ssa-693555
Vulnerability from csaf_siemens
Published
2022-06-14 00:00
Modified
2022-06-14 00:00
Summary
SSA-693555: Memory Corruption Vulnerability in EN100 Ethernet Module
Notes
Summary
EN100 Ethernet module is affected by memory corruption vulnerability (CVE-2022-30937).
Siemens has released an update for the EN100 Ethernet module IEC 61850 variant and recommends to update to the latest version. Siemens recommends specific countermeasures for products where updates are not, or not yet available.
General Recommendations
Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.
Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.
As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Recommended security guidelines can be found at:
https://www.siemens.com/gridsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.
{
"document": {
"acknowledgments": [
{
"names": [
"Michael Messner"
],
"organization": "Siemens Energy",
"summary": "reporting the vulnerabilities"
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited.",
"tlp": {
"label": "WHITE"
}
},
"notes": [
{
"category": "summary",
"text": "EN100 Ethernet module is affected by memory corruption vulnerability (CVE-2022-30937).\n\nSiemens has released an update for the EN100 Ethernet module IEC 61850 variant and recommends to update to the latest version. Siemens recommends specific countermeasures for products where updates are not, or not yet available.",
"title": "Summary"
},
{
"category": "general",
"text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\n\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.\n\nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-693555: Memory Corruption Vulnerability in EN100 Ethernet Module - PDF Version",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-693555.pdf"
},
{
"category": "self",
"summary": "SSA-693555: Memory Corruption Vulnerability in EN100 Ethernet Module - TXT Version",
"url": "https://cert-portal.siemens.com/productcert/txt/ssa-693555.txt"
},
{
"category": "self",
"summary": "SSA-693555: Memory Corruption Vulnerability in EN100 Ethernet Module - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-693555.json"
}
],
"title": "SSA-693555: Memory Corruption Vulnerability in EN100 Ethernet Module",
"tracking": {
"current_release_date": "2022-06-14T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-693555",
"initial_release_date": "2022-06-14T00:00:00Z",
"revision_history": [
{
"date": "2022-06-14T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "EN100 Ethernet module DNP3 IP variant",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "EN100 Ethernet module DNP3 IP variant"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "EN100 Ethernet module IEC 104 variant",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "EN100 Ethernet module IEC 104 variant"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c V4.37",
"product": {
"name": "EN100 Ethernet module IEC 61850 variant",
"product_id": "3"
}
}
],
"category": "product_name",
"name": "EN100 Ethernet module IEC 61850 variant"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "EN100 Ethernet module Modbus TCP variant",
"product_id": "4"
}
}
],
"category": "product_name",
"name": "EN100 Ethernet module Modbus TCP variant"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "EN100 Ethernet module PROFINET IO variant",
"product_id": "5"
}
}
],
"category": "product_name",
"name": "EN100 Ethernet module PROFINET IO variant"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2022-30937",
"cwe": {
"id": "CWE-119",
"name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
},
"notes": [
{
"category": "summary",
"text": "Affected applications contains a memory corruption vulnerability while parsing specially crafted HTTP packets to /txtrace endpoint. This could allow an attacker to crash the affected application leading to a denial of service condition.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1",
"2",
"3",
"4",
"5"
]
},
"references": [
{
"summary": "CVE-2022-30937 - EN100 Ethernet module IEC 61850 variant",
"url": "https://support.industry.siemens.com/cs/us/en/view/109745821/"
},
{
"summary": "CVE-2022-30937 Mitre 5.0 json",
"url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2022-30937.json"
}
],
"remediations": [
{
"category": "no_fix_planned",
"details": "Currently no fix is planned",
"product_ids": [
"1",
"2",
"4",
"5"
]
},
{
"category": "vendor_fix",
"details": "Update to V4.37 or later version",
"product_ids": [
"3"
],
"url": "https://support.industry.siemens.com/cs/us/en/view/109745821/"
},
{
"category": "mitigation",
"details": "Disable web service within the device configuration if it is not used",
"product_ids": [
"1",
"2",
"3",
"4",
"5"
]
},
{
"category": "workaround",
"details": "Block access to port 80/tcp and 443/tcp e.g. with an external firewall",
"product_ids": [
"1",
"2",
"3",
"4",
"5"
]
},
{
"category": "workaround",
"details": "Apply secure substation concept and Defense-in-Depth (see https://www.siemens.com/gridsecurity) or contact customer care to find specific solutions",
"product_ids": [
"1",
"2",
"3",
"4",
"5"
]
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 8.6,
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H/E:P/RL:O/RC:C",
"version": "3.1"
},
"products": [
"1",
"2",
"3",
"4",
"5"
]
}
],
"title": "CVE-2022-30937"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…