icsa-21-131-04
Vulnerability from csaf_cisa
Published
2021-05-11 00:00
Modified
2021-08-10 00:00
Summary
Siemens SINAMICS Medium Voltage Products Remote Access (Update B)
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could allow an attacker to gain full remote access to the HMI.
Critical infrastructure sectors
Chemical, Commercial Facilities, Critical Manufacturing, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
CISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Exploitability
No known public exploits specifically target these vulnerabilities. These vulnerabilities have ahigh attack complexity.
{ "document": { "acknowledgments": [ { "organization": "Siemens", "summary": "reporting this vulnerability to CISA" } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov", "title": "CISA Disclaimer" }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "summary", "text": "Successful exploitation of this vulnerability could allow an attacker to gain full remote access to the HMI.", "title": "Risk evaluation" }, { "category": "other", "text": "Chemical, Commercial Facilities, Critical Manufacturing, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, Water and Wastewater Systems", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "Germany", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nCISA also provides a section for control systems security recommended practices on the ICS webpage onus-cert.cisa.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage on us-cert.cisa.gov in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" }, { "category": "general", "text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories", "title": "Additional Resources" }, { "category": "other", "text": "No known public exploits specifically target these vulnerabilities. These vulnerabilities have ahigh attack complexity.", "title": "Exploitability" } ], "publisher": { "category": "coordinator", "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "external", "summary": "SSA-286838: Multiple Vulnerabilities in SINAMICS Medium Voltage Products - CSAF Version", "url": "https://cert-portal.siemens.com/productcert/csaf/ssa-286838.json" }, { "category": "self", "summary": "ICS Advisory ICSA-21-131-04 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2021/icsa-21-131-04.json" }, { "category": "self", "summary": "ICS Advisory ICSA-21-131-04 Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-21-131-04" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/ics/tips/ICS-TIP-12-146-01B" }, { "category": "external", "summary": "SSA-286838: Multiple Vulnerabilities in SINAMICS Medium Voltage Products - PDF Version", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-286838.pdf" }, { "category": "external", "summary": "SSA-286838: Multiple Vulnerabilities in SINAMICS Medium Voltage Products - TXT Version", "url": "https://cert-portal.siemens.com/productcert/txt/ssa-286838.txt" } ], "title": "Siemens SINAMICS Medium Voltage Products Remote Access (Update B)", "tracking": { "current_release_date": "2021-08-10T00:00:00.000000Z", "generator": { "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-21-131-04", "initial_release_date": "2021-05-11T00:00:00.000000Z", "revision_history": [ { "date": "2021-05-11T00:00:00.000000Z", "legacy_version": "Initial", "number": "1", "summary": "ICSA-21-131-04 Siemens SINAMICS Medium Voltage Products Remote Access" }, { "date": "2021-06-08T00:00:00.000000Z", "legacy_version": "A", "number": "2", "summary": "ICSA-21-131-04 Siemens SINAMICS Medium Voltage Products Remote Access (Update A)" }, { "date": "2021-08-10T00:00:00.000000Z", "legacy_version": "B", "number": "3", "summary": "ICSA-21-131-04 Siemens SINAMICS Medium Voltage Products Remote Access (Update B)" } ], "status": "final", "version": "3" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINAMICS GH150", "product_id": "CSAFPID-0001" } } ], "category": "product_name", "name": "SINAMICS GH150" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINAMICS GL150 (with option X30)", "product_id": "CSAFPID-0002" } } ], "category": "product_name", "name": "SINAMICS GL150 (with option X30)" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINAMICS GM150 (with option X30)", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "SINAMICS GM150 (with option X30)" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINAMICS SH150", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "SINAMICS SH150" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINAMICS SL150", "product_id": "CSAFPID-0005" } } ], "category": "product_name", "name": "SINAMICS SL150" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINAMICS SM120", "product_id": "CSAFPID-0006" } } ], "category": "product_name", "name": "SINAMICS SM120" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINAMICS SM150", "product_id": "CSAFPID-0007" } } ], "category": "product_name", "name": "SINAMICS SM150" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "SINAMICS SM150i", "product_id": "CSAFPID-0008" } } ], "category": "product_name", "name": "SINAMICS SM150i" } ], "category": "vendor", "name": "Siemens" } ] }, "vulnerabilities": [ { "cve": "CVE-2019-8259", "cwe": { "id": "CWE-665", "name": "Improper Initialization" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1198 contains multiple memory leaks in VNC client code, which could allow an attacker to read stack memory and can be abused for information disclosure. Combined with another vulnerability, it can be used to leak stack memory and bypass ASLR. This vulnerability appears to be exploitable via network connectivity. These vulnerabilities have been fixed in revision 1199.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8259 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8259.