CVE-2026-1773 (GCVE-0-2026-1773)

Vulnerability from cvelistv5 – Published: 2026-02-24 13:13 – Updated: 2026-05-27 14:50
VLAI
Summary
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
SSVC
Exploitation: none Automatable: yes Technical Impact: partial
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2026-02-28 02:19 UTC
CWE
  • CWE-184 - Incomplete List of Disallowed Inputs
Assigner
Impacted products
Vendor Product Version CPE status
Hitachi Energy RTU500 series CMU firmware Affected: 12.7.1 , ≤ 12.7.7 (custom)
Affected: 13.5.1 , ≤ 13.5.4 (custom)
Affected: 13.6.1 , ≤ 13.6.2 (custom)
Affected: 13.7.1 , ≤ 13.7.7 (custom)
Affected: 13.8.1 (custom)
guessed Create a notification for this product.
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2026-1773",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2026-02-28T02:19:44.432868Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2026-05-27T14:50:01.447Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "RTU500 series CMU firmware",
          "vendor": "Hitachi Energy",
          "versions": [
            {
              "lessThanOrEqual": "12.7.7",
              "status": "affected",
              "version": "12.7.1",
              "versionType": "custom"
            },
            {
              "lessThanOrEqual": "13.5.4",
              "status": "affected",
              "version": "13.5.1",
              "versionType": "custom"
            },
            {
              "lessThanOrEqual": "13.6.2",
              "status": "affected",
              "version": "13.6.1",
              "versionType": "custom"
            },
            {
              "lessThanOrEqual": "13.7.7",
              "status": "affected",
              "version": "13.7.1",
              "versionType": "custom"
            },
            {
              "status": "affected",
              "version": "13.8.1",
              "versionType": "custom"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame.\u0026nbsp;Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.\u003cbr\u003e"
            }
          ],
          "value": "IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame.\u00a0Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation."
        }
      ],
      "impacts": [
        {
          "capecId": "CAPEC-278",
          "descriptions": [
            {
              "lang": "en",
              "value": "CAPEC-278 Web Services Protocol Manipulation"
            }
          ]
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "NONE",
            "attackVector": "NETWORK",
            "baseScore": 8.7,
            "baseSeverity": "HIGH",
            "exploitMaturity": "NOT_DEFINED",
            "privilegesRequired": "NONE",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "NONE",
            "vulnIntegrityImpact": "NONE",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-184",
              "description": "CWE-184 Incomplete List of Disallowed Inputs",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2026-05-26T14:53:41.970Z",
        "orgId": "e383dce4-0c27-4495-91c4-0db157728d17",
        "shortName": "Hitachi Energy"
      },
      "references": [
        {
          "url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000237\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
        }
      ],
      "source": {
        "discovery": "UNKNOWN"
      },
      "x_generator": {
        "engine": "Vulnogram 0.5.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "e383dce4-0c27-4495-91c4-0db157728d17",
    "assignerShortName": "Hitachi Energy",
    "cveId": "CVE-2026-1773",
    "datePublished": "2026-02-24T13:13:17.990Z",
    "dateReserved": "2026-02-02T16:28:59.394Z",
    "dateUpdated": "2026-05-27T14:50:01.447Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.2",
  "vulnerability-lookup:meta": {
    "epss": {
      "cve": "CVE-2026-1773",
      "date": "2026-09-22",
      "epss": "0.00411",
      "percentile": "0.35055"
    },
    "nvd": {
      "cve": {
        "affected": [
          {
            "affectedData": [
              {
                "defaultStatus": "unaffected",
                "product": "RTU500 series CMU firmware",
                "vendor": "Hitachi Energy",
                "versions": [
                  {
                    "lessThanOrEqual": "12.7.7",
                    "status": "affected",
                    "version": "12.7.1",
                    "versionType": "custom"
                  },
                  {
                    "lessThanOrEqual": "13.5.4",
                    "status": "affected",
                    "version": "13.5.1",
                    "versionType": "custom"
                  },
                  {
                    "lessThanOrEqual": "13.6.2",
                    "status": "affected",
                    "version": "13.6.1",
                    "versionType": "custom"
                  },
                  {
                    "lessThanOrEqual": "13.7.7",
                    "status": "affected",
                    "version": "13.7.1",
                    "versionType": "custom"
                  },
                  {
                    "status": "affected",
                    "version": "13.8.1",
                    "versionType": "custom"
                  }
                ]
              }
            ],
            "source": "cybersecurity@hitachienergy.com"
          }
        ],
        "configurations": [
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu540_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "FCFA1FB7-1834-4425-9DDB-0C08140DAD4B",
                    "versionEndIncluding": "12.7.7",
