures \u00e0 Service Pack R8.2 SP1", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC WinCC Runtime Advanced", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "RUGGEDCOM ROS RSL910", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC WinCC (TIA Portal) versions ant\u00e9rieures \u00e0 V16", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "Famille de commutateurs SCALANCE X-200IRT et les variantes SIPLUSNET versions ant\u00e9rieures \u00e0 V5.4.2", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC S7-200 SMART CPU", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC WinCC OA versions ant\u00e9rieures \u00e0 3.16 patch version 13", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SiNVR 3 Video Server", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "EN100 Ethernet module DNP3", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SCALANCE W1700 versions ant\u00e9rieures \u00e0 V1.1", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "RUGGEDCOM ROS RSG2488", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "EN100 Ethernet module PROFINET IO", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "EN100 Ethernet module IEC104", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "RUGGEDCOM ROS RSG920P", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "TIM 1531 IRC", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "XHQ versions ant\u00e9rieures \u00e0 V6.0.0.2", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC STEP 7 (TIA Portal) versions ant\u00e9rieures \u00e0 V16", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "RUGGEDCOM ROS RST2228", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "SIMATIC HMI Panel", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } }, { "description": "Famille de commutateurs SCALANCE X-200 et les variantes SIPLUSNET versions ant\u00e9rieures \u00e0 V5.2.4", "product": { "name": "N/A", "vendor": { "name": "Siemens", "scada": true } } } ], "affected_systems_content": null, "content": "## Solution\n\nSe r\u00e9f\u00e9rer au bulletin de s\u00e9curit\u00e9 de l\u0027\u00e9diteur pour l\u0027obtention des\ncorrectifs (cf. section Documentation).\n", "cves": [ { "name": "CVE-2019-13944", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13944" }, { "name": "CVE-2019-18339", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18339" }, { "name": "CVE-2019-18341", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18341" }, { "name": "CVE-2019-18332", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18332" }, { "name": "CVE-2019-18335", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18335" }, { "name": "CVE-2019-18338", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18338" }, { "name": "CVE-2018-14526", "url": "https://www.cve.org/CVERecord?id=CVE-2018-14526" }, { "name": "CVE-2019-18319", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18319" }, { "name": "CVE-2019-18331", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18331" }, { "name": "CVE-2019-18312", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18312" }, { "name": "CVE-2019-18320", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18320" }, { "name": "CVE-2019-18322", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18322" }, { "name": "CVE-2019-18283", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18283" }, { "name": "CVE-2019-18303", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18303" }, { "name": "CVE-2019-18302", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18302" }, { "name": "CVE-2019-18311", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18311" }, { "name": "CVE-2019-18290", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18290" }, { "name": "CVE-2019-18292", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18292" }, { "name": "CVE-2019-18309", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18309" }, { "name": "CVE-2019-18291", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18291" }, { "name": "CVE-2019-18304", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18304" }, { "name": "CVE-2019-18326", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18326" }, { "name": "CVE-2019-18305", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18305" }, { "name": "CVE-2019-18318", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18318" }, { "name": "CVE-2013-3634", "url": "https://www.cve.org/CVERecord?id=CVE-2013-3634" }, { "name": "CVE-2019-18334", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18334" }, { "name": "CVE-2019-18299", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18299" }, { "name": "CVE-2019-13932", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13932" }, { "name": "CVE-2019-18316", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18316" }, { "name": "CVE-2019-18329", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18329" }, { "name": "CVE-2019-10929", "url": "https://www.cve.org/CVERecord?id=CVE-2019-10929" }, { "name": "CVE-2019-13931", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13931" }, { "name": "CVE-2019-18333", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18333" }, { "name": "CVE-2019-18300", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18300" }, { "name": "CVE-2019-18301", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18301" }, { "name": "CVE-2019-18328", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18328" }, { "name": "CVE-2019-18321", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18321" }, { "name": "CVE-2019-13947", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13947" }, { "name": "CVE-2019-18317", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18317" }, { "name": "CVE-2019-18294", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18294" }, { "name": "CVE-2019-13943", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13943" }, { "name": "CVE-2019-18330", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18330" }, { "name": "CVE-2019-18314", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18314" }, { "name": "CVE-2019-18307", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18307" }, { "name": "CVE-2019-13945", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13945" }, { "name": "CVE-2019-18308", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18308" }, { "name": "CVE-2013-3633", "url": "https://www.cve.org/CVERecord?id=CVE-2013-3633" }, { "name": "CVE-2019-18306", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18306" }, { "name": "CVE-2019-18340", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18340" }, { "name": "CVE-2019-18342", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18342" }, { "name": "CVE-2019-18325", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18325" }, { "name": "CVE-2018-4832", "url": "https://www.cve.org/CVERecord?id=CVE-2018-4832" }, { "name": "CVE-2019-18310", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18310" }, { "name": "CVE-2019-13103", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13103" }, { "name": "CVE-2019-13930", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13930" }, { "name": "CVE-2019-18337", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18337" }, { "name": "CVE-2019-18323", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18323" }, { "name": "CVE-2019-18327", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18327" }, { "name": "CVE-2018-18440", "url": "https://www.cve.org/CVERecord?id=CVE-2018-18440" }, { "name": "CVE-2019-18315", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18315" }, { "name": "CVE-2019-18298", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18298" }, { "name": "CVE-2019-13942", "url": "https://www.cve.org/CVERecord?id=CVE-2019-13942" }, { "name": "CVE-2019-18313", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18313" }, { "name": "CVE-2019-18324", "url": "https://www.cve.org/CVERecord?id=CVE-2019-18324" } ], "initial_release_date": "2019-12-10T00:00:00", "last_revision_date": "2019-12-10T00:00:00", "links": [], "reference": "CERTFR-2019-AVI-615", "revisions": [ { "description": "Version initiale", "revision_date": "2019-12-10T00:00:00.000000" } ], "risks": [ { "description": "D\u00e9ni de service \u00e0 distance" }, { "description": "Injection de code indirecte \u00e0 distance (XSS)" }, { "description": "Injection de requ\u00eates ill\u00e9gitimes par rebond (CSRF)" }, { "description": "Ex\u00e9cution de code arbitraire \u00e0 distance" }, { "description": "Atteinte \u00e0 l\u0027int\u00e9grit\u00e9 des donn\u00e9es" }, { "description": "Contournement de la politique de s\u00e9curit\u00e9" }, { "description": "Atteinte \u00e0 la confidentialit\u00e9 des donn\u00e9es" }, { "description": "\u00c9l\u00e9vation de privil\u00e8ges" } ], "summary": "De multiples vuln\u00e9rabilit\u00e9s ont \u00e9t\u00e9 d\u00e9couvertes dans les produits\nSiemens. Certaines d\u0027entre elles permettent \u00e0 un attaquant de provoquer\nune ex\u00e9cution de code arbitraire \u00e0 distance, un d\u00e9ni de service \u00e0\ndistance et un contournement de la politique de s\u00e9curit\u00e9.\n", "title": "Multiples vuln\u00e9rabilit\u00e9s dans les produits Siemens", "vendor_advisories": [ { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-451445 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-418979 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-170686 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf" }, { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-344983 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-344983.pdf" }, { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-761617 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-618620 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf" }, { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-525454 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" }, { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-686531 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-686531.pdf" }, { "published_at": null, "title": "Bulletin de s\u00e9curit\u00e9 Siemens ssa-273799 du 10 d\u00e9cembre 2019", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-273799.pdf" } ] }
CVE-2019-18291 (GCVE-0-2019-18291)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.216Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:22", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18291", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18291", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.216Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18306 (GCVE-0-2019-18306)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-125 - Out-of-bounds Read
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.163Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-125", "description": "CWE-125: Out-of-bounds Read", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:49", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18306", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-125: Out-of-bounds Read" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18306", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.163Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18301 (GCVE-0-2019-18301)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-190 - Integer Overflow or Wraparound
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.190Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-190", "description": "CWE-190: Integer Overflow or Wraparound", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:40", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18301", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-190: Integer Overflow or Wraparound" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18301", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.190Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18307 (GCVE-0-2019-18307)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-125 - Out-of-bounds Read
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, and CVE-2019-18306. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.140Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, and CVE-2019-18306. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-125", "description": "CWE-125: Out-of-bounds Read", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:51", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18307", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, and CVE-2019-18306. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-125: Out-of-bounds Read" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18307", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.140Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18318 (GCVE-0-2019-18318)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server can cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18317 and CVE-2019-18319. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.486Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server can cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18317 and CVE-2019-18319. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:11", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18318", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server can cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18317 and CVE-2019-18319. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18318", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.486Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2013-3633 (GCVE-0-2013-3633)
Vulnerability from cvelistv5
Published
2013-05-24 20:00
Modified
2024-08-06 16:14
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- n/a
Summary
A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The user privileges for the web interface are only enforced on client side and not properly verified on server side. Therefore, an attacker is able to execute privileged commands using an unprivileged account.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-06T16:14:56.558Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "n/a", "vendor": "n/a", "versions": [ { "status": "affected", "version": "n/a" } ] } ], "datePublic": "2013-05-24T00:00:00", "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions \u003c V5.0.0 for CVE-2013-3633 and versions \u003c V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions \u003c V5.1.0). The user privileges for the web interface are only enforced on client side and not properly verified on server side. Therefore, an attacker is able to execute privileged commands using an unprivileged account." } ], "problemTypes": [ { "descriptions": [ { "description": "n/a", "lang": "en", "type": "text" } ] } ], "providerMetadata": { "dateUpdated": "2019-12-12T19:08:46", "orgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "shortName": "mitre" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "cve@mitre.org", "ID": "CVE-2013-3633", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "n/a", "version": { "version_data": [ { "version_value": "n/a" } ] } } ] }, "vendor_name": "n/a" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions \u003c V5.0.0 for CVE-2013-3633 and versions \u003c V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions \u003c V5.1.0). The user privileges for the web interface are only enforced on client side and not properly verified on server side. Therefore, an attacker is able to execute privileged commands using an unprivileged account." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "n/a" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "assignerShortName": "mitre", "cveId": "CVE-2013-3633", "datePublished": "2013-05-24T20:00:00", "dateReserved": "2013-05-22T00:00:00", "dateUpdated": "2024-08-06T16:14:56.558Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18328 (GCVE-0-2019-18328)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.301Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:27", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18328", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18328", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.301Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18334 (GCVE-0-2019-18334)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-200 - Exposure of Sensitive Information to an Unauthorized Actor
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to enumerate valid user names by sending specifically crafted packets to 8090/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.301Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to enumerate valid user names by sending specifically crafted packets to 8090/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-200", "description": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:37", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18334", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to enumerate valid user names by sending specifically crafted packets to 8090/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18334", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.301Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18335 (GCVE-0-2019-18335)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-200 - Exposure of Sensitive Information to an Unauthorized Actor
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to gain access to logs and configuration files by sending specifically crafted packets to 80/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.330Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to gain access to logs and configuration files by sending specifically crafted packets to 80/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-200", "description": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:39", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18335", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to gain access to logs and configuration files by sending specifically crafted packets to 80/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18335", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.330Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18308 (GCVE-0-2019-18308)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-284 - Improper Access Control
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with local access to the MS3000 Server and a low privileged user account could gain root privileges by manipulating specific files in the local file system. This vulnerability is independent from CVE-2019-18309. Please note that an attacker needs to have local access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.307Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with local access to the MS3000 Server and a low privileged user account could gain root privileges by manipulating specific files in the local file system. This vulnerability is independent from CVE-2019-18309. Please note that an attacker needs to have local access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-284", "description": "CWE-284: Improper Access Control", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:52", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18308", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with local access to the MS3000 Server and a low privileged user account could gain root privileges by manipulating specific files in the local file system. This vulnerability is independent from CVE-2019-18309. Please note that an attacker needs to have local access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-284: Improper Access Control" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18308", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.307Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2018-14526 (GCVE-0-2018-14526)
Vulnerability from cvelistv5
Published
2018-08-08 19:00
Modified
2024-08-05 09:29
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- n/a
Summary
An issue was discovered in rsn_supp/wpa.c in wpa_supplicant 2.0 through 2.6. Under certain conditions, the integrity of EAPOL-Key messages is not checked, leading to a decryption oracle. An attacker within range of the Access Point and client can abuse the vulnerability to recover sensitive information.