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8259" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8259" }, { "cve": "CVE-2019-8260", "cwe": { "id": "CWE-125", "name": "Out-of-bounds Read" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1199 has a out-of-bounds read vulnerability in VNC client RRE decoder code, caused by multiplication overflow. This vulnerability appears to be exploitable via network connectivity. This vulnerability has been fixed in revision 1200.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8260 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8260.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8260" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8260" }, { "cve": "CVE-2019-8261", "cwe": { "id": "CWE-125", "name": "Out-of-bounds Read" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1199 has a out-of-bounds read vulnerability in VNC code inside client CoRRE decoder, caused by multiplication overflow. This vulnerability appears to be exploitable via network connectivity. This vulnerability has been fixed in revision 1200.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8261 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8261.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8261" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8261" }, { "cve": "CVE-2019-8262", "cwe": { "id": "CWE-122", "name": "Heap-based Buffer Overflow" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1203 has multiple heap buffer overflow vulnerabilities in VNC client code inside Ultra decoder, which could result in code execution. This vulnerability appears to be exploitable via network connectivity. These vulnerabilities have been fixed in revision 1204.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8262 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8262.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8262" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8262" }, { "cve": "CVE-2019-8263", "cwe": { "id": "CWE-121", "name": "Stack-based Buffer Overflow" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1205 has a stack-based buffer overflow vulnerability in VNC client code inside ShowConnInfo routine, which could lead to a denial of service (DoS) condition. This vulnerability appear to be exploitable via network connectivity. User interaction is required to trigger this vulnerability. This vulnerability has been fixed in revision 1206.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8263 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8263.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8263" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 6.5, "baseSeverity": "MEDIUM", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8263" }, { "cve": "CVE-2019-8264", "cwe": { "id": "CWE-788", "name": "Access of Memory Location After End of Buffer" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1203 has a out-of-bounds access vulnerability in VNC client inside Ultra2 decoder, which can potentially result in code execution. This vulnerability appears to be exploitable via network connectivity. This vulnerability has been fixed in revision 1204.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8264 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8264.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8264" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8264" }, { "cve": "CVE-2019-8265", "cwe": { "id": "CWE-788", "name": "Access of Memory Location After End of Buffer" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1207 has multiple out-of-bounds access vulnerabilities connected with improper usage of SETPIXELS macro in VNC client code, which can potentially result in code execution. This vulnerability appears to be exploitable via network connectivity. These vulnerabilities have been fixed in revision 1208.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8265 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8265.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8265" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8265" }, { "cve": "CVE-2019-8275", "cwe": { "id": "CWE-170", "name": "Improper Null Termination" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1211 has multiple improper null termination vulnerabilities in VNC server code, which could result in out-of-bound data being accessed by remote users. This vulnerability appears to be exploitable via network connectivity. These vulnerabilities have been fixed in revision 1212.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8275 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8275.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8275" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8275" }, { "cve": "CVE-2019-8277", "cwe": { "id": "CWE-665", "name": "Improper Initialization" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1211 contains multiple memory leaks in VNC server code, which could allow an attacker to read stack memory and can be abused for information disclosure. Combined with another vulnerability, it can be used to leak stack memory and bypass ASLR. This vulnerability appears to be exploitable via network connectivity. These vulnerabilities have been fixed in revision 1212.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8277 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8277.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8277" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8277" }, { "cve": "CVE-2019-8280", "cwe": { "id": "CWE-788", "name": "Access of Memory Location After End of Buffer" }, "notes": [ { "category": "summary", "text": "UltraVNC revision 1203 has out-of-bounds access vulnerability in VNC client inside RAW decoder, which can potentially result in code execution. This vulnerability appear to be exploitable via network connectivity. This vulnerability has been fixed in revision 1204.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2019-8280 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-8280.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-8280" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2019-8280" }, { "cve": "CVE-2021-27383", "cwe": { "id": "CWE-770", "name": "Allocation of Resources Without Limits or Throttling" }, "notes": [ { "category": "summary", "text": "SmartVNC has a heap allocation leak vulnerability in the server Tight encoder, which could result in a Denial-of-Service condition.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2021-27383 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-27383.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-27383" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2021-27383" }, { "cve": "CVE-2021-27384", "cwe": { "id": "CWE-788", "name": "Access of Memory Location After End of Buffer" }, "notes": [ { "category": "summary", "text": "SmartVNC has an out-of-bounds memory access vulnerability in the device layout handler, represented by a binary data stream on client side, which can potentially result in code execution.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2021-27384 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-27384.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-27384" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 9.8, "baseSeverity": "CRITICAL", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2021-27384" }, { "cve": "CVE-2021-27385", "cwe": { "id": "CWE-400", "name": "Uncontrolled Resource Consumption" }, "notes": [ { "category": "summary", "text": "A remote attacker could send specially crafted packets to SmartVNC device layout handler on client side, which could influence the amount of resources consumed and result in a Denial-of-Service (infinite loop) condition.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2021-27385 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-27385.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-27385" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2021-27385" }, { "cve": "CVE-2021-27386", "cwe": { "id": "CWE-401", "name": "Missing Release of Memory after Effective Lifetime" }, "notes": [ { "category": "summary", "text": "SmartVNC has a heap allocation leak vulnerability in the device layout handler on client side, which could result in a Denial-of-Service condition.", "title": "Summary" } ], "product_status": { "known_affected": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, "references": [ { "summary": "CVE-2021-27386 Mitre 5.0 json", "url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-27386.json" }, { "category": "external", "summary": "web.nvd.nist.gov", "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2021-27386" }, { "category": "external", "summary": "www.first.org", "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" } ], "remediations": [ { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0001" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109746530/", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0006" ] }, { "category": "none_available", "details": "Currently no remediation is available", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GL150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0002" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS GM150 (with option X30) to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0003" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SH150 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0004" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SL150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0005" ] }, { "category": "mitigation", "details": "https://support.industry.siemens.com/cs/ww/en/view/109763890/", "product_ids": [ "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V16 Update 4 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM120 to V16 Update 4 or later version", "product_ids": [ "CSAFPID-0006" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150 to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0007" ] }, { "category": "mitigation", "details": "As only SIMATIC HMI image versions \u003c V15 SP1 Update 6 are affected, please update the HMI Panel image as included in your installation of SINAMICS SM150i to V15 SP1 Update 6 or later version", "product_ids": [ "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Restrict access to port 5900/tcp to trusted IP addresses only", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Disable Sm@rtServer in the SIMATIC HMI Comfort Panels system component of SINAMICS. If this is not possible, Defense-in-Depth should be used. Note: By default Sm@rtServer is disabled, but it can be enabled on request by the system integrator", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "Follow SINAMICS MV Industrial Security guidelines", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "For any questions regarding update, please contact Siemens customer service or your system integrator.", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] }, { "category": "mitigation", "details": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity", "product_ids": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "scores": [ { "cvss_v3": { "baseScore": 7.5, "baseSeverity": "HIGH", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:O/RC:C", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0002", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008" ] } ], "title": "CVE-2021-27386" } ] }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.