                    "versionStartIncluding": "12.7.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu540_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "B70918C5-85C2-40B8-8681-921942C41561",
                    "versionEndIncluding": "13.5.4",
                    "versionStartIncluding": "13.5.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu540_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "30F20A11-9ECB-4CC6-88C2-0CC96DFFABE2",
                    "versionEndIncluding": "13.6.2",
                    "versionStartIncluding": "13.6.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu540_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "199A1127-9B24-46A6-9122-30FD2EF64F32",
                    "versionEndExcluding": "13.7.8",
                    "versionStartIncluding": "13.7.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu540_firmware:13.8.1:*:*:*:*:*:*:*",
                    "matchCriteriaId": "4D49545F-C765-4579-89C5-01B1EBB45B36",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:hitachienergy:rtu540:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "6EEFDEF0-883D-402B-9CD4-333A145E3C75",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu560_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "EF5BF48F-4BDF-4D38-A836-221066FA6234",
                    "versionEndIncluding": "12.7.7",
                    "versionStartIncluding": "12.7.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu560_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "C75F1BB5-558A-4292-BA2B-E77D811D5E09",
                    "versionEndIncluding": "13.5.4",
                    "versionStartIncluding": "13.5.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu560_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "4DE20728-0C7A-4388-AA09-AC50C8AD51F9",
                    "versionEndIncluding": "13.6.2",
                    "versionStartIncluding": "13.6.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu560_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "2CCC0128-9A27-4F4A-B254-C0C31BDCA78B",
                    "versionEndExcluding": "13.7.8",
                    "versionStartIncluding": "13.7.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu560_firmware:13.8.1:*:*:*:*:*:*:*",
                    "matchCriteriaId": "B9753BCF-0BE9-4B1A-88B4-0B0DE5F623CE",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:hitachienergy:rtu560:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "495DCBD6-D2D1-4295-81D1-6ACA1B2CA223",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "064FFA76-2AD3-425F-B003-4D038C941E7D",
                    "versionEndIncluding": "12.7.7",
                    "versionStartIncluding": "12.7.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "AC2DF255-AB45-4CAE-A7BD-0B2A1B5D04D6",
                    "versionEndIncluding": "13.5.4",
                    "versionStartIncluding": "13.5.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "CB44D4BF-8F0F-4770-A150-A5469A262A5A",
                    "versionEndIncluding": "13.6.2",
                    "versionStartIncluding": "13.6.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu520_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "432CB425-58CC-47E2-847D-5E3FD31F8EB3",
                    "versionEndExcluding": "13.7.8",
                    "versionStartIncluding": "13.7.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu520_firmware:13.8.1:*:*:*:*:*:*:*",
                    "matchCriteriaId": "D034F19D-920A-44DE-A886-6021242FF6E3",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:hitachienergy:rtu520:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "11AF93AD-200F-47A6-BA2C-F82165AFB50D",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          },
          {
            "nodes": [
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "50ECC099-2676-45CE-82DA-4A6943452976",
                    "versionEndIncluding": "12.7.7",
                    "versionStartIncluding": "12.7.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "3D5D8077-C84A-4821-9F89-76A0F4664927",
                    "versionEndIncluding": "13.5.4",
                    "versionStartIncluding": "13.5.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "89FAF654-7F2C-4918-B074-6CB685E885D8",
                    "versionEndIncluding": "13.6.2",
                    "versionStartIncluding": "13.6.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu530_firmware:*:*:*:*:*:*:*:*",
                    "matchCriteriaId": "0561AA77-CE68-4C93-8611-630FB07B507C",
                    "versionEndExcluding": "13.7.8",
                    "versionStartIncluding": "13.7.1",
                    "vulnerable": true
                  },
                  {
                    "criteria": "cpe:2.3:o:hitachienergy:rtu530_firmware:13.8.1:*:*:*:*:*:*:*",
                    "matchCriteriaId": "45F698BE-5EDF-46DF-8B1E-96AC8894AA64",
                    "vulnerable": true
                  }
                ],
                "negate": false,
                "operator": "OR"
              },
              {
                "cpeMatch": [
                  {
                    "criteria": "cpe:2.3:h:hitachienergy:rtu530:-:*:*:*:*:*:*:*",
                    "matchCriteriaId": "FC6F9377-E6BB-4DEA-9D87-0AF792CBAC57",
                    "vulnerable": false
                  }
                ],
                "negate": false,
                "operator": "OR"
              }
            ],
            "operator": "AND"
          }
        ],
        "cveTags": [],
        "descriptions": [
          {
            "lang": "en",
            "value": "IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame.\u00a0Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation."
          },
          {
            "lang": "es",
            "value": "IEC 60870-5-104: Hay un potencial impacto de denegaci\u00f3n de servicio en la recepci\u00f3n de una trama de formato U inv\u00e1lida. El producto solo se ve afectado si est\u00e1 configurada la funcionalidad bidireccional IEC 60870-5-104. Si se habilita la comunicaci\u00f3n segura siguiendo la IEC 62351-3 no se remedia la vulnerabilidad, pero se mitiga el riesgo de explotaci\u00f3n."
          }
        ],
        "id": "CVE-2026-1773",
        "lastModified": "2026-06-17T10:16:29.673",
        "metrics": {
          "cvssMetricV31": [
            {
              "cvssData": {
                "attackComplexity": "LOW",
                "attackVector": "NETWORK",
                "availabilityImpact": "HIGH",
                "baseScore": 7.5,
                "baseSeverity": "HIGH",
                "confidentialityImpact": "NONE",
                "integrityImpact": "NONE",
                "privilegesRequired": "NONE",
                "scope": "UNCHANGED",
                "userInteraction": "NONE",
                "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
                "version": "3.1"
              },
              "exploitabilityScore": 3.9,
              "impactScore": 3.6,
              "source": "nvd@nist.gov",
              "type": "Primary"
            }
          ],
          "cvssMetricV40": [
            {
              "cvssData": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "availabilityRequirement": "NOT_DEFINED",
                "baseScore": 8.7,
                "baseSeverity": "HIGH",
                "confidentialityRequirement": "NOT_DEFINED",
                "exploitMaturity": "NOT_DEFINED",
                "integrityRequirement": "NOT_DEFINED",
                "modifiedAttackComplexity": "NOT_DEFINED",
                "modifiedAttackRequirements": "NOT_DEFINED",
                "modifiedAttackVector": "NOT_DEFINED",
                "modifiedPrivilegesRequired": "NOT_DEFINED",
                "modifiedSubAvailabilityImpact": "NOT_DEFINED",
                "modifiedSubConfidentialityImpact": "NOT_DEFINED",
                "modifiedSubIntegrityImpact": "NOT_DEFINED",
                "modifiedUserInteraction": "NOT_DEFINED",
                "modifiedVulnAvailabilityImpact": "NOT_DEFINED",
                "modifiedVulnConfidentialityImpact": "NOT_DEFINED",
                "modifiedVulnIntegrityImpact": "NOT_DEFINED",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "NONE",
                "vulnIntegrityImpact": "NONE",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "source": "cybersecurity@hitachienergy.com",
              "type": "Secondary"
            }
          ],
          "ssvcV203": [
            {
              "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "ssvcData": {
                "id": "CVE-2026-1773",
                "options": [
                  {
                    "exploitation": "none"
                  },
                  {
                    "automatable": "yes"
                  },
                  {
                    "technicalImpact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2026-02-28T02:19:44.432868Z",
                "version": "2.0.3"
              }
            }
          ]
        },
        "published": "2026-02-24T14:16:22.420",
        "references": [
          {
            "source": "cybersecurity@hitachienergy.com",
            "tags": [
              "Vendor Advisory"
            ],
            "url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000237\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
          }
        ],
        "sourceIdentifier": "cybersecurity@hitachienergy.com",
        "vulnStatus": "Modified",
        "weaknesses": [
          {
            "description": [
              {
                "lang": "en",
                "value": "CWE-184"
              }
            ],
            "source": "cybersecurity@hitachienergy.com",
            "type": "Secondary"
          }
        ]
      }
    },
    "redhat_vex": {
      "current_release_date": "2026-05-26T20:13:55+00:00",
      "cve": "CVE-2026-1773",
      "id": "CVE-2026-1773",
      "initial_release_date": "2026-01-01T00:00:00+00:00",
      "product_status:known_not_affected": "1",
      "source": "Red Hat CSAF VEX",
      "status": "final",
      "title": "CVE-2026-1773",
      "url": "https://security.access.redhat.com/data/csaf/v2/vex/2026/cve-2026-1773.json",
      "version": "3"
    },
    "vulnrichment": {
      "containers": {
        "adp": [
          {
            "metrics": [
              {
                "other": {
                  "content": {
                    "id": "CVE-2026-1773",
                    "options": [
                      {
                        "Exploitation": "none"
                      },
                      {
                        "Automatable": "yes"
                      },
                      {
                        "Technical Impact": "partial"
                      }
                    ],
                    "role": "CISA Coordinator",
                    "timestamp": "2026-02-28T02:19:44.432868Z",
                    "version": "2.0.3"
                  },
                  "type": "ssvc"
                }
              }
            ],
            "providerMetadata": {
              "dateUpdated": "2026-02-28T02:19:54.971Z",
              "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
              "shortName": "CISA-ADP"
            },
            "title": "CISA ADP Vulnrichment"
          }
        ],
        "cna": {
          "affected": [
            {
              "defaultStatus": "unaffected",
              "product": "RTU500 series CMU firmware",
              "vendor": "Hitachi Energy",
              "versions": [
                {
                  "lessThanOrEqual": "12.7.7",
                  "status": "affected",
                  "version": "12.7.1",
                  "versionType": "custom"
                },
                {
                  "lessThanOrEqual": "13.5.4",
                  "status": "affected",
                  "version": "13.5.1",
                  "versionType": "custom"
                },
                {
                  "lessThanOrEqual": "13.6.2",
                  "status": "affected",
                  "version": "13.6.1",
                  "versionType": "custom"
                },
                {
                  "lessThanOrEqual": "13.7.7",
                  "status": "affected",
                  "version": "13.7.1",
                  "versionType": "custom"
                },
                {
                  "status": "affected",
                  "version": "13.8.1",
                  "versionType": "custom"
                }
              ]
            }
          ],
          "descriptions": [
            {
              "lang": "en",
              "supportingMedia": [
                {
                  "base64": false,
                  "type": "text/html",
                  "value": "IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame.\u0026nbsp;Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.\u003cbr\u003e"
                }
              ],
              "value": "IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame.\u00a0Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation."
            }
          ],
          "impacts": [
            {
              "capecId": "CAPEC-278",
              "descriptions": [
                {
                  "lang": "en",
                  "value": "CAPEC-278 Web Services Protocol Manipulation"
                }
              ]
            }
          ],
          "metrics": [
            {
              "cvssV4_0": {
                "Automatable": "NOT_DEFINED",
                "Recovery": "NOT_DEFINED",
                "Safety": "NOT_DEFINED",
                "attackComplexity": "LOW",
                "attackRequirements": "NONE",
                "attackVector": "NETWORK",
                "baseScore": 8.7,
                "baseSeverity": "HIGH",
                "exploitMaturity": "NOT_DEFINED",
                "privilegesRequired": "NONE",
                "providerUrgency": "NOT_DEFINED",
                "subAvailabilityImpact": "NONE",
                "subConfidentialityImpact": "NONE",
                "subIntegrityImpact": "NONE",
                "userInteraction": "NONE",
                "valueDensity": "NOT_DEFINED",
                "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N",
                "version": "4.0",
                "vulnAvailabilityImpact": "HIGH",
                "vulnConfidentialityImpact": "NONE",
                "vulnIntegrityImpact": "NONE",
                "vulnerabilityResponseEffort": "NOT_DEFINED"
              },
              "format": "CVSS",
              "scenarios": [
                {
                  "lang": "en",
                  "value": "GENERAL"
                }
              ]
            }
          ],
          "problemTypes": [
            {
              "descriptions": [
                {
                  "cweId": "CWE-184",
                  "description": "CWE-184 Incomplete List of Disallowed Inputs",
                  "lang": "en",
                  "type": "CWE"
                }
              ]
            }
          ],
          "providerMetadata": {
            "dateUpdated": "2026-05-26T14:53:41.970Z",
            "orgId": "e383dce4-0c27-4495-91c4-0db157728d17",
            "shortName": "Hitachi Energy"
          },
          "references": [
            {
              "url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000237\u0026LanguageCode=en\u0026DocumentPartId=\u0026Action=Launch"
            }
          ],
          "source": {
            "discovery": "UNKNOWN"
          },
          "x_generator": {
            "engine": "Vulnogram 0.5.0"
          }
        }
      },
      "cveMetadata": {
        "assignerOrgId": "e383dