icsa-21-194-02
Vulnerability from csaf_cisa
Published
2021-07-13 00:00
Modified
2021-07-27 00:00
Summary
Schneider Electric Modicon Controllers and Software (Update A)

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities may allow arbitrary code execution and loss of confidentiality and integrity of the project file.
Critical infrastructure sectors
Commercial Facilities, Energy, Food and Agriculture, Government Facilities, Transportation Systems, Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
France
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also recommends users take the following measures to protect themselves from social engineering attacks:
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target these vulnerabilities.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "Kai Wang"
        ],
        "organization": "Fortinet\u0027s FortiGuard Labs",
        "summary": "reporting these vulnerabilities to Schneider Electric"
      },
      {
        "names": [
          "Andrey Muravitsky"
        ],
        "organization": "Kaspersky",
        "summary": "reporting these vulnerabilities to Schneider Electric"
      },
      {
        "names": [
          "Gal Kauffman"
        ],
        "organization": "Armis",
        "summary": "reporting these vulnerabilities to Schneider Electric"
      },
      {
        "names": [
          "Nicholas Miles"
        ],
        "organization": "Tenable",
        "summary": "reporting these vulnerabilities to Schneider Electric"
      },
      {
        "names": [
          "Li Wei"
        ],
        "organization": "Friday Lab - Bolean Tech",
        "summary": "reporting these vulnerabilities to Schneider Electric"
      },
      {
        "names": [
          "Maxim Tumakov",
          "Artem Zinenko"
        ],
        "organization": "Kaspersky",
        "summary": "reporting these vulnerabilities to Schneider Electric"
      },
      {
        "names": [
          "Kai Wang"
        ],
        "organization": "Codesafe Team of Legendsec at Qi\u0027anxin Group",
        "summary": "reporting these vulnerabilities to Schneider Electric"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities may allow arbitrary code execution and loss of confidentiality and integrity of the project file.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Commercial Facilities, Energy, Food and Agriculture, Government Facilities, Transportation Systems, Water and Wastewater Systems",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "France",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also recommends users take the following measures to protect themselves from social engineering attacks:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target these vulnerabilities.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-194-02 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2021/icsa-21-194-02.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-21-194-02 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-21-194-02"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/ncas/tips/ST04-014"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Schneider Electric Modicon Controllers and Software (Update A)",
    "tracking": {
      "current_release_date": "2021-07-27T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-21-194-02",
      "initial_release_date": "2021-07-13T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2021-07-13T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-21-194-02 Schneider Electric SCADApack RTU, Modicon Controllers, and Software"
        },
        {
          "date": "2021-07-27T00:00:00.000000Z",
          "legacy_version": "A",
          "number": "2",
          "summary": "ICSA-21-194-02 Schneider Electric Modicon Controllers and Software (Update A)"
        }
      ],
      "status": "final",
      "version": "2"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "EcoStruxure Process Expert: all versions Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert)",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure Process Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "15.0 SP1",
                "product": {
                  "name": "EcoStruxure Control Expert: v15.0 SP1",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure Control Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "Modicon M340 CPU (part numbers BMXP34*): all versions",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M340 CPU (part numbers BMXP34*)"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "Modicon M580 CPU (part numbers BMEP* and BMEH*): all versions",
                  "product_id": "CSAFPID-0004"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU (part numbers BMEP* and BMEH*)"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:all/*",
                "product": {
                  "name": "SCADAPack RemoteConnect for x70: all versions",
                  "product_id": "CSAFPID-0005"
                }
              }
            ],
            "category": "product_name",
            "name": "SCADAPack RemoteConnect for x70"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c 15.0 SP1",
                "product": {
                  "name": "EcoStruxure Control Expert: all versions prior to v15.0 SP1 Including all versions of Unity Pro (former name of EcoStruxure Control Expert)",
                  "product_id": "CSAFPID-0006"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure Control Expert"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric Software, LLC"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2021-22778",
      "cwe": {
        "id": "CWE-522",
        "name": "Insufficiently Protected Credentials"
      },
      "notes": [
        {
          "category": "summary",
          "text": "An insufficiently protected credentials vulnerability exists that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file. CVE-2021-22778 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H).. --------- Begin Update A Part 2 of 2 --------CVE-2021-22778 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-22778"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Schneider Electric provides detailed mitigation information for each of the affected products in their own advisory, for more information about these issues, please refer to the original Schneider Electric publication SEVD-2021-194-01.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ],
          "url": "http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-194-01"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.6,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-22779",
      "cwe": {
        "id": "CWE-290",
        "name": "Authentication Bypass by Spoofing"
      },
      "notes": [
        {
          "category": "summary",
          "text": "An authentication bypass by spoofing vulnerability exists that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. CVE-2021-22779 has been assigned to this vulnerability. A CVSS v3 base score of 9.8has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).. --------- End Update A Part 2 of 2 --------CVE-2021-22779 has been assigned to this vulnerability. A CVSS v3 base score of 9.8has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-22779"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Schneider Electric provides detailed mitigation information for each of the affected products in their own advisory, for more information about these issues, please refer to the original Schneider Electric publication SEVD-2021-194-01.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ],
          "url": "http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-194-01"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2020-12525",
      "cwe": {
        "id": "CWE-502",
        "name": "Deserialization of Untrusted Data"
      },
      "notes": [
        {
          "category": "summary",
          "text": "M\u0026M Software fdtCONTAINER component in versions below 3.5.20304.x and between 3.6 and 3.6.20304.x is vulnerable to deserialization of untrusted data in its project storage.\nNote: This vulnerability could cause local code execution on the engineering workstation when a malicious project file is loaded into the engineering software.CVE-2020-12525 has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H).\n",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-12525"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Schneider Electric provides detailed mitigation information for each of the affected products in their own advisory, for more information about these issues, please refer to the original Schneider Electric publication SEVD-2021-194-01.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ],
          "url": "http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-194-01"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.3,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-22780",
      "cwe": {
        "id": "CWE-522",
        "name": "Insufficiently Protected Credentials"
      },
      "notes": [
        {
          "category": "summary",
          "text": "An insufficiently protected credentials vulnerability exists that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources. An attacker may bypass the password protection and be able to view and modify a project file.CVE-2021-22780 has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N).\n",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-22780"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Schneider Electric provides detailed mitigation information for each of the affected products in their own advisory, for more information about these issues, please refer to the original Schneider Electric publication SEVD-2021-194-01.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ],
          "url": "http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-194-01"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-22781",
      "cwe": {
        "id": "CWE-522",
        "name": "Insufficiently Protected Credentials"
      },
      "notes": [
        {
          "category": "summary",
          "text": "An insufficiently protected credentials vulnerability exists that could cause a leak of SMTP credentials used for mailbox authentication when an attacker can access a project file.CVE-2021-22781 has been assigned to this vulnerability. A CVSS v3 base score of 6.2 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).\n",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-22781"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Schneider Electric provides detailed mitigation information for each of the affected products in their own advisory, for more information about these issues, please refer to the original Schneider Electric publication SEVD-2021-194-01.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ],
          "url": "http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-194-01"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.2,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2021-22782",
      "cwe": {
        "id": "CWE-311",
        "name": "Missing Encryption of Sensitive Data"
      },
      "notes": [
        {
          "category": "summary",
          "text": "A missing encryption of sensitive data vulnerability exists that could cause an information leak allowing disclosure of network and process information, credentials, or intellectual property when an attacker can access a project file.CVE-2021-22782 has been assigned to this vulnerability. A CVSS v3 base score of 6.2 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003",
          "CSAFPID-0004",
          "CSAFPID-0005",
          "CSAFPID-0006"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-22782"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Schneider Electric provides detailed mitigation information for each of the affected products in their own advisory, for more information about these issues, please refer to the original Schneider Electric publication SEVD-2021-194-01.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ],
          "url": "http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2021-194-01"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.2,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.0/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003",
            "CSAFPID-0004",
            "CSAFPID-0005",
            "CSAFPID-0006"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.