Hitachi Energy RTU500 Series Product (Update A)

Notes

Summary
Hitachi Energy is aware of the vulnerability CVE-2024-2617 in the RTU500 Web server component, that affects the RTU500 versions that are listed below. An attacker successfully exploiting this vulnerability could bypass secure update. Please refer to the Recommended Immediate Actions for information about the available mitigation/remediation strategies.
Notice
The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Energy. Hitachi Energy provides no warranty, express or implied, including warran-ties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall Hitachi Energy or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software de-scribed in this document, even if Hitachi Energy or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from Hitachi Energy and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners.
General Mitigation Factors/Workarounds
Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.
Support
For additional information and support please contact your product provider or Hitachi Energy service organization. For contact information, see https://www.hitachienergy.com/contact-us/ for Hitachi Energy contact-centers.
Legal Notice and Terms of Use
This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Advisory Conversion Disclaimer
This ICSA is a verbatim republication of Hitachi Energy PSIRT 8DBD000199 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Hitachi Energy PSIRT directly for any questions regarding this advisory.
Critical infrastructure sectors
Energy
Countries/areas deployed
Worldwide
Company headquarters location
Switzerland
Recommended Practices
CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.



{
  "document": {
    "acknowledgments": [
      {
        "organization": "Hitachi Energy PSIRT",
        "summary": "reporting this vulnerability to CISA."
      }
    ],
    "aggregate_severity": {
      "namespace": "https://www.first.org/cvss/specification-document",
      "text": "HIGH"
    },
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "summary",
        "text": "Hitachi Energy is aware of the vulnerability CVE-2024-2617 in the RTU500 Web server component, that affects the RTU500 versions that are listed below. An attacker successfully exploiting this vulnerability could bypass secure update. Please refer to the Recommended Immediate Actions for information about the available mitigation/remediation strategies.",
        "title": "Summary"
      },
      {
        "category": "legal_disclaimer",
        "text": "The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Energy. Hitachi Energy provides no warranty, express or implied, including warran-ties of merchantability and fitness for a particular purpose, for the information contained in this document, and assumes no responsibility for any errors that may appear in this document. In no event shall Hitachi Energy or any of its suppliers be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, or from the use of any hardware or software de-scribed in this document, even if Hitachi Energy or its suppliers have been advised of the possibility of such damages. This document and parts hereof must not be reproduced or copied without written permission from Hitachi Energy and the contents hereof must not be imparted to a third party nor used for any unauthorized purpose. All rights to registrations and trademarks reside with their respective owners.",
        "title": "Notice"
      },
      {
        "category": "general",
        "text": "Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.",
        "title": "General Mitigation Factors/Workarounds"
      },
      {
        "category": "other",
        "text": "For additional information and support please contact your product provider or Hitachi Energy service organization. For contact information, see https://www.hitachienergy.com/contact-us/ for Hitachi Energy contact-centers.",
        "title": "Support"
      },
      {
        "category": "legal_disclaimer",
        "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy \u0026 Use policy (https://www.cisa.gov/privacy-policy).",
        "title": "Legal Notice and Terms of Use"
      },
      {
        "category": "other",
        "text": "This ICSA is a verbatim republication of Hitachi Energy PSIRT 8DBD000199 from a direct conversion of the vendor\u0027s Common Security Advisory Framework (CSAF) advisory. This is republished to CISA\u0027s website as a means of increasing visibility and is provided \"as-is\" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory.  Further, CISA does not endorse any commercial product or service.  Please contact Hitachi Energy PSIRT directly for any questions regarding this advisory.",
        "title": "Advisory Conversion Disclaimer"
      },
      {
        "category": "other",
        "text": "Energy",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Switzerland",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "other",
      "contact_details": "central@cisa.dhs.gov",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-25-023-02 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2025/icsa-25-023-02.json"
      },
      {
        "category": "self",
        "summary": "CYBERSECURITY ADVISORY - Secure Update Bypass Vulnerability in Hitachi Energy\u2019s RTU500 series Product",
        "url": "https://publisher.hitachienergy.com/preview?DocumentId=8DBD000199\u0026languageCode=en\u0026Preview=true"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-25-023-02 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-023-02"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b"
      }
    ],
    "title": "Hitachi Energy RTU500 Series Product (Update A)",
    "tracking": {
      "current_release_date": "2025-09-09T10:00:00.000000Z",
      "generator": {
        "date": "2025-09-23T20:54:23.059816Z",
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-25-023-02",
      "initial_release_date": "2024-04-30T12:30:00.000000Z",
      "revision_history": [
        {
          "date": "2024-04-30T12:30:00.000000Z",
          "number": "1",
          "summary": "Initial version."
        },
        {
          "date": "2025-09-09T10:00:00.000000Z",
          "number": "2",
          "summary": "Updated fixed versions 13.5.4 and 13.7.7"
        }
      ],
      "status": "final",
      "version": "2"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003e=13.2.1|\u003c=13.2.7",
                "product": {
                  "name": "RTU500 series CMU Firmware versions 13.2.1 to 13.2.7",
                  "product_id": "CSAFPID-0001"
                }
              },
              {
                "category": "product_version_range",
                "name": "\u003e=13.4.1|\u003c=13.4.4",
                "product": {
                  "name": "RTU500 series CMU Firmware versions 13.4.1 to 13.4.4",
                  "product_id": "CSAFPID-0002"
                }
              },
              {
                "category": "product_version_range",
                "name": "\u003e=13.5.1|\u003c=13.5.3",
                "product": {
                  "name": "RTU500 series CMU Firmware versions 13.5.1 to 13.5.3",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_family",
            "name": "RTU500 series CMU Firmware"
          }
        ],
        "category": "vendor",
        "name": "Hitachi Energy"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2024-2617",
      "cwe": {
        "id": "CWE-358",
        "name": "Improperly Implemented Security Check for Standard"
      },
      "notes": [
        {
          "category": "description",
          "text": "A vulnerability exists in the RTU500 that allows for authenticated and authorized users to bypass secure update. If a malicious actor successfully exploits this vulnerability, they could use it to update the RTU500 with unsigned firmware",
          "title": "CVE description"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "NVD - CVE-2024-2377",
          "url": "https://nvd.nist.gov/vuln/detail/CVE-2024-2617"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to CMU Firmware version 13.7.7 and enable secure update feature on all CMUs of an RTU500",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to CMU Firmware version 13.5.4 and enable secure update feature on all CMUs of an RTU500",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 7.2,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 7.2,
            "environmentalSeverity": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "HIGH",
            "scope": "UNCHANGED",
            "temporalScore": 7.2,
            "temporalSeverity": "HIGH",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2024-2617"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.


Loading…