References
URL | Tags | |||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T09:29:51.701Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://papers.mathyvanhoef.com/woot2018.pdf" }, { "name": "1041438", "tags": [ "vdb-entry", "x_refsource_SECTRACK", "x_transferred" ], "url": "http://www.securitytracker.com/id/1041438" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://w1.fi/security/2018-1/unauthenticated-eapol-key-decryption.txt" }, { "name": "FreeBSD-SA-18:11", "tags": [ "vendor-advisory", "x_refsource_FREEBSD", "x_transferred" ], "url": "https://security.FreeBSD.org/advisories/FreeBSD-SA-18:11.hostapd.asc" }, { "name": "RHSA-2018:3107", "tags": [ "vendor-advisory", "x_refsource_REDHAT", "x_transferred" ], "url": "https://access.redhat.com/errata/RHSA-2018:3107" }, { "name": "[debian-lts-announce] 20180809 [SECURITY] [DLA 1462-1] wpa security update", "tags": [ "mailing-list", "x_refsource_MLIST", "x_transferred" ], "url": "https://lists.debian.org/debian-lts-announce/2018/08/msg00009.html" }, { "name": "USN-3745-1", "tags": [ "vendor-advisory", "x_refsource_UBUNTU", "x_transferred" ], "url": "https://usn.ubuntu.com/3745-1/" }, { "name": "openSUSE-SU-2019:1345", "tags": [ "vendor-advisory", "x_refsource_SUSE", "x_transferred" ], "url": "http://lists.opensuse.org/opensuse-security-announce/2019-05/msg00013.html" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-344983.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-01" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "n/a", "vendor": "n/a", "versions": [ { "status": "affected", "version": "n/a" } ] } ], "datePublic": "2018-08-08T00:00:00", "descriptions": [ { "lang": "en", "value": "An issue was discovered in rsn_supp/wpa.c in wpa_supplicant 2.0 through 2.6. Under certain conditions, the integrity of EAPOL-Key messages is not checked, leading to a decryption oracle. An attacker within range of the Access Point and client can abuse the vulnerability to recover sensitive information." } ], "problemTypes": [ { "descriptions": [ { "description": "n/a", "lang": "en", "type": "text" } ] } ], "providerMetadata": { "dateUpdated": "2019-12-19T18:23:13", "orgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "shortName": "mitre" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://papers.mathyvanhoef.com/woot2018.pdf" }, { "name": "1041438", "tags": [ "vdb-entry", "x_refsource_SECTRACK" ], "url": "http://www.securitytracker.com/id/1041438" }, { "tags": [ "x_refsource_MISC" ], "url": "https://w1.fi/security/2018-1/unauthenticated-eapol-key-decryption.txt" }, { "name": "FreeBSD-SA-18:11", "tags": [ "vendor-advisory", "x_refsource_FREEBSD" ], "url": "https://security.FreeBSD.org/advisories/FreeBSD-SA-18:11.hostapd.asc" }, { "name": "RHSA-2018:3107", "tags": [ "vendor-advisory", "x_refsource_REDHAT" ], "url": "https://access.redhat.com/errata/RHSA-2018:3107" }, { "name": "[debian-lts-announce] 20180809 [SECURITY] [DLA 1462-1] wpa security update", "tags": [ "mailing-list", "x_refsource_MLIST" ], "url": "https://lists.debian.org/debian-lts-announce/2018/08/msg00009.html" }, { "name": "USN-3745-1", "tags": [ "vendor-advisory", "x_refsource_UBUNTU" ], "url": "https://usn.ubuntu.com/3745-1/" }, { "name": "openSUSE-SU-2019:1345", "tags": [ "vendor-advisory", "x_refsource_SUSE" ], "url": "http://lists.opensuse.org/opensuse-security-announce/2019-05/msg00013.html" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-344983.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-01" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "cve@mitre.org", "ID": "CVE-2018-14526", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "n/a", "version": { "version_data": [ { "version_value": "n/a" } ] } } ] }, "vendor_name": "n/a" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "An issue was discovered in rsn_supp/wpa.c in wpa_supplicant 2.0 through 2.6. Under certain conditions, the integrity of EAPOL-Key messages is not checked, leading to a decryption oracle. An attacker within range of the Access Point and client can abuse the vulnerability to recover sensitive information." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "n/a" } ] } ] }, "references": { "reference_data": [ { "name": "https://papers.mathyvanhoef.com/woot2018.pdf", "refsource": "MISC", "url": "https://papers.mathyvanhoef.com/woot2018.pdf" }, { "name": "1041438", "refsource": "SECTRACK", "url": "http://www.securitytracker.com/id/1041438" }, { "name": "https://w1.fi/security/2018-1/unauthenticated-eapol-key-decryption.txt", "refsource": "MISC", "url": "https://w1.fi/security/2018-1/unauthenticated-eapol-key-decryption.txt" }, { "name": "FreeBSD-SA-18:11", "refsource": "FREEBSD", "url": "https://security.FreeBSD.org/advisories/FreeBSD-SA-18:11.hostapd.asc" }, { "name": "RHSA-2018:3107", "refsource": "REDHAT", "url": "https://access.redhat.com/errata/RHSA-2018:3107" }, { "name": "[debian-lts-announce] 20180809 [SECURITY] [DLA 1462-1] wpa security update", "refsource": "MLIST", "url": "https://lists.debian.org/debian-lts-announce/2018/08/msg00009.html" }, { "name": "USN-3745-1", "refsource": "UBUNTU", "url": "https://usn.ubuntu.com/3745-1/" }, { "name": "openSUSE-SU-2019:1345", "refsource": "SUSE", "url": "http://lists.opensuse.org/opensuse-security-announce/2019-05/msg00013.html" }, { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-344983.pdf", "refsource": "CONFIRM", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-344983.pdf" }, { "name": "https://www.us-cert.gov/ics/advisories/icsa-19-344-01", "refsource": "MISC", "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-01" } ] } } } }, "cveMetadata": { "assignerOrgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "assignerShortName": "mitre", "cveId": "CVE-2018-14526", "datePublished": "2018-08-08T19:00:00", "dateReserved": "2018-07-22T00:00:00", "dateUpdated": "2024-08-05T09:29:51.701Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18337 (GCVE-0-2019-18337)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-10-15 18:35
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The Control Center Server (CCS) contains an authentication bypass
vulnerability in its XML-based communication protocol as provided by default
on ports 5444/tcp and 5440/tcp.
