ICSA-22-179-06
Vulnerability from csaf_cisa - Published: 2022-06-28 00:00 - Updated: 2022-06-28 00:00Summary
Motorola Solutions ACE1000
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow an attacker to manipulate the RTU configuration, cause a denial-of-service condition, or achieve remote code execution.
Critical infrastructure sectors
Multiple
Countries/areas deployed
Worldwide
Company headquarters location
United States
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Exploitability
No known public exploits specifically target these vulnerabilities.
{
"document": {
"acknowledgments": [
{
"names": [
"Daniel dos Santos",
"Jos Wetzels"
],
"organization": "Forescout Technologies",
"summary": "reporting these vulnerabilities to CISA"
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited",
"tlp": {
"label": "WHITE",
"url": "https://us-cert.cisa.gov/tlp/"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
"title": "CISA Disclaimer"
},
{
"category": "legal_disclaimer",
"text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
"title": "Legal Notice"
},
{
"category": "summary",
"text": "Successful exploitation of these vulnerabilities could allow an attacker to manipulate the RTU configuration, cause a denial-of-service condition, or achieve remote code execution.",
"title": "Risk evaluation"
},
{
"category": "other",
"text": "Multiple",
"title": "Critical infrastructure sectors"
},
{
"category": "other",
"text": "Worldwide",
"title": "Countries/areas deployed"
},
{
"category": "other",
"text": "United States",
"title": "Company headquarters location"
},
{
"category": "general",
"text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should:",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
"title": "Recommended Practices"
},
{
"category": "other",
"text": "No known public exploits specifically target these vulnerabilities.",
"title": "Exploitability"
}
],
"publisher": {
"category": "coordinator",
"contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
"name": "CISA",
"namespace": "https://www.cisa.gov/"
},
"references": [
{
"category": "self",
"summary": "ICS Advisory ICSA-22-179-06 JSON",
"url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-179-06.json"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-22-179-06 Web Version",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-179-06"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-179-06"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
}
],
"title": "Motorola Solutions ACE1000",
"tracking": {
"current_release_date": "2022-06-28T00:00:00.000000Z",
"generator": {
"engine": {
"name": "CISA CSAF Generator",
"version": "1.0.0"
}
},
"id": "ICSA-22-179-06",
"initial_release_date": "2022-06-28T00:00:00.000000Z",
"revision_history": [
{
"date": "2022-06-28T00:00:00.000000Z",
"legacy_version": "Initial",
"number": "1",
"summary": "Publication Date"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version",
"name": "vers:all/*",
"product": {
"name": "Motorola Solutions ACE1000: All versions",
"product_id": "CSAFPID-0001"
}
}
],
"category": "product_name",
"name": "Motorola Solutions ACE1000"
}
],
"category": "vendor",
"name": "Motorola Solutions"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2022-30271",
"cwe": {
"id": "CWE-321",
"name": "Use of Hard-coded Cryptographic Key"
},
"notes": [
{
"category": "summary",
"text": "The affected product ships with a hardcoded SSH private key and initialization scripts (such as /etc/init.d/sshd_service) only generate a new key if no such file yet exists. As such, this hard-coded key is likely to be used by default. This could allow an attacker to remotely execute code, manipulate configuration, or cause a denial-of-service condition.CVE-2022-30271 has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H).",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-30271"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "While individual remediation steps are specified, note all vulnerabilities listed above can be resolved by upgrading the ACE1000 to MC-EDGE intelligent RTU.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_xp/products/industrial-internet-of-things/scada-systems/mc-edge.html#tabproductinfo"
},
{
"category": "mitigation",
"details": "CVE-2022-30271: To remediate, manually rotate the private key using the \u201cACE1000 SSH Key Rotation\u201d process.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "For user guide and procedural information mentioned within this report, use the Contact Us form and select \u201cOther\u201d for Product Interest and request the manual for IoT products.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_us/contact-us-form.html"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 9.1,
"baseSeverity": "CRITICAL",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0001"
]
}
]
},
{
"cve": "CVE-2022-30270",
"cwe": {
"id": "CWE-798",
"name": "Use of Hard-coded Credentials"
},
"notes": [
{
"category": "summary",
"text": "The affected product SSH service is controlled by five preconfigured accounts, all of which come with default hard-coded credentials. This could allow an attacker to manipulate configuration, remotely execute code, and cause a denial-of-service condition.CVE-2022-30270 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-30270"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "While individual remediation steps are specified, note all vulnerabilities listed above can be resolved by upgrading the ACE1000 to MC-EDGE intelligent RTU.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_xp/products/industrial-internet-of-things/scada-systems/mc-edge.html#tabproductinfo"
