icsa-22-046-01
Vulnerability from csaf_cisa
Published
2022-02-15 00:00
Modified
2022-02-15 00:00
Summary
Schneider Electric IGSS
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could result in a variety of issues, including disclosure of data and loss of control of the SCADA system with IGSS running in production mode.
Critical infrastructure sectors
Commercial Facilities, Critical Manufacturing, Energy
Countries/areas deployed
Worldwide
Company headquarters location
France
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target these vulnerabilities.
{ "document": { "acknowledgments": [ { "organization": "Tenable", "summary": "independently reporting to Schneider Electric and CISA by Tenable, and by Vyacheslav Moskvin working with Trend Micro \u0027s Zero Day Initiative" }, { "names": [ "Vyacheslav Moskvin" ], "organization": "Trend Micro \u0027s Zero Day Initiative", "summary": "independently reporting to Schneider Electric and CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of these vulnerabilities could result in a variety of issues, including disclosure of data and loss of control of the SCADA system with IGSS running in production mode.", "title": "Risk evaluation" }, { "category": "other", "text": "Commercial Facilities, Critical Manufacturing, Energy", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "France", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "other", "text": "No known public exploits specifically target these vulnerabilities.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "ICS Advisory ICSA-22-046-01 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-046-01.json" }, { "category": "self", "summary": "ICS Advisory ICSA-22-046-01 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-046-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Schneider Electric IGSS", "tracking": { "current_release_date": "2022-02-15T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-22-046-01", "initial_release_date": "2022-02-15T00:00:00.000000Z", "revision_history": [ { "date": "2022-02-15T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-22-046-01 Schneider Electric IGSS" } ], "status": "final", "version": "1" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c= 15.0.0.22020", "product": { "name": "IGSS Data Server (IGSSdataServer.exe): v15.0.0.22020 and prior", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "IGSS Data Server (IGSSdataServer.exe)" } ], "category": "vendor", "name": "Schneider Electric Software, LLC" } ] }, "vulnerabilities": [ { "cve": "CVE-2022-24310", "cwe": { "id": "CWE-190", "name": "Integer Overflow or Wraparound" }, "notes": [ { "category": "summary", "text": "A vulnerability exists that could cause heap-based buffer overflow, leading to denial of service and potentially remote code execution when an attacker sends multiple specially crafted messages.CVE-2022-24310 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-24310" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Version 15.0.0.22021 of IGSS Data Server includes corrections for these vulnerabilities and is available for download through IGSS Master \u003e Update IGSS Software.", "product_ids": [ "CSAFPID-0001" ], "url": "https://igss.schneider-electric.com/igss/igssupdates/v150/IGSSUPDATE.ZIP" }, { "category": "mitigation", "details": "Schneider Electric recommends users use appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center for assistance removing a patch.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.se.com/us/en/work/support/contacts.jsp" }, { "category": "mitigation", "details": "If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Follow the general security recommendations below and verify devices are isolated on a private network and that firewalls are configured with strict boundaries for devices that require remote access.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the network.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never connect programming software to any network other than the network intended for that device.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc., before use in the terminals or any node connected to these networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information see Schneider Electric\u0027s security notification: SEVD-2022-039-01", "product_ids": [ "CSAFPID-0001" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2022-24311", "cwe": { "id": "CWE-22", "name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)" }, "notes": [ { "category": "summary", "text": "A vulnerability exists that could cause modification of an existing file by inserting data at the beginning of the file or creating a new file in the context of the data server. This could potentially lead to remote code execution when an attacker sends a specially crafted message.CVE-2022-24311 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-24311" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Version 15.0.0.22021 of IGSS Data Server includes corrections for these vulnerabilities and is available for download through IGSS Master \u003e Update IGSS Software.", "product_ids": [ "CSAFPID-0001" ], "url": "https://igss.schneider-electric.com/igss/igssupdates/v150/IGSSUPDATE.ZIP" }, { "category": "mitigation", "details": "Schneider Electric recommends users use appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center for assistance removing a patch.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.se.com/us/en/work/support/contacts.jsp" }, { "category": "mitigation", "details": "If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Follow the general security recommendations below and verify devices are isolated on a private network and that firewalls are configured with strict boundaries for devices that require remote access.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the network.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never connect programming software to any network other than the network intended for that device.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc., before use in the terminals or any node connected to these networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information see Schneider Electric\u0027s security notification: SEVD-2022-039-01", "product_ids": [ "CSAFPID-0001" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2022-24312", "cwe": { "id": "CWE-22", "name": "Improper Limitation of a Pathname to a Restricted Directory (\u0027Path Traversal\u0027)" }, "notes": [ { "category": "summary", "text": "A vulnerability exists that could cause modification of an existing file by adding data at the end of the file or creating a new file in the context of the data server. This could potentially lead to remote code execution when an attacker sends a specially crafted message.CVE-2022-24312 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-24312" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Version 15.0.0.22021 of IGSS Data Server includes corrections for these vulnerabilities and is available for download through IGSS Master \u003e Update IGSS Software.", "product_ids": [ "CSAFPID-0001" ], "url": "https://igss.schneider-electric.com/igss/igssupdates/v150/IGSSUPDATE.ZIP" }, { "category": "mitigation", "details": "Schneider Electric recommends users use appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center for assistance removing a patch.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.se.com/us/en/work/support/contacts.jsp" }, { "category": "mitigation", "details": "If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Follow the general security recommendations below and verify devices are isolated on a private network and that firewalls are configured with strict boundaries for devices that require remote access.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the network.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never connect programming software to any network other than the network intended for that device.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc., before use in the terminals or any node connected to these networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information see Schneider Electric\u0027s security notification: SEVD-2022-039-01", "product_ids": [ "CSAFPID-0001" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2022-24313", "cwe": { "id": "CWE-120", "name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)" }, "notes": [ { "category": "summary", "text": "A vulnerability exists that could cause a stack-based buffer overflow potentially leading to remote code execution when an attacker sends a specially crafted message.CVE-2022-24313 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-24313" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Version 15.0.0.22021 of IGSS Data Server includes corrections for these vulnerabilities and is available for download through IGSS Master \u003e Update IGSS Software.", "product_ids": [ "CSAFPID-0001" ], "url": "https://igss.schneider-electric.com/igss/igssupdates/v150/IGSSUPDATE.ZIP" }, { "category": "mitigation", "details": "Schneider Electric recommends users use appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center for assistance removing a patch.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.se.com/us/en/work/support/contacts.jsp" }, { "category": "mitigation", "details": "If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Follow the general security recommendations below and verify devices are isolated on a private network and that firewalls are configured with strict boundaries for devices that require remote access.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the network.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never connect programming software to any network other than the network intended for that device.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc., before use in the terminals or any node connected to these networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information see Schneider Electric\u0027s security notification: SEVD-2022-039-01", "product_ids": [ "CSAFPID-0001" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01" } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2022-24314", "cwe": { "id": "CWE-125", "name": "Out-of-bounds Read" }, "notes": [ { "category": "summary", "text": "A vulnerability exists that could cause memory leaks potentially resulting in denial of service when an attacker repeatedly sends a specially crafted message.CVE-2022-24314 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-24314" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Version 15.0.0.22021 of IGSS Data Server includes corrections for these vulnerabilities and is available for download through IGSS Master \u003e Update IGSS Software.", "product_ids": [ "CSAFPID-0001" ], "url": "https://igss.schneider-electric.com/igss/igssupdates/v150/IGSSUPDATE.ZIP" }, { "category": "mitigation", "details": "Schneider Electric recommends users use appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center for assistance removing a patch.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.se.com/us/en/work/support/contacts.jsp" }, { "category": "mitigation", "details": "If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Follow the general security recommendations below and verify devices are isolated on a private network and that firewalls are configured with strict boundaries for devices that require remote access.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the network.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never connect programming software to any network other than the network intended for that device.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc., before use in the terminals or any node connected to these networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information see Schneider Electric\u0027s security notification: SEVD-2022-039-01", "product_ids": [ "CSAFPID-0001" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2022-24315", "cwe": { "id": "CWE-125", "name": "Out-of-bounds Read" }, "notes": [ { "category": "summary", "text": "A vulnerability exists that could cause denial of service when an attacker repeatedly sends a specially crafted message.CVE-2022-24315 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-24315" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "Version 15.0.0.22021 of IGSS Data Server includes corrections for these vulnerabilities and is available for download through IGSS Master \u003e Update IGSS Software.", "product_ids": [ "CSAFPID-0001" ], "url": "https://igss.schneider-electric.com/igss/igssupdates/v150/IGSSUPDATE.ZIP" }, { "category": "mitigation", "details": "Schneider Electric recommends users use appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center for assistance removing a patch.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.se.com/us/en/work/support/contacts.jsp" }, { "category": "mitigation", "details": "If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Follow the general security recommendations below and verify devices are isolated on a private network and that firewalls are configured with strict boundaries for devices that require remote access.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the network.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never connect programming software to any network other than the network intended for that device.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc., before use in the terminals or any node connected to these networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information see Schneider Electric\u0027s security notification: SEVD-2022-039-01", "product_ids": [ "CSAFPID-0001" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01" } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2022-24316", "cwe": { "id": "CWE-665", "name": "Improper Initialization" }, "notes": [ { "category": "summary", "text": "A vulnerability exists that could cause information exposure when an attacker sends a specially crafted message.CVE-2022-24316 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-24316" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "Version 15.0.0.22021 of IGSS Data Server includes corrections for these vulnerabilities and is available for download through IGSS Master \u003e Update IGSS Software.", "product_ids": [ "CSAFPID-0001" ], "url": "https://igss.schneider-electric.com/igss/igssupdates/v150/IGSSUPDATE.ZIP" }, { "category": "mitigation", "details": "Schneider Electric recommends users use appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center for assistance removing a patch.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.se.com/us/en/work/support/contacts.jsp" }, { "category": "mitigation", "details": "If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Follow the general security recommendations below and verify devices are isolated on a private network and that firewalls are configured with strict boundaries for devices that require remote access.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the network.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never connect programming software to any network other than the network intended for that device.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc., before use in the terminals or any node connected to these networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information see Schneider Electric\u0027s security notification: SEVD-2022-039-01", "product_ids": [ "CSAFPID-0001" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01" } ], "scores": [ { "cvss_v3": { "baseScore": 5.3, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] }, { "cve": "CVE-2022-24317", "cwe": { "id": "CWE-862", "name": "Missing Authorization" }, "notes": [ { "category": "summary", "text": "A vulnerability exists that could cause information exposure when an attacker sends a specific message.CVE-2022-24317 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).", "title": "Vulnerability Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001" ] }, "references": [ { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-24317" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "Version 15.0.0.22021 of IGSS Data Server includes corrections for these vulnerabilities and is available for download through IGSS Master \u003e Update IGSS Software.", "product_ids": [ "CSAFPID-0001" ], "url": "https://igss.schneider-electric.com/igss/igssupdates/v150/IGSSUPDATE.ZIP" }, { "category": "mitigation", "details": "Schneider Electric recommends users use appropriate patching methodologies when applying these patches to their systems. They strongly recommend the use of back-ups and evaluating the impact of these patches in a test and development environment or on an offline infrastructure. Contact Schneider Electric\u0027s Customer Care Center for assistance removing a patch.", "product_ids": [ "CSAFPID-0001" ], "url": "https://www.se.com/us/en/work/support/contacts.jsp" }, { "category": "mitigation", "details": "If users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Follow the general security recommendations below and verify devices are isolated on a private network and that firewalls are configured with strict boundaries for devices that require remote access.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the network.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never connect programming software to any network other than the network intended for that device.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc., before use in the terminals or any node connected to these networks.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "Minimize network exposure for all control system devices and systems and ensure they are not accessible from the Internet.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "When remote access is required, use secure methods, such as virtual private networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "For more information see Schneider Electric\u0027s security notification: SEVD-2022-039-01", "product_ids": [ "CSAFPID-0001" ], "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2022-039-01" } ], "scores": [ { "cvss_v3": { "baseScore": 5.3, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N", "version": "3.0" }, "products": [ "CSAFPID-0001" ] } ] } ] }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…