A remote attacker with network access to the CCS server could
exploit this vulnerability to read the CCS users database, including
the passwords of all users in obfuscated cleartext.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | Control Center Server (CCS) |
Version: All versions < V1.5.0 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:14.368Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ], "title": "CVE Program Container" }, { "metrics": [ { "other": { "content": { "id": "CVE-2019-18337", "options": [ { "Exploitation": "none" }, { "Automatable": "yes" }, { "Technical Impact": "total" } ], "role": "CISA Coordinator", "timestamp": "2024-10-15T17:36:29.248431Z", "version": "2.0.3" }, "type": "ssvc" } } ], "providerMetadata": { "dateUpdated": "2024-10-15T18:35:44.549Z", "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP" }, "title": "CISA ADP Vulnrichment" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "Control Center Server (CCS)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V1.5.0" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in Control Center Server (CCS) (All versions \u003c V1.5.0). The Control Center Server (CCS) contains an authentication bypass\nvulnerability in its XML-based communication protocol as provided by default\non ports 5444/tcp and 5440/tcp.\n\nA remote attacker with network access to the CCS server could\nexploit this vulnerability to read the CCS users database, including\nthe passwords of all users in obfuscated cleartext." } ], "metrics": [ { "cvssV3_1": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:F/RL:U/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:56:11.011Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18337", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-10-15T18:35:44.549Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13942 (GCVE-0-2019-13942)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 00:05
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-119 - Improper Restriction of Operations within the Bounds of a Memory Buffer
Summary
A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). An unauthorized user could exploit a buffer overflow vulnerability in the webserver. Specially crafted packets sent could cause a Denial-of-Service condition and if certain conditions are met, the affected devices must be restarted manually to fully recover. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Siemens AG | EN100 Ethernet module DNP3 variant |
Version: All versions |
||||||||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T00:05:44.006Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "EN100 Ethernet module DNP3 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module IEC 61850 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c V4.37" } ] }, { "product": "EN100 Ethernet module IEC104 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module Modbus TCP variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module PROFINET IO variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions \u003c V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). An unauthorized user could exploit a buffer overflow vulnerability in the webserver. Specially crafted packets sent could cause a Denial-of-Service condition and if certain conditions are met, the affected devices must be restarted manually to fully recover. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-119", "description": "CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2020-01-16T15:35:24", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-13942", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "EN100 Ethernet module DNP3 variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module IEC 61850 variant", "version": { "version_data": [ { "version_value": "All versions \u003c V4.37" } ] } }, { "product_name": "EN100 Ethernet module IEC104 variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module Modbus TCP variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module PROFINET IO variant", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens AG" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions \u003c V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). An unauthorized user could exploit a buffer overflow vulnerability in the webserver. Specially crafted packets sent could cause a Denial-of-Service condition and if certain conditions are met, the affected devices must be restarted manually to fully recover. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "name": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07", "refsource": "MISC", "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-13942", "datePublished": "2019-12-12T19:08:46", "dateReserved": "2019-07-18T00:00:00", "dateUpdated": "2024-08-05T00:05:44.006Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18299 (GCVE-0-2019-18299)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-190 - Integer Overflow or Wraparound
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.155Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-190", "description": "CWE-190: Integer Overflow or Wraparound", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:36", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18299", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-190: Integer Overflow or Wraparound" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18299", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.155Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18290 (GCVE-0-2019-18290)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.161Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:21", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18290", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18290", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.161Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18292 (GCVE-0-2019-18292)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.122Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:24", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18292", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18292", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.122Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18320 (GCVE-0-2019-18320)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to upload arbitrary files without authentication. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:14.044Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to upload arbitrary files without authentication. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:14", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18320", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could be able to upload arbitrary files without authentication. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18320", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:14.044Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2013-3634 (GCVE-0-2013-3634)
Vulnerability from cvelistv5
Published
2013-05-24 20:00
Modified
2024-08-06 16:14
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- n/a
Summary
A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-06T16:14:56.585Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "n/a", "vendor": "n/a", "versions": [ { "status": "affected", "version": "n/a" } ] } ], "datePublic": "2013-05-24T00:00:00", "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions \u003c V5.0.0 for CVE-2013-3633 and versions \u003c V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions \u003c V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials." } ], "problemTypes": [ { "descriptions": [ { "description": "n/a", "lang": "en", "type": "text" } ] } ], "providerMetadata": { "dateUpdated": "2019-12-12T19:08:46", "orgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "shortName": "mitre" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "cve@mitre.org", "ID": "CVE-2013-3634", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "n/a", "version": { "version_data": [ { "version_value": "n/a" } ] } } ] }, "vendor_name": "n/a" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions \u003c V5.0.0 for CVE-2013-3633 and versions \u003c V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions \u003c V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "n/a" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-170686.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "assignerShortName": "mitre", "cveId": "CVE-2013-3634", "datePublished": "2013-05-24T20:00:00", "dateReserved": "2013-05-22T00:00:00", "dateUpdated": "2024-08-06T16:14:56.585Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18323 (GCVE-0-2019-18323)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:14.271Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:19", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18323", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18323", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:14.271Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13943 (GCVE-0-2019-13943)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 00:05
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-79 - Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting')
Summary
A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The web interface could allow Cross-Site Scripting (XSS) attacks if an attacker is able to modify content of particular web pages, causing the application to behave in unexpected ways for legitimate users. Successful exploitation does not require for an attacker to be authenticated to the web interface. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security. vulnerability was known.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Siemens AG | EN100 Ethernet module DNP3 variant |
Version: All versions |
||||||||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T00:05:44.073Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "EN100 Ethernet module DNP3 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module IEC 61850 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c V4.37" } ] }, { "product": "EN100 Ethernet module IEC104 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module Modbus TCP variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module PROFINET IO variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions \u003c V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The web interface could allow Cross-Site Scripting (XSS) attacks if an attacker is able to modify content of particular web pages, causing the application to behave in unexpected ways for legitimate users. Successful exploitation does not require for an attacker to be authenticated to the web interface. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security. vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-79", "description": "CWE-79: Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2020-01-16T15:35:24", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-13943", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "EN100 Ethernet module DNP3 variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module IEC 61850 variant", "version": { "version_data": [ { "version_value": "All versions \u003c V4.37" } ] } }, { "product_name": "EN100 Ethernet module IEC104 variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module Modbus TCP variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module PROFINET IO variant", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens AG" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions \u003c V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). The web interface could allow Cross-Site Scripting (XSS) attacks if an attacker is able to modify content of particular web pages, causing the application to behave in unexpected ways for legitimate users. Successful exploitation does not require for an attacker to be authenticated to the web interface. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security. vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-79: Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "name": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07", "refsource": "MISC", "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-13943", "datePublished": "2019-12-12T19:08:46", "dateReserved": "2019-07-18T00:00:00", "dateUpdated": "2024-08-05T00:05:44.073Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18302 (GCVE-0-2019-18302)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-190 - Integer Overflow or Wraparound
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.167Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-190", "description": "CWE-190: Integer Overflow or Wraparound", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:42", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18302", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-190: Integer Overflow or Wraparound" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18302", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.167Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18322 (GCVE-0-2019-18322)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to read and write arbitrary files on the local file system by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18321. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:12.859Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to read and write arbitrary files on the local file system by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18321. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:17", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18322", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to read and write arbitrary files on the local file system by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18321. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18322", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:12.859Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18324 (GCVE-0-2019-18324)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.588Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:20", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18324", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18324", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.588Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18304 (GCVE-0-2019-18304)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-190 - Integer Overflow or Wraparound
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.161Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-190", "description": "CWE-190: Integer Overflow or Wraparound", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:45", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18304", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-190: Integer Overflow or Wraparound" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18304", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.161Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18325 (GCVE-0-2019-18325)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:12.854Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:22", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18325", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18325", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:12.854Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18283 (GCVE-0-2019-18283)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-502 - Deserialization of Untrusted Data
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). The AdminService is available without authentication on the Application Server. An attacker can gain remote code execution by sending specifically crafted objects to one of its functions. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.154Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). The AdminService is available without authentication on the Application Server. An attacker can gain remote code execution by sending specifically crafted objects to one of its functions. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-502", "description": "CWE-502: Deserialization of Untrusted Data", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:09", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18283", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). The AdminService is available without authentication on the Application Server. An attacker can gain remote code execution by sending specifically crafted objects to one of its functions. Please note that an attacker needs to have access to the Application Highway in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-502: Deserialization of Untrusted Data" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18283", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.154Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13944 (GCVE-0-2019-13944)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 00:05
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-23 - Relative Path Traversal
Summary
A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions < V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). A vulnerability in the integrated web server of the affected devices could allow unauthorized attackers to obtain sensitive information about the device, including logs and configurations. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Siemens AG | EN100 Ethernet module DNP3 variant |
Version: All versions |
||||||||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T00:05:43.799Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "EN100 Ethernet module DNP3 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module IEC 61850 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c V4.37" } ] }, { "product": "EN100 Ethernet module IEC104 variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module Modbus TCP variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "EN100 Ethernet module PROFINET IO variant", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions \u003c V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). A vulnerability in the integrated web server of the affected devices could allow unauthorized attackers to obtain sensitive information about the device, including logs and configurations. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-23", "description": "CWE-23: Relative Path Traversal", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2020-01-16T15:35:24", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-13944", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "EN100 Ethernet module DNP3 variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module IEC 61850 variant", "version": { "version_data": [ { "version_value": "All versions \u003c V4.37" } ] } }, { "product_name": "EN100 Ethernet module IEC104 variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module Modbus TCP variant", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "EN100 Ethernet module PROFINET IO variant", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens AG" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in EN100 Ethernet module DNP3 variant (All versions), EN100 Ethernet module IEC 61850 variant (All versions \u003c V4.37), EN100 Ethernet module IEC104 variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module PROFINET IO variant (All versions). A vulnerability in the integrated web server of the affected devices could allow unauthorized attackers to obtain sensitive information about the device, including logs and configurations. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-23: Relative Path Traversal" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-418979.pdf" }, { "name": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07", "refsource": "MISC", "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-07" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-13944", "datePublished": "2019-12-12T19:08:46", "dateReserved": "2019-07-18T00:00:00", "dateUpdated": "2024-08-05T00:05:43.799Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18317 (GCVE-0-2019-18317)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18318 and CVE-2019-18319. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.255Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18318 and CVE-2019-18319. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:09", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18317", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18318 and CVE-2019-18319. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18317", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.255Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18338 (GCVE-0-2019-18338)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-11-15 14:50
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-23 - Relative Path Traversal
Summary
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The Control Center Server (CCS) contains a directory traversal
vulnerability in its XML-based communication protocol as provided by default
on ports 5444/tcp and 5440/tcp.
An authenticated remote attacker with network access to the CCS server
could exploit this vulnerability to list arbitrary directories
or read files outside of the CCS application context.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | Control Center Server (CCS) |
Version: All versions < V1.5.0 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.984Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ], "title": "CVE Program Container" }, { "metrics": [ { "other": { "content": { "id": "CVE-2019-18338", "options": [ { "Exploitation": "none" }, { "Automatable": "no" }, { "Technical Impact": "partial" } ], "role": "CISA Coordinator", "timestamp": "2024-01-16T20:16:01.878394Z", "version": "2.0.3" }, "type": "ssvc" } } ], "providerMetadata": { "dateUpdated": "2024-11-15T14:50:03.991Z", "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP" }, "title": "CISA ADP Vulnrichment" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "Control Center Server (CCS)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V1.5.0" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in Control Center Server (CCS) (All versions \u003c V1.5.0). The Control Center Server (CCS) contains a directory traversal\nvulnerability in its XML-based communication protocol as provided by default\non ports 5444/tcp and 5440/tcp.\n\nAn authenticated remote attacker with network access to the CCS server\ncould exploit this vulnerability to list arbitrary directories\nor read files outside of the CCS application context." } ], "metrics": [ { "cvssV3_1": { "baseScore": 7.7, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:N/A:N/E:F/RL:U/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-23", "description": "CWE-23: Relative Path Traversal", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:56:12.210Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18338", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-11-15T14:50:03.991Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18341 (GCVE-0-2019-18341)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The SFTP service (default port 22/tcp) of the Control Center Server
(CCS) contains an authentication bypass vulnerability.
A remote attacker with network access to the CCS server could
exploit this vulnerability to read data from the EDIR directory
(for example, the list of all configured stations).
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | Control Center Server (CCS) |
Version: All versions < V1.5.0 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.535Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "Control Center Server (CCS)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V1.5.0" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in Control Center Server (CCS) (All versions \u003c V1.5.0). The SFTP service (default port 22/tcp) of the Control Center Server\n(CCS) contains an authentication bypass vulnerability.\n\nA remote attacker with network access to the CCS server could\nexploit this vulnerability to read data from the EDIR directory\n(for example, the list of all configured stations)." } ], "metrics": [ { "cvssV3_1": { "baseScore": 5.3, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N/E:F/RL:U/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:56:15.845Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18341", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.535Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18330 (GCVE-0-2019-18330)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, and CVE-2019-18329. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.278Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, and CVE-2019-18329. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:30", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18330", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, and CVE-2019-18329. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18330", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.278Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18315 (GCVE-0-2019-18315)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 8888/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.304Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 8888/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:06", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18315", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 8888/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18315", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.304Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18340 (GCVE-0-2019-18340)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-327 - Use of a Broken or Risky Cryptographic Algorithm
Summary
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0), Control Center Server (CCS) (All versions >= V1.5.0), SiNVR/SiVMS Video Server (All versions < V5.0.0), SiNVR/SiVMS Video Server (All versions >= V5.0.0). Both the SiVMS/SiNVR Video Server and the Control Center Server (CCS) store
user and device passwords by applying weak cryptography.
A local attacker could exploit this vulnerability to extract
the passwords from the user database and/or the device configuration files
to conduct further attacks.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Siemens | Control Center Server (CCS) |
Version: All versions < V1.5.0 |
|||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:14.118Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "Control Center Server (CCS)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V1.5.0" } ] }, { "defaultStatus": "unknown", "product": "Control Center Server (CCS)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003e= V1.5.0" } ] }, { "defaultStatus": "unknown", "product": "SiNVR/SiVMS Video Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V5.0.0" } ] }, { "defaultStatus": "unknown", "product": "SiNVR/SiVMS Video Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003e= V5.0.0" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in Control Center Server (CCS) (All versions \u003c V1.5.0), Control Center Server (CCS) (All versions \u003e= V1.5.0), SiNVR/SiVMS Video Server (All versions \u003c V5.0.0), SiNVR/SiVMS Video Server (All versions \u003e= V5.0.0). Both the SiVMS/SiNVR Video Server and the Control Center Server (CCS) store\nuser and device passwords by applying weak cryptography.\n\nA local attacker could exploit this vulnerability to extract\nthe passwords from the user database and/or the device configuration files\nto conduct further attacks." } ], "metrics": [ { "cvssV3_1": { "baseScore": 5.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:N/A:N/E:F/RL:U/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-327", "description": "CWE-327: Use of a Broken or Risky Cryptographic Algorithm", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:56:14.606Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18340", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:14.118Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18311 (GCVE-0-2019-18311)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-952 - SFP Secondary Cluster: Missing Authentication
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 7061/tcp. This vulnerability is independent from CVE-2019-18310. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:12.839Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 7061/tcp. This vulnerability is independent from CVE-2019-18310. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-952", "description": "CWE-952: SFP Secondary Cluster: Missing Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:57", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18311", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 7061/tcp. This vulnerability is independent from CVE-2019-18310. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-952: SFP Secondary Cluster: Missing Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18311", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:12.839Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13932 (GCVE-0-2019-13932)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 00:05
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-20 - Improper Input Validation
Summary
A vulnerability has been identified in XHQ (All versions < V6.0.0.2). The web application requests could be manipulated, causing the the application to behave in unexpected ways for legitimate users. Successful exploitation does not require for an attacker to be authenticated. A successful attack could allow the import of scripts or generation of malicious links. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens AG | XHQ |
Version: All versions < V6.0.0.2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T00:05:44.019Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "XHQ", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c V6.0.0.2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in XHQ (All versions \u003c V6.0.0.2). The web application requests could be manipulated, causing the the application to behave in unexpected ways for legitimate users. Successful exploitation does not require for an attacker to be authenticated. A successful attack could allow the import of scripts or generation of malicious links. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-20", "description": "CWE-20: Improper Input Validation", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2019-12-12T19:08:46", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-13932", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "XHQ", "version": { "version_data": [ { "version_value": "All versions \u003c V6.0.0.2" } ] } } ] }, "vendor_name": "Siemens AG" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in XHQ (All versions \u003c V6.0.0.2). The web application requests could be manipulated, causing the the application to behave in unexpected ways for legitimate users. Successful exploitation does not require for an attacker to be authenticated. A successful attack could allow the import of scripts or generation of malicious links. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-20: Improper Input Validation" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-13932", "datePublished": "2019-12-12T19:08:46", "dateReserved": "2019-07-18T00:00:00", "dateUpdated": "2024-08-05T00:05:44.019Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18331 (GCVE-0-2019-18331)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-200 - Exposure of Sensitive Information to an Unauthorized Actor
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to path and filenames on the server by sending specifically crafted packets to 1099/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.562Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to path and filenames on the server by sending specifically crafted packets to 1099/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-200", "description": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:32", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18331", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to path and filenames on the server by sending specifically crafted packets to 1099/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18331", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.562Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18309 (GCVE-0-2019-18309)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-284 - Improper Access Control
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with local access to the MS3000 Server and a low privileged user account could gain root privileges by manipulating specific files in the local file system. This vulnerability is independent from CVE-2019-18308. Please note that an attacker needs to have local access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:12.833Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with local access to the MS3000 Server and a low privileged user account could gain root privileges by manipulating specific files in the local file system. This vulnerability is independent from CVE-2019-18308. Please note that an attacker needs to have local access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-284", "description": "CWE-284: Improper Access Control", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:54", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18309", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with local access to the MS3000 Server and a low privileged user account could gain root privileges by manipulating specific files in the local file system. This vulnerability is independent from CVE-2019-18308. Please note that an attacker needs to have local access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-284: Improper Access Control" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18309", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:12.833Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18303 (GCVE-0-2019-18303)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-190 - Integer Overflow or Wraparound
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.192Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-190", "description": "CWE-190: Integer Overflow or Wraparound", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:43", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18303", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-190: Integer Overflow or Wraparound" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18303", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.192Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13103 (GCVE-0-2019-13103)
Vulnerability from cvelistv5
Published
2019-07-29 14:52
Modified
2024-08-04 23:41
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- n/a
Summary
A crafted self-referential DOS partition table will cause all Das U-Boot versions through 2019.07-rc4 to infinitely recurse, causing the stack to grow infinitely and eventually either crash or overwrite other data.
References
URL | Tags | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-04T23:41:10.417Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://github.com/u-boot/u-boot/commits/master" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://lists.denx.de/pipermail/u-boot/2019-July/375512.html" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://gist.github.com/deephooloovoo/d91b81a1674b4750e662dfae93804d75" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "n/a", "vendor": "n/a", "versions": [ { "status": "affected", "version": "n/a" } ] } ], "descriptions": [ { "lang": "en", "value": "A crafted self-referential DOS partition table will cause all Das U-Boot versions through 2019.07-rc4 to infinitely recurse, causing the stack to grow infinitely and eventually either crash or overwrite other data." } ], "problemTypes": [ { "descriptions": [ { "description": "n/a", "lang": "en", "type": "text" } ] } ], "providerMetadata": { "dateUpdated": "2019-12-10T13:06:03", "orgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "shortName": "mitre" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://github.com/u-boot/u-boot/commits/master" }, { "tags": [ "x_refsource_MISC" ], "url": "https://lists.denx.de/pipermail/u-boot/2019-July/375512.html" }, { "tags": [ "x_refsource_MISC" ], "url": "https://gist.github.com/deephooloovoo/d91b81a1674b4750e662dfae93804d75" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "cve@mitre.org", "ID": "CVE-2019-13103", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "n/a", "version": { "version_data": [ { "version_value": "n/a" } ] } } ] }, "vendor_name": "n/a" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A crafted self-referential DOS partition table will cause all Das U-Boot versions through 2019.07-rc4 to infinitely recurse, causing the stack to grow infinitely and eventually either crash or overwrite other data." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "n/a" } ] } ] }, "references": { "reference_data": [ { "name": "https://github.com/u-boot/u-boot/commits/master", "refsource": "MISC", "url": "https://github.com/u-boot/u-boot/commits/master" }, { "name": "https://lists.denx.de/pipermail/u-boot/2019-July/375512.html", "refsource": "MISC", "url": "https://lists.denx.de/pipermail/u-boot/2019-July/375512.html" }, { "name": "https://gist.github.com/deephooloovoo/d91b81a1674b4750e662dfae93804d75", "refsource": "MISC", "url": "https://gist.github.com/deephooloovoo/d91b81a1674b4750e662dfae93804d75" }, { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf", "refsource": "CONFIRM", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "assignerShortName": "mitre", "cveId": "CVE-2019-13103", "datePublished": "2019-07-29T14:52:02", "dateReserved": "2019-06-30T00:00:00", "dateUpdated": "2024-08-04T23:41:10.417Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13931 (GCVE-0-2019-13931)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 00:05
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-80 - Improper Neutralization of Script-Related HTML Tags in a Web Page (Basic XSS)
Summary
A vulnerability has been identified in XHQ (All versions < V6.0.0.2). The web interface could allow for an an attacker to craft the input in a form that is not expected, causing the application to behave in unexpected ways for legitimate users. Successful exploitation requires for an attacker to be authenticated to the web interface. A successful attack could cause the application to have unexpected behavior. This could allow the attacker to modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens AG | XHQ |
Version: All versions < V6.0.0.2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T00:05:44.015Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "XHQ", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c V6.0.0.2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in XHQ (All versions \u003c V6.0.0.2). The web interface could allow for an an attacker to craft the input in a form that is not expected, causing the application to behave in unexpected ways for legitimate users. Successful exploitation requires for an attacker to be authenticated to the web interface. A successful attack could cause the application to have unexpected behavior. This could allow the attacker to modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-80", "description": "CWE-80: Improper Neutralization of Script-Related HTML Tags in a Web Page (Basic XSS)", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2019-12-12T19:08:46", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-13931", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "XHQ", "version": { "version_data": [ { "version_value": "All versions \u003c V6.0.0.2" } ] } } ] }, "vendor_name": "Siemens AG" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in XHQ (All versions \u003c V6.0.0.2). The web interface could allow for an an attacker to craft the input in a form that is not expected, causing the application to behave in unexpected ways for legitimate users. Successful exploitation requires for an attacker to be authenticated to the web interface. A successful attack could cause the application to have unexpected behavior. This could allow the attacker to modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-80: Improper Neutralization of Script-Related HTML Tags in a Web Page (Basic XSS)" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-13931", "datePublished": "2019-12-12T19:08:46", "dateReserved": "2019-07-18T00:00:00", "dateUpdated": "2024-08-05T00:05:44.015Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18300 (GCVE-0-2019-18300)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-190 - Integer Overflow or Wraparound
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.212Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-190", "description": "CWE-190: Integer Overflow or Wraparound", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:38", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18300", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-190: Integer Overflow or Wraparound" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18300", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.212Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18327 (GCVE-0-2019-18327)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.389Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:25", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18327", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18327", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.389Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18319 (GCVE-0-2019-18319)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18317 and CVE-2019-18318. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.298Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18317 and CVE-2019-18318. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:12", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18319", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could cause a Denial-of-Service condition by sending specifically crafted objects via RMI. This vulnerability is independent from CVE-2019-18317 and CVE-2019-18318. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18319", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.298Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18310 (GCVE-0-2019-18310)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-121 - Stack-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 7061/tcp. This vulnerability is independent from CVE-2019-18311. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:12.814Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 7061/tcp. This vulnerability is independent from CVE-2019-18311. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-121", "description": "CWE-121: Stack-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:56", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18310", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 7061/tcp. This vulnerability is independent from CVE-2019-18311. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-121: Stack-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18310", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:12.814Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13930 (GCVE-0-2019-13930)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 00:05
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-352 - Cross-Site Request Forgery (CSRF)
Summary
A vulnerability has been identified in XHQ (All versions < V6.0.0.2). The web interface could allow a Cross-Site Request Forgery (CSRF) attack if an unsuspecting user is tricked into accessing a malicious link. Successful exploitation requires user interaction by a legitimate user, who must be authenticated to the web interface. A successful attack could allow an attacker to trigger actions via the web interface that the legitimate user is allowed to perform. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens AG | XHQ |
Version: All versions < V6.0.0.2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T00:05:43.777Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "XHQ", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c V6.0.0.2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in XHQ (All versions \u003c V6.0.0.2). The web interface could allow a Cross-Site Request Forgery (CSRF) attack if an unsuspecting user is tricked into accessing a malicious link. Successful exploitation requires user interaction by a legitimate user, who must be authenticated to the web interface. A successful attack could allow an attacker to trigger actions via the web interface that the legitimate user is allowed to perform. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-352", "description": "CWE-352: Cross-Site Request Forgery (CSRF)", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2019-12-12T19:08:46", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-13930", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "XHQ", "version": { "version_data": [ { "version_value": "All versions \u003c V6.0.0.2" } ] } } ] }, "vendor_name": "Siemens AG" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in XHQ (All versions \u003c V6.0.0.2). The web interface could allow a Cross-Site Request Forgery (CSRF) attack if an unsuspecting user is tricked into accessing a malicious link. Successful exploitation requires user interaction by a legitimate user, who must be authenticated to the web interface. A successful attack could allow an attacker to trigger actions via the web interface that the legitimate user is allowed to perform. This could allow the attacker to read or modify contents of the web application. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-352: Cross-Site Request Forgery (CSRF)" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-525454.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-13930", "datePublished": "2019-12-12T19:08:46", "dateReserved": "2019-07-18T00:00:00", "dateUpdated": "2024-08-05T00:05:43.777Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18298 (GCVE-0-2019-18298)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-190 - Integer Overflow or Wraparound
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.157Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-190", "description": "CWE-190: Integer Overflow or Wraparound", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:34", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18298", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-190: Integer Overflow or Wraparound" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18298", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.157Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18314 (GCVE-0-2019-18314)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted objects via RMI. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:12.829Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted objects via RMI. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:04", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18314", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted objects via RMI. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18314", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:12.829Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18294 (GCVE-0-2019-18294)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.156Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:27", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18294", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18305, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18294", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.156Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18332 (GCVE-0-2019-18332)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-200 - Exposure of Sensitive Information to an Unauthorized Actor
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to directory listings of the server by sending specifically crafted packets to 80/tcp, 8095/tcp or 8080/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:14.471Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to directory listings of the server by sending specifically crafted packets to 80/tcp, 8095/tcp or 8080/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-200", "description": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:34", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18332", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to directory listings of the server by sending specifically crafted packets to 80/tcp, 8095/tcp or 8080/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18332", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:14.471Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18316 (GCVE-0-2019-18316)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-502 - Deserialization of Untrusted Data
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 1099/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:12.839Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 1099/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-502", "description": "CWE-502: Deserialization of Untrusted Data", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:07", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18316", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain remote code execution by sending specifically crafted packets to 1099/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-502: Deserialization of Untrusted Data" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18316", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:12.839Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18305 (GCVE-0-2019-18305)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:47
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-190 - Integer Overflow or Wraparound
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:47:14.168Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-190", "description": "CWE-190: Integer Overflow or Wraparound", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:47", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18305", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could trigger a Denial-of-Service condition by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18290, CVE-2019-18291, CVE-2019-18292, CVE-2019-18294, CVE-2019-18298, CVE-2019-18299, CVE-2019-18300, CVE-2019-18301, CVE-2019-18302, CVE-2019-18303, CVE-2019-18304, CVE-2019-18306, and CVE-2019-18307. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-190: Integer Overflow or Wraparound" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18305", "datePublished": "2019-12-12T19:08:47", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:47:14.168Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18321 (GCVE-0-2019-18321)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to read and write arbitrary files on the local file system by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18322. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.332Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to read and write arbitrary files on the local file system by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18322. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:16", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18321", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to read and write arbitrary files on the local file system by sending specifically crafted packets to port 5010/tcp. This vulnerability is independent from CVE-2019-18322. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18321", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.332Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2018-18440 (GCVE-0-2018-18440)
Vulnerability from cvelistv5
Published
2018-11-20 19:00
Modified
2024-08-05 11:08
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- n/a
Summary
DENX U-Boot through 2018.09-rc1 has a locally exploitable buffer overflow via a crafted kernel image because filesystem loading is mishandled.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T11:08:21.824Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "name": "[oss-security] 20181102 CVE-2018-18439, CVE-2018-18440 - U-Boot verified boot bypass vulnerabilities", "tags": [ "mailing-list", "x_refsource_MLIST", "x_transferred" ], "url": "http://www.openwall.com/lists/oss-security/2018/11/02/2" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "n/a", "vendor": "n/a", "versions": [ { "status": "affected", "version": "n/a" } ] } ], "datePublic": "2018-11-02T00:00:00", "descriptions": [ { "lang": "en", "value": "DENX U-Boot through 2018.09-rc1 has a locally exploitable buffer overflow via a crafted kernel image because filesystem loading is mishandled." } ], "problemTypes": [ { "descriptions": [ { "description": "n/a", "lang": "en", "type": "text" } ] } ], "providerMetadata": { "dateUpdated": "2019-12-10T13:06:03", "orgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "shortName": "mitre" }, "references": [ { "name": "[oss-security] 20181102 CVE-2018-18439, CVE-2018-18440 - U-Boot verified boot bypass vulnerabilities", "tags": [ "mailing-list", "x_refsource_MLIST" ], "url": "http://www.openwall.com/lists/oss-security/2018/11/02/2" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "cve@mitre.org", "ID": "CVE-2018-18440", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "n/a", "version": { "version_data": [ { "version_value": "n/a" } ] } } ] }, "vendor_name": "n/a" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "DENX U-Boot through 2018.09-rc1 has a locally exploitable buffer overflow via a crafted kernel image because filesystem loading is mishandled." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "n/a" } ] } ] }, "references": { "reference_data": [ { "name": "[oss-security] 20181102 CVE-2018-18439, CVE-2018-18440 - U-Boot verified boot bypass vulnerabilities", "refsource": "MLIST", "url": "http://www.openwall.com/lists/oss-security/2018/11/02/2" }, { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf", "refsource": "CONFIRM", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-618620.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "8254265b-2729-46b6-b9e3-3dfca2d5bfca", "assignerShortName": "mitre", "cveId": "CVE-2018-18440", "datePublished": "2018-11-20T19:00:00", "dateReserved": "2018-10-17T00:00:00", "dateUpdated": "2024-08-05T11:08:21.824Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18333 (GCVE-0-2019-18333)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-200 - Exposure of Sensitive Information to an Unauthorized Actor
Summary
A vulnerability has been identified in SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to filenames on the server by sending specifically crafted packets to 8090/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 Application Server |
Version: All versions < Service Pack R8.2 SP2 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.437Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to filenames on the server by sending specifically crafted packets to 8090/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-200", "description": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:35", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18333", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). An attacker with network access to the Application Server could gain access to filenames on the server by sending specifically crafted packets to 8090/tcp. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18333", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.437Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18339 (GCVE-0-2019-18339)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-306 - Missing Authentication for Critical Function
Summary
A vulnerability has been identified in SiNVR/SiVMS Video Server (All versions < V5.0.0). The HTTP service (default port 5401/tcp) of the SiVMS/SiNVR Video Server
contains an authentication bypass vulnerability, even when properly
configured with enforced authentication.
A remote attacker with network access to the Video Server could
exploit this vulnerability to read the SiVMS/SiNVR users database, including
the passwords of all users in obfuscated cleartext.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SiNVR/SiVMS Video Server |
Version: All versions < V5.0.0 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:14.297Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "SiNVR/SiVMS Video Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V5.0.0" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SiNVR/SiVMS Video Server (All versions \u003c V5.0.0). The HTTP service (default port 5401/tcp) of the SiVMS/SiNVR Video Server\ncontains an authentication bypass vulnerability, even when properly\nconfigured with enforced authentication.\n\nA remote attacker with network access to the Video Server could \nexploit this vulnerability to read the SiVMS/SiNVR users database, including\nthe passwords of all users in obfuscated cleartext." } ], "metrics": [ { "cvssV3_1": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:F/RL:U/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-306", "description": "CWE-306: Missing Authentication for Critical Function", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:56:13.407Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18339", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:14.297Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13947 (GCVE-0-2019-13947)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 00:05
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-317 - Cleartext Storage of Sensitive Information in GUI
Summary
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The user configuration menu in the web interface of the
Control Center Server (CCS) transfers user passwords in clear to the
client (browser).
An attacker with administrative privileges for the web interface could be
able to read (and not only reset) passwords of other CCS users.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | Control Center Server (CCS) |
Version: All versions < V1.5.0 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T00:05:43.988Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "Control Center Server (CCS)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V1.5.0" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in Control Center Server (CCS) (All versions \u003c V1.5.0). The user configuration menu in the web interface of the\nControl Center Server (CCS) transfers user passwords in clear to the\nclient (browser).\n\nAn attacker with administrative privileges for the web interface could be\nable to read (and not only reset) passwords of other CCS users." } ], "metrics": [ { "cvssV3_1": { "baseScore": 4.9, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N/E:F/RL:U/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-317", "description": "CWE-317: Cleartext Storage of Sensitive Information in GUI", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:56:09.762Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-13947", "datePublished": "2019-12-12T19:08:46", "dateReserved": "2019-07-18T00:00:00", "dateUpdated": "2024-08-05T00:05:43.988Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2018-4832 (GCVE-0-2018-4832)
Vulnerability from cvelistv5
Published
2018-04-24 17:00
Modified
2024-08-05 05:18
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-20 - Improper Input Validation
Summary
A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versions), OpenPCS 7 V8.1 (All versions < V8.1 Upd5), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions < V9.0 Upd1), SIMATIC BATCH V7.1 and earlier (All versions), SIMATIC BATCH V8.0 (All versions < V8.0 SP1 Upd21), SIMATIC BATCH V8.1 (All versions < V8.1 SP1 Upd16), SIMATIC BATCH V8.2 (All versions < V8.2 Upd10), SIMATIC BATCH V9.0 (All versions < V9.0 SP1), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions < 15 SP1), SIMATIC PCS 7 V7.1 and earlier (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP1), SIMATIC Route Control V7.1 and earlier (All versions), SIMATIC Route Control V8.0 (All versions), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions < V9.0 Upd1), SIMATIC WinCC Runtime Professional V13 (All versions < V13 SP2 Upd2), SIMATIC WinCC Runtime Professional V14 (All versions < V14 SP1 Upd5), SIMATIC WinCC V7.2 and earlier (All versions < WinCC 7.2 Upd 15), SIMATIC WinCC V7.3 (All versions < WinCC 7.3 Upd 16), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 4), SPPA-T3000 Application Server (All versions < Service Pack R8.2 SP2). Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | |
---|---|---|
Impacted products
Vendor | Product | Version | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Siemens | OpenPCS 7 V7.1 and earlier |
Version: All versions |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T05:18:26.633Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-348629.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "OpenPCS 7 V7.1 and earlier", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "OpenPCS 7 V8.0", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "OpenPCS 7 V8.1", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V8.1 Upd5" } ] }, { "product": "OpenPCS 7 V8.2", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "OpenPCS 7 V9.0", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V9.0 Upd1" } ] }, { "product": "SIMATIC BATCH V7.1 and earlier", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC BATCH V8.0", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V8.0 SP1 Upd21" } ] }, { "product": "SIMATIC BATCH V8.1", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V8.1 SP1 Upd16" } ] }, { "product": "SIMATIC BATCH V8.2", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V8.2 Upd10" } ] }, { "product": "SIMATIC BATCH V9.0", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V9.0 SP1" } ] }, { "product": "SIMATIC NET PC Software V14", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V14 SP1 Update 14" } ] }, { "product": "SIMATIC NET PC Software V15", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c 15 SP1" } ] }, { "product": "SIMATIC PCS 7 V7.1 and earlier", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC PCS 7 V8.0", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC PCS 7 V8.1", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC PCS 7 V8.2", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V8.2 SP1" } ] }, { "product": "SIMATIC PCS 7 V9.0", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V9.0 SP1" } ] }, { "product": "SIMATIC Route Control V7.1 and earlier", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC Route Control V8.0", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC Route Control V8.1", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC Route Control V8.2", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC Route Control V9.0", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V9.0 Upd1" } ] }, { "product": "SIMATIC WinCC Runtime Professional V13", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V13 SP2 Upd2" } ] }, { "product": "SIMATIC WinCC Runtime Professional V14", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V14 SP1 Upd5" } ] }, { "product": "SIMATIC WinCC V7.2 and earlier", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c WinCC 7.2 Upd 15" } ] }, { "product": "SIMATIC WinCC V7.3", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c WinCC 7.3 Upd 16" } ] }, { "product": "SIMATIC WinCC V7.4", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V7.4 SP1 Upd 4" } ] }, { "product": "SPPA-T3000 Application Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c Service Pack R8.2 SP2" } ] } ], "datePublic": "2018-03-27T00:00:00", "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versions), OpenPCS 7 V8.1 (All versions \u003c V8.1 Upd5), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions \u003c V9.0 Upd1), SIMATIC BATCH V7.1 and earlier (All versions), SIMATIC BATCH V8.0 (All versions \u003c V8.0 SP1 Upd21), SIMATIC BATCH V8.1 (All versions \u003c V8.1 SP1 Upd16), SIMATIC BATCH V8.2 (All versions \u003c V8.2 Upd10), SIMATIC BATCH V9.0 (All versions \u003c V9.0 SP1), SIMATIC NET PC Software V14 (All versions \u003c V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions \u003c 15 SP1), SIMATIC PCS 7 V7.1 and earlier (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions \u003c V8.2 SP1), SIMATIC PCS 7 V9.0 (All versions \u003c V9.0 SP1), SIMATIC Route Control V7.1 and earlier (All versions), SIMATIC Route Control V8.0 (All versions), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions \u003c V9.0 Upd1), SIMATIC WinCC Runtime Professional V13 (All versions \u003c V13 SP2 Upd2), SIMATIC WinCC Runtime Professional V14 (All versions \u003c V14 SP1 Upd5), SIMATIC WinCC V7.2 and earlier (All versions \u003c WinCC 7.2 Upd 15), SIMATIC WinCC V7.3 (All versions \u003c WinCC 7.3 Upd 16), SIMATIC WinCC V7.4 (All versions \u003c V7.4 SP1 Upd 4), SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-20", "description": "CWE-20: Improper Input Validation", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-04-12T09:06:48", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-348629.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2018-4832", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "OpenPCS 7 V7.1 and earlier", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "OpenPCS 7 V8.0", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "OpenPCS 7 V8.1", "version": { "version_data": [ { "version_value": "All versions \u003c V8.1 Upd5" } ] } }, { "product_name": "OpenPCS 7 V8.2", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "OpenPCS 7 V9.0", "version": { "version_data": [ { "version_value": "All versions \u003c V9.0 Upd1" } ] } }, { "product_name": "SIMATIC BATCH V7.1 and earlier", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC BATCH V8.0", "version": { "version_data": [ { "version_value": "All versions \u003c V8.0 SP1 Upd21" } ] } }, { "product_name": "SIMATIC BATCH V8.1", "version": { "version_data": [ { "version_value": "All versions \u003c V8.1 SP1 Upd16" } ] } }, { "product_name": "SIMATIC BATCH V8.2", "version": { "version_data": [ { "version_value": "All versions \u003c V8.2 Upd10" } ] } }, { "product_name": "SIMATIC BATCH V9.0", "version": { "version_data": [ { "version_value": "All versions \u003c V9.0 SP1" } ] } }, { "product_name": "SIMATIC NET PC Software V14", "version": { "version_data": [ { "version_value": "All versions \u003c V14 SP1 Update 14" } ] } }, { "product_name": "SIMATIC NET PC Software V15", "version": { "version_data": [ { "version_value": "All versions \u003c 15 SP1" } ] } }, { "product_name": "SIMATIC PCS 7 V7.1 and earlier", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC PCS 7 V8.0", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC PCS 7 V8.1", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC PCS 7 V8.2", "version": { "version_data": [ { "version_value": "All versions \u003c V8.2 SP1" } ] } }, { "product_name": "SIMATIC PCS 7 V9.0", "version": { "version_data": [ { "version_value": "All versions \u003c V9.0 SP1" } ] } }, { "product_name": "SIMATIC Route Control V7.1 and earlier", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC Route Control V8.0", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC Route Control V8.1", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC Route Control V8.2", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC Route Control V9.0", "version": { "version_data": [ { "version_value": "All versions \u003c V9.0 Upd1" } ] } }, { "product_name": "SIMATIC WinCC Runtime Professional V13", "version": { "version_data": [ { "version_value": "All versions \u003c V13 SP2 Upd2" } ] } }, { "product_name": "SIMATIC WinCC Runtime Professional V14", "version": { "version_data": [ { "version_value": "All versions \u003c V14 SP1 Upd5" } ] } }, { "product_name": "SIMATIC WinCC V7.2 and earlier", "version": { "version_data": [ { "version_value": "All versions \u003c WinCC 7.2 Upd 15" } ] } }, { "product_name": "SIMATIC WinCC V7.3", "version": { "version_data": [ { "version_value": "All versions \u003c WinCC 7.3 Upd 16" } ] } }, { "product_name": "SIMATIC WinCC V7.4", "version": { "version_data": [ { "version_value": "All versions \u003c V7.4 SP1 Upd 4" } ] } }, { "product_name": "SPPA-T3000 Application Server", "version": { "version_data": [ { "version_value": "All versions \u003c Service Pack R8.2 SP2" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in OpenPCS 7 V7.1 and earlier (All versions), OpenPCS 7 V8.0 (All versions), OpenPCS 7 V8.1 (All versions \u003c V8.1 Upd5), OpenPCS 7 V8.2 (All versions), OpenPCS 7 V9.0 (All versions \u003c V9.0 Upd1), SIMATIC BATCH V7.1 and earlier (All versions), SIMATIC BATCH V8.0 (All versions \u003c V8.0 SP1 Upd21), SIMATIC BATCH V8.1 (All versions \u003c V8.1 SP1 Upd16), SIMATIC BATCH V8.2 (All versions \u003c V8.2 Upd10), SIMATIC BATCH V9.0 (All versions \u003c V9.0 SP1), SIMATIC NET PC Software V14 (All versions \u003c V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions \u003c 15 SP1), SIMATIC PCS 7 V7.1 and earlier (All versions), SIMATIC PCS 7 V8.0 (All versions), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions \u003c V8.2 SP1), SIMATIC PCS 7 V9.0 (All versions \u003c V9.0 SP1), SIMATIC Route Control V7.1 and earlier (All versions), SIMATIC Route Control V8.0 (All versions), SIMATIC Route Control V8.1 (All versions), SIMATIC Route Control V8.2 (All versions), SIMATIC Route Control V9.0 (All versions \u003c V9.0 Upd1), SIMATIC WinCC Runtime Professional V13 (All versions \u003c V13 SP2 Upd2), SIMATIC WinCC Runtime Professional V14 (All versions \u003c V14 SP1 Upd5), SIMATIC WinCC V7.2 and earlier (All versions \u003c WinCC 7.2 Upd 15), SIMATIC WinCC V7.3 (All versions \u003c WinCC 7.3 Upd 16), SIMATIC WinCC V7.4 (All versions \u003c V7.4 SP1 Upd 4), SPPA-T3000 Application Server (All versions \u003c Service Pack R8.2 SP2). Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality. Please note that an attacker needs to have network access to the Application Server in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-20: Improper Input Validation" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" }, { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-348629.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-348629.pdf" }, { "name": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html", "refsource": "MISC", "url": "http://packetstormsecurity.com/files/155665/Siemens-Security-Advisory-SPPA-T3000-Code-Execution.html" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2018-4832", "datePublished": "2018-04-24T17:00:00", "dateReserved": "2018-01-02T00:00:00", "dateUpdated": "2024-08-05T05:18:26.633Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-10929 (GCVE-0-2019-10929)
Vulnerability from cvelistv5
Published
2019-08-13 18:55
Modified
2024-08-04 22:40
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-327 - Use of a Broken or Risky Cryptographic Algorithm
Summary
A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.8.1), SIMATIC S7-1500 Software Controller (All versions < V20.8), SIMATIC S7-PLCSIM Advanced (All versions < V3.0), SIMATIC STEP 7 (TIA Portal) (All versions < V16), SIMATIC WinCC (TIA Portal) (All versions < V16), SIMATIC WinCC OA (All versions < V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions < V16), SIMATIC WinCC Runtime Professional (All versions < V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions < V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices.
References
URL | Tags | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
|
Impacted products
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-04T22:40:15.230Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-232418.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-273799.pdf" }, { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-04" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SIMATIC CP 1626", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V20.8" } ] }, { "product": "SIMATIC HMI Panel (incl. SIPLUS variants)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC NET PC Software V14", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V14 SP1 Update 14" } ] }, { "product": "SIMATIC NET PC Software V15", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V4.4.0" } ] }, { "product": "SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.8.1" } ] }, { "product": "SIMATIC S7-1500 Software Controller", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V20.8" } ] }, { "product": "SIMATIC S7-PLCSIM Advanced", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.0" } ] }, { "product": "SIMATIC STEP 7 (TIA Portal)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V16" } ] }, { "product": "SIMATIC WinCC (TIA Portal)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V16" } ] }, { "product": "SIMATIC WinCC OA", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V3.16 P013" } ] }, { "product": "SIMATIC WinCC Runtime Advanced", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V16" } ] }, { "product": "SIMATIC WinCC Runtime Professional", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V16" } ] }, { "product": "TIM 1531 IRC (incl. SIPLUS NET variants)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V2.1" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions \u003c V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions \u003c V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions \u003c V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions \u003c V2.8.1), SIMATIC S7-1500 Software Controller (All versions \u003c V20.8), SIMATIC S7-PLCSIM Advanced (All versions \u003c V3.0), SIMATIC STEP 7 (TIA Portal) (All versions \u003c V16), SIMATIC WinCC (TIA Portal) (All versions \u003c V16), SIMATIC WinCC OA (All versions \u003c V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions \u003c V16), SIMATIC WinCC Runtime Professional (All versions \u003c V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions \u003c V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-327", "description": "CWE-327: Use of a Broken or Risky Cryptographic Algorithm", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-08-10T11:16:07", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-232418.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-273799.pdf" }, { "tags": [ "x_refsource_MISC" ], "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-04" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-10929", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SIMATIC CP 1626", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)", "version": { "version_data": [ { "version_value": "All versions \u003c V20.8" } ] } }, { "product_name": "SIMATIC HMI Panel (incl. SIPLUS variants)", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC NET PC Software V14", "version": { "version_data": [ { "version_value": "All versions \u003c V14 SP1 Update 14" } ] } }, { "product_name": "SIMATIC NET PC Software V15", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)", "version": { "version_data": [ { "version_value": "All versions \u003c V4.4.0" } ] } }, { "product_name": "SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)", "version": { "version_data": [ { "version_value": "All versions \u003c V2.8.1" } ] } }, { "product_name": "SIMATIC S7-1500 Software Controller", "version": { "version_data": [ { "version_value": "All versions \u003c V20.8" } ] } }, { "product_name": "SIMATIC S7-PLCSIM Advanced", "version": { "version_data": [ { "version_value": "All versions \u003c V3.0" } ] } }, { "product_name": "SIMATIC STEP 7 (TIA Portal)", "version": { "version_data": [ { "version_value": "All versions \u003c V16" } ] } }, { "product_name": "SIMATIC WinCC (TIA Portal)", "version": { "version_data": [ { "version_value": "All versions \u003c V16" } ] } }, { "product_name": "SIMATIC WinCC OA", "version": { "version_data": [ { "version_value": "All versions \u003c V3.16 P013" } ] } }, { "product_name": "SIMATIC WinCC Runtime Advanced", "version": { "version_data": [ { "version_value": "All versions \u003c V16" } ] } }, { "product_name": "SIMATIC WinCC Runtime Professional", "version": { "version_data": [ { "version_value": "All versions \u003c V16" } ] } }, { "product_name": "TIM 1531 IRC (incl. SIPLUS NET variants)", "version": { "version_data": [ { "version_value": "All versions \u003c V2.1" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SIMATIC CP 1626 (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions \u003c V20.8), SIMATIC HMI Panel (incl. SIPLUS variants) (All versions), SIMATIC NET PC Software V14 (All versions \u003c V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions \u003c V4.4.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions \u003c V2.8.1), SIMATIC S7-1500 Software Controller (All versions \u003c V20.8), SIMATIC S7-PLCSIM Advanced (All versions \u003c V3.0), SIMATIC STEP 7 (TIA Portal) (All versions \u003c V16), SIMATIC WinCC (TIA Portal) (All versions \u003c V16), SIMATIC WinCC OA (All versions \u003c V3.16 P013), SIMATIC WinCC Runtime Advanced (All versions \u003c V16), SIMATIC WinCC Runtime Professional (All versions \u003c V16), TIM 1531 IRC (incl. SIPLUS NET variants) (All versions \u003c V2.1). Affected devices contain a message protection bypass vulnerability due to certain properties in the calculation used for integrity protection. This could allow an attacker in a Man-in-the-Middle position to modify network traffic sent on port 102/tcp to the affected devices." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-327: Use of a Broken or Risky Cryptographic Algorithm" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-232418.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-232418.pdf" }, { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-273799.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-273799.pdf" }, { "name": "https://www.us-cert.gov/ics/advisories/icsa-19-344-04", "refsource": "MISC", "url": "https://www.us-cert.gov/ics/advisories/icsa-19-344-04" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-10929", "datePublished": "2019-08-13T18:55:57", "dateReserved": "2019-04-08T00:00:00", "dateUpdated": "2024-08-04T22:40:15.230Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18326 (GCVE-0-2019-18326)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:14.095Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:24", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18326", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18327, CVE-2019-18328, CVE-2019-18329, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18326", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:14.095Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18313 (GCVE-0-2019-18313)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-434 - Unrestricted Upload of File with Dangerous Type
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could gain remote code execution by sending specifically crafted objects to one of the RPC services. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.298Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could gain remote code execution by sending specifically crafted objects to one of the RPC services. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-434", "description": "CWE-434: Unrestricted Upload of File with Dangerous Type", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:01", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18313", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could gain remote code execution by sending specifically crafted objects to one of the RPC services. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-434: Unrestricted Upload of File with Dangerous Type" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18313", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.298Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18329 (GCVE-0-2019-18329)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-122 - Heap-based Buffer Overflow
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.454Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-122", "description": "CWE-122: Heap-based Buffer Overflow", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:52:29", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18329", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server can cause a Denial-of-Service condition and potentially gain remote code execution by sending specifically crafted packets to 5010/tcp. This vulnerability is independent from CVE-2019-18323, CVE-2019-18324, CVE-2019-18325, CVE-2019-18326, CVE-2019-18327, CVE-2019-18328, and CVE-2019-18330. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-122: Heap-based Buffer Overflow" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18329", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.454Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18342 (GCVE-0-2019-18342)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-749 - Exposed Dangerous Method or Function
Summary
A vulnerability has been identified in Control Center Server (CCS) (All versions < V1.5.0). The SFTP service (default port 22/tcp) of the Control Center Server
(CCS) does not properly limit its capabilities to the specified purpose.
In conjunction with CVE-2019-18341, an unauthenticated remote attacker with
network access to the CCS server could exploit this vulnerability
to read or delete arbitrary files, or access other resources on the same
server.
References
URL | Tags | |||||||
---|---|---|---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | Control Center Server (CCS) |
Version: All versions < V1.5.0 |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:13.423Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "defaultStatus": "unknown", "product": "Control Center Server (CCS)", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions \u003c V1.5.0" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in Control Center Server (CCS) (All versions \u003c V1.5.0). The SFTP service (default port 22/tcp) of the Control Center Server\n(CCS) does not properly limit its capabilities to the specified purpose.\n\nIn conjunction with CVE-2019-18341, an unauthenticated remote attacker with\nnetwork access to the CCS server could exploit this vulnerability\nto read or delete arbitrary files, or access other resources on the same\nserver." } ], "metrics": [ { "cvssV3_1": { "baseScore": 9.9, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:F/RL:U/RC:C", "version": "3.1" } } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-749", "description": "CWE-749: Exposed Dangerous Method or Function", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2024-01-09T09:56:17.087Z", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761617.pdf" }, { "tags": [ "x_refsource_CONFIRM" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-761844.pdf" } ] } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18342", "datePublished": "2019-12-12T19:08:49", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:13.423Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-18312 (GCVE-0-2019-18312)
Vulnerability from cvelistv5
Published
2019-12-12 19:08
Modified
2024-08-05 01:54
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-287 - Improper Authentication
Summary
A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to enumerate running RPC services. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | ||
---|---|---|---|---|
Siemens | SPPA-T3000 MS3000 Migration Server |
Version: All versions |
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T01:54:12.859Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SPPA-T3000 MS3000 Migration Server", "vendor": "Siemens", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to enumerate running RPC services. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-287", "description": "CWE-287: Improper Authentication", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2022-02-22T17:51:59", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-18312", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SPPA-T3000 MS3000 Migration Server", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SPPA-T3000 MS3000 Migration Server (All versions). An attacker with network access to the MS3000 Server could be able to enumerate running RPC services. Please note that an attacker needs to have network access to the MS3000 in order to exploit this vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-287: Improper Authentication" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-451445.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-18312", "datePublished": "2019-12-12T19:08:48", "dateReserved": "2019-10-23T00:00:00", "dateUpdated": "2024-08-05T01:54:12.859Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
CVE-2019-13945 (GCVE-0-2019-13945)
Vulnerability from cvelistv5
Published
2019-12-12 13:19
Modified
2024-08-05 00:05
Severity ?
VLAI Severity ?
EPSS score ?
CWE
- CWE-749 - Exposed Dangerous Method or Function
Summary
A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family < V4.x (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants) (All versions with Function State (FS) < 11), SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR40 (6ES7 288-1CR40-0AA0) (All versions <= V2.2.2 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU CR40s (6ES7 288-1CR40-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR60 (6ES7 288-1CR60-0AA0) (All versions <= V2.2.2 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU CR60s (6ES7 288-1CR60-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU SR20 (6ES7 288-1SR20-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 11), SIMATIC S7-200 SMART CPU SR30 (6ES7 288-1SR30-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU SR40 (6ES7 288-1SR40-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 10), SIMATIC S7-200 SMART CPU SR60 (6ES7 288-1SR60-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 12), SIMATIC S7-200 SMART CPU ST20 (6ES7 288-1ST20-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 9), SIMATIC S7-200 SMART CPU ST30 (6ES7 288-1ST30-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 9), SIMATIC S7-200 SMART CPU ST40 (6ES7 288-1ST40-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU ST60 (6ES7 288-1ST60-0AA0) (All versions <= V2.5.0 and Function State (FS) <= 8), SIMATIC S7-200 SMART CPU family (All versions). There is an access mode used during manufacturing of the affected devices that allows additional diagnostic functionality. The security vulnerability could be exploited by an attacker with physical access to the UART interface during boot process.
References
URL | Tags | ||||
---|---|---|---|---|---|
|
Impacted products
Vendor | Product | Version | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Siemens AG | SIMATIC S7-1200 CPU family (incl. SIPLUS variants) |
Version: All versions |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
{ "containers": { "adp": [ { "providerMetadata": { "dateUpdated": "2024-08-05T00:05:44.067Z", "orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE" }, "references": [ { "tags": [ "x_refsource_MISC", "x_transferred" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-686531.pdf" } ], "title": "CVE Program Container" } ], "cna": { "affected": [ { "product": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC S7-1200 CPU family \u003c V4.x (incl. SIPLUS variants)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] }, { "product": "SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions with Function State (FS) \u003c 11" } ] }, { "product": "SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3" } ] }, { "product": "SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3" } ] }, { "product": "SIMATIC S7-200 SMART CPU CR40 (6ES7 288-1CR40-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.2.2 and Function State (FS) \u003c= 8" } ] }, { "product": "SIMATIC S7-200 SMART CPU CR40s (6ES7 288-1CR40-0AA1)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3" } ] }, { "product": "SIMATIC S7-200 SMART CPU CR60 (6ES7 288-1CR60-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.2.2 and Function State (FS) \u003c= 10" } ] }, { "product": "SIMATIC S7-200 SMART CPU CR60s (6ES7 288-1CR60-0AA1)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3" } ] }, { "product": "SIMATIC S7-200 SMART CPU SR20 (6ES7 288-1SR20-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 11" } ] }, { "product": "SIMATIC S7-200 SMART CPU SR30 (6ES7 288-1SR30-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 10" } ] }, { "product": "SIMATIC S7-200 SMART CPU SR40 (6ES7 288-1SR40-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 10" } ] }, { "product": "SIMATIC S7-200 SMART CPU SR60 (6ES7 288-1SR60-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 12" } ] }, { "product": "SIMATIC S7-200 SMART CPU ST20 (6ES7 288-1ST20-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 9" } ] }, { "product": "SIMATIC S7-200 SMART CPU ST30 (6ES7 288-1ST30-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 9" } ] }, { "product": "SIMATIC S7-200 SMART CPU ST40 (6ES7 288-1ST40-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 8" } ] }, { "product": "SIMATIC S7-200 SMART CPU ST60 (6ES7 288-1ST60-0AA0)", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 8" } ] }, { "product": "SIMATIC S7-200 SMART CPU family", "vendor": "Siemens AG", "versions": [ { "status": "affected", "version": "All versions" } ] } ], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family \u003c V4.x (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants) (All versions with Function State (FS) \u003c 11), SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1) (All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3), SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1) (All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3), SIMATIC S7-200 SMART CPU CR40 (6ES7 288-1CR40-0AA0) (All versions \u003c= V2.2.2 and Function State (FS) \u003c= 8), SIMATIC S7-200 SMART CPU CR40s (6ES7 288-1CR40-0AA1) (All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3), SIMATIC S7-200 SMART CPU CR60 (6ES7 288-1CR60-0AA0) (All versions \u003c= V2.2.2 and Function State (FS) \u003c= 10), SIMATIC S7-200 SMART CPU CR60s (6ES7 288-1CR60-0AA1) (All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3), SIMATIC S7-200 SMART CPU SR20 (6ES7 288-1SR20-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 11), SIMATIC S7-200 SMART CPU SR30 (6ES7 288-1SR30-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 10), SIMATIC S7-200 SMART CPU SR40 (6ES7 288-1SR40-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 10), SIMATIC S7-200 SMART CPU SR60 (6ES7 288-1SR60-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 12), SIMATIC S7-200 SMART CPU ST20 (6ES7 288-1ST20-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 9), SIMATIC S7-200 SMART CPU ST30 (6ES7 288-1ST30-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 9), SIMATIC S7-200 SMART CPU ST40 (6ES7 288-1ST40-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 8), SIMATIC S7-200 SMART CPU ST60 (6ES7 288-1ST60-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 8), SIMATIC S7-200 SMART CPU family (All versions). There is an access mode used during manufacturing of the affected devices that allows additional diagnostic functionality. The security vulnerability could be exploited by an attacker with physical access to the UART interface during boot process." } ], "problemTypes": [ { "descriptions": [ { "cweId": "CWE-749", "description": "CWE-749: Exposed Dangerous Method or Function", "lang": "en", "type": "CWE" } ] } ], "providerMetadata": { "dateUpdated": "2020-07-14T13:18:04", "orgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "shortName": "siemens" }, "references": [ { "tags": [ "x_refsource_MISC" ], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-686531.pdf" } ], "x_legacyV4Record": { "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-13945", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC S7-1200 CPU family \u003c V4.x (incl. SIPLUS variants)", "version": { "version_data": [ { "version_value": "All versions" } ] } }, { "product_name": "SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants)", "version": { "version_data": [ { "version_value": "All versions with Function State (FS) \u003c 11" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU CR40 (6ES7 288-1CR40-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.2.2 and Function State (FS) \u003c= 8" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU CR40s (6ES7 288-1CR40-0AA1)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU CR60 (6ES7 288-1CR60-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.2.2 and Function State (FS) \u003c= 10" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU CR60s (6ES7 288-1CR60-0AA1)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU SR20 (6ES7 288-1SR20-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 11" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU SR30 (6ES7 288-1SR30-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 10" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU SR40 (6ES7 288-1SR40-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 10" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU SR60 (6ES7 288-1SR60-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 12" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU ST20 (6ES7 288-1ST20-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 9" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU ST30 (6ES7 288-1ST30-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 9" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU ST40 (6ES7 288-1ST40-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 8" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU ST60 (6ES7 288-1ST60-0AA0)", "version": { "version_data": [ { "version_value": "All versions \u003c= V2.5.0 and Function State (FS) \u003c= 8" } ] } }, { "product_name": "SIMATIC S7-200 SMART CPU family", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] }, "vendor_name": "Siemens AG" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family \u003c V4.x (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants) (All versions with Function State (FS) \u003c 11), SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1) (All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3), SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1) (All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3), SIMATIC S7-200 SMART CPU CR40 (6ES7 288-1CR40-0AA0) (All versions \u003c= V2.2.2 and Function State (FS) \u003c= 8), SIMATIC S7-200 SMART CPU CR40s (6ES7 288-1CR40-0AA1) (All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3), SIMATIC S7-200 SMART CPU CR60 (6ES7 288-1CR60-0AA0) (All versions \u003c= V2.2.2 and Function State (FS) \u003c= 10), SIMATIC S7-200 SMART CPU CR60s (6ES7 288-1CR60-0AA1) (All versions \u003c= V2.3.0 and Function State (FS) \u003c= 3), SIMATIC S7-200 SMART CPU SR20 (6ES7 288-1SR20-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 11), SIMATIC S7-200 SMART CPU SR30 (6ES7 288-1SR30-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 10), SIMATIC S7-200 SMART CPU SR40 (6ES7 288-1SR40-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 10), SIMATIC S7-200 SMART CPU SR60 (6ES7 288-1SR60-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 12), SIMATIC S7-200 SMART CPU ST20 (6ES7 288-1ST20-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 9), SIMATIC S7-200 SMART CPU ST30 (6ES7 288-1ST30-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 9), SIMATIC S7-200 SMART CPU ST40 (6ES7 288-1ST40-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 8), SIMATIC S7-200 SMART CPU ST60 (6ES7 288-1ST60-0AA0) (All versions \u003c= V2.5.0 and Function State (FS) \u003c= 8), SIMATIC S7-200 SMART CPU family (All versions). There is an access mode used during manufacturing of the affected devices that allows additional diagnostic functionality. The security vulnerability could be exploited by an attacker with physical access to the UART interface during boot process." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-749: Exposed Dangerous Method or Function" } ] } ] }, "references": { "reference_data": [ { "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-686531.pdf", "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-686531.pdf" } ] } } } }, "cveMetadata": { "assignerOrgId": "cec7a2ec-15b4-4faf-bd53-b40f371f3a77", "assignerShortName": "siemens", "cveId": "CVE-2019-13945", "datePublished": "2019-12-12T13:19:51", "dateReserved": "2019-07-18T00:00:00", "dateUpdated": "2024-08-05T00:05:44.067Z", "state": "PUBLISHED" }, "dataType": "CVE_RECORD", "dataVersion": "5.1" }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…