},
{
"category": "mitigation",
"details": "CVE-2022-30270: To remediate, users should change their password manually. This process can be found in the ACE1000 user guide.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "For user guide and procedural information mentioned within this report, use the Contact Us form and select \u201cOther\u201d for Product Interest and request the manual for IoT products.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_us/contact-us-form.html"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0001"
]
}
]
},
{
"cve": "CVE-2022-30274",
"cwe": {
"id": "CWE-321",
"name": "Use of Hard-coded Cryptographic Key"
},
"notes": [
{
"category": "summary",
"text": "The affected device communicates with an XRT Lan-to-radio gateway by means of an embedded client. Credentials for accessing this gateway are stored after being encrypted with the tiny encryption algorithm (TEA) in ECB mode using a hardcoded key, which could allow an attacker to manipulate the device configuration.CVE-2022-30274 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N).",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-30274"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "While individual remediation steps are specified, note all vulnerabilities listed above can be resolved by upgrading the ACE1000 to MC-EDGE intelligent RTU.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_xp/products/industrial-internet-of-things/scada-systems/mc-edge.html#tabproductinfo"
},
{
"category": "mitigation",
"details": "CVE-2022-30274: Upgrade to MOTOTRBO Capacity Max.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_us/products/mototrbo-systems/mototrbo-private-systems/mototrbo-capacity-max.html#taboverview"
},
{
"category": "mitigation",
"details": "For user guide and procedural information mentioned within this report, use the Contact Us form and select \u201cOther\u201d for Product Interest and request the manual for IoT products.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_us/contact-us-form.html"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 7.5,
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N",
"version": "3.0"
},
"products": [
"CSAFPID-0001"
]
}
]
},
{
"cve": "CVE-2022-30269",
"cwe": {
"id": "CWE-345",
"name": "Insufficient Verification of Data Authenticity"
},
"notes": [
{
"category": "summary",
"text": "The affected product allows for custom application installation via STS software, the C toolkit, or the ACE1000 Easy Configurator. Application images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. This could allow an authenticated attacker to run remote code execution or cause a denial-of-service condition.CVE-2022-30269 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H).",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-30269"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "While individual remediation steps are specified, note all vulnerabilities listed above can be resolved by upgrading the ACE1000 to MC-EDGE intelligent RTU.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_xp/products/industrial-internet-of-things/scada-systems/mc-edge.html#tabproductinfo"
},
{
"category": "mitigation",
"details": "CVE-2022-30269: To remediate, use the \u201cSecured Download and Installation for ACE1000\u201d procedure.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "For user guide and procedural information mentioned within this report, use the Contact Us form and select \u201cOther\u201d for Product Interest and request the manual for IoT products.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_us/contact-us-form.html"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 6.5,
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0001"
]
}
]
},
{
"cve": "CVE-2022-30272",
"cwe": {
"id": "CWE-345",
"name": "Insufficient Verification of Data Authenticity"
},
"notes": [
{
"category": "summary",
"text": "An attacker capable of communicating with and authenticating to a Motorola ACE1000 RTU via SSH or Web UI could push malicious firmware images to the RTU, which could allow firmware manipulation, remote code execution, and a denial-of-service condition.CVE-2022-30272 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H).",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-30272"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "While individual remediation steps are specified, note all vulnerabilities listed above can be resolved by upgrading the ACE1000 to MC-EDGE intelligent RTU.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_xp/products/industrial-internet-of-things/scada-systems/mc-edge.html#tabproductinfo"
},
{
"category": "mitigation",
"details": "CVE-2022-30272: To remediate, use the \u201cSecured Download and Installation for ACE1000\u201d procedure.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "For user guide and procedural information mentioned within this report, use the Contact Us form and select \u201cOther\u201d for Product Interest and request the manual for IoT products.",
"product_ids": [
"CSAFPID-0001"
],
"url": "https://www.motorolasolutions.com/en_us/contact-us-form.html"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 5.9,
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.0/AV:N/AC:H/PR:H/UI:N/S:U/C:N/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0001"
]
}
]
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.
Loading…
Loading…