icsa-19-192-06
Vulnerability from csaf_cisa
Published
2019-07-11 00:00
Modified
2019-07-11 00:00
Summary
Schneider Electric Interactive Graphical SCADA System

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of this vulnerability could allow an attacker to achieve arbitrary code execution or crash the software.
Critical infrastructure sectors
Commercial Facilities, Critical Manufacturing, Energy
Countries/areas deployed
Worldwide
Company headquarters location
France
Recommended Practices
NCCIC also recommends that users take the following measures to protect themselves from social engineering attacks:
Recommended Practices
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures. NCCIC also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies. Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
Exploitability
No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely. High skill level is needed to exploit.



{
  "document": {
    "acknowledgments": [
      {
        "names": [
          "mdm",
          "rgod"
        ],
        "organization": "9SG Security Team",
        "summary": "reporting this vulnerability to NCCIC"
      },
      {
        "organization": "Trend Micro Zero Day Initiative",
        "summary": "reporting this vulnerability to NCCIC"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of this vulnerability could allow an attacker to achieve arbitrary code execution or crash the software.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Commercial Facilities, Critical Manufacturing, Energy",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "France",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "NCCIC also recommends that users take the following measures to protect themselves from social engineering attacks:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.\nNCCIC also provides a section for control systems security recommended practices on the ICS webpage on us-cert.gov. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.\nOrganizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target this vulnerability. This vulnerability is not exploitable remotely. High skill level is needed to exploit.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-19-192-06 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2019/icsa-19-192-06.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-19-192-06 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-19-192-06"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.us-cert.gov/cas/tips/ST04-014.html"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://ics-cert.us-cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.us-cert.gov/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Schneider Electric Interactive Graphical SCADA System",
    "tracking": {
      "current_release_date": "2019-07-11T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-19-192-06",
      "initial_release_date": "2019-07-11T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2019-07-11T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-19-192-06 Schneider Electric Interactive Graphical SCADA System"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c= 14",
                "product": {
                  "name": "IGSS: Version 14 and prior",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "IGSS"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric Software, LLC"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2019-6827",
      "cwe": {
        "id": "CWE-787",
        "name": "Out-of-bounds Write"
      },
      "notes": [
        {
          "category": "summary",
          "text": "An out-of-bounds vulnerability exists and could be exploited by the application processing a specially crafted project file. Exploitation could cause a software crash when data in the mdb database is manipulated or allow code execution.CVE-2019-6827 has been assigned to this vulnerability. A CVSS v3 base score of 7.0 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-6827"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "mitigation",
          "details": "Schneider Electric recommends upgrading to Version 13.0.0.19140 or 14.0.0.19120",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "http://igss.schneider-electric.com/products/igss/download/licensed-versions.aspx"
        },
        {
          "category": "vendor_fix",
          "details": "Do not allow untrusted access to the configuration database (mdb) and update IGSS to the latest version of IGSS, either Version 13 or Version 14.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "A restart of the software is required, but a reboot of the system is not required.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Physical controls should be in place so that no unauthorized person would have access to the ICS and safety controllers, peripheral equipment, or the ICS and safety networks.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "All controllers should reside in locked cabinets and never be left in \u201cProgram\u201d mode.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "All programming software should be kept in locked cabinets and should never be connected to any network other than the network intended for the devices.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "All methods of mobile data exchange with the isolated network, such as CDs, USB drives, etc., should be scanned before use in the terminals or any node connected to these networks.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Laptops that have connected to any other network besides the intended network should never be allowed to connect to the safety or control networks without proper sanitation.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "Minimize network exposure for all control system devices and/or systems and ensure that they are not accessible from the Internet.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "When remote access is required, use secure methods such as virtual private networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, please see Schneider Electric advisory: SEVD-2019-190-02",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-190-02/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.0,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.


Loading…