icsa-18-102-02
Vulnerability from csaf_cisa
Published
2018-04-12 00:00
Modified
2018-05-31 00:00
Summary
Rockwell Automation FactoryTalk Activation Manager (Update B)

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could allow a remote attacker to access sensitive information, rewrite content, or cause a buffer overflow that could result in remote code execution.
Critical infrastructure sectors
Chemical, Critical Manufacturing, Food and Agriculture, Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
U.S.
Recommended Practices
NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Exploitability
No known public exploits specifically target these vulnerabilities.



{
  "document": {
    "acknowledgments": [
      {
        "organization": "Rockwell Automation",
        "summary": "reporting these vulnerabilities to NCCIC"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could allow a remote attacker to access sensitive information, rewrite content, or cause a buffer overflow that could result in remote code execution.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Chemical, Critical Manufacturing, Food and Agriculture, Water and Wastewater Systems",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "U.S.",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "NCCIC reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "NCCIC also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to NCCIC for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS-CERT website in the Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target these vulnerabilities.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-18-102-02 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2018/icsa-18-102-02.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-18-102-02 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-102-02"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-18-102-02"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      }
    ],
    "title": "Rockwell Automation FactoryTalk Activation Manager (Update B)",
    "tracking": {
      "current_release_date": "2018-05-31T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-18-102-02",
      "initial_release_date": "2018-04-12T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2018-04-12T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "ICSA-18-102-02P Rockwell Automation FactoryTalk"
        },
        {
          "date": "2018-05-10T00:00:00.000000Z",
          "legacy_version": "A",
          "number": "2",
          "summary": "ICSA-18-102-02 Rockwell Automation FactoryTalk (Update A)"
        },
        {
          "date": "2018-05-24T00:00:00.000000Z",
          "legacy_version": "B",
          "number": "3",
          "summary": "ICSA-18-102-02 Rockwell Automation Factory Talk Activation Manager (Update B)"
        },
        {
          "date": "2018-05-31T00:00:00.000000Z",
          "legacy_version": "C",
          "number": "4",
          "summary": "ICSA-18-102-02 Rockwell Automation FactoryTalk Activation Manager (Update C)"
        }
      ],
      "status": "final",
      "version": "4"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c= 4.00",
                "product": {
                  "name": "FactoryTalk Activation Manager: v4.00 and earlier",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "FactoryTalk Activation Manager"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "4.00 | 4.01",
                "product": {
                  "name": "FactoryTalk Activation Manager: v4.00 and v4.01",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "FactoryTalk Activation Manager"
          }
        ],
        "category": "vendor",
        "name": "Rockwell Automation"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2017-13754",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "A Cross-Site Scripting (XSS) vulnerability was found in certain versions of Wibu-Systems CodeMeter that may allow local attackers to inject arbitrary web script or HTML via a specific field in a configuration file, allowing an attacker to access sensitive information, or even rewrite the content of the HTML page.CVE-2017-13754 has been assigned to this vulnerability. A CVSS v3 base score of 2.7 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:N/UI:R/S:C/C:N/I:L/A:N).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-13754"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:C/C:N/I:L/A:N"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Rockwell Automation recommends users with affected versions of CodeMeter and/or FlexNet Publisher that were installed with FactoryTalk Activation Manager to update Factory Talk Activation Manager to v4.02. If unable to update FactoryTalk Activation Manager to v4.02, update CodeMeter to a compatible version of CodeMeter that is compatible with FactoryTalk Activation Manager.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Rockwell Automation also encourages users to combine the updates above with these general security guidelines to employ multiple strategies simultaneously.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Block all traffic to EtherNet/IP or other CIP protocol-based devices from outside the Manufacturing Zone by blocking or restricting access to Port 2222/TCP and UDP and Port 44818/TCP and UDP, using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270 available at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/898270/page/1 (Login required).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Locate control system networks and devices behind firewalls and isolate them from the business network.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "When remote access is required, use secure methods such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. VPN is only as secure as the connected devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information about these vulnerabilities and the recommended mitigations, please see Rockwell Automation Knowledgebase Advisory 1073133 available at:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073133"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 2.7,
            "baseSeverity": "LOW",
            "vectorString": "CVSS:3.0/AV:L/AC:H/PR:N/UI:R/S:C/C:N/I:L/A:N",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2015-8277",
      "cwe": {
        "id": "CWE-119",
        "name": "Improper Restriction of Operations within the Bounds of a Memory Buffer"
      },
      "notes": [
        {
          "category": "summary",
          "text": "A custom string copying function of the license server manager in FlexNet Publisher does not use proper bounds checking on incoming data, allowing a remote, unauthenticated user to send crafted messages with the intent of causing a buffer overflow.CVE-2015-8277 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2015-8277"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Rockwell Automation recommends users with affected versions of CodeMeter and/or FlexNet Publisher that were installed with FactoryTalk Activation Manager to update Factory Talk Activation Manager to v4.02. If unable to update FactoryTalk Activation Manager to v4.02, update CodeMeter to a compatible version of CodeMeter that is compatible with FactoryTalk Activation Manager.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Rockwell Automation also encourages users to combine the updates above with these general security guidelines to employ multiple strategies simultaneously.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Block all traffic to EtherNet/IP or other CIP protocol-based devices from outside the Manufacturing Zone by blocking or restricting access to Port 2222/TCP and UDP and Port 44818/TCP and UDP, using proper network infrastructure controls, such as firewalls, UTM devices, or other security appliances. For more information on TCP/UDP ports used by Rockwell Automation Products, see Knowledgebase Article ID 898270 available at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/898270/page/1 (Login required).",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the Internet.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Locate control system networks and devices behind firewalls and isolate them from the business network.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "When remote access is required, use secure methods such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. VPN is only as secure as the connected devices.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information about these vulnerabilities and the recommended mitigations, please see Rockwell Automation Knowledgebase Advisory 1073133 available at:",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1073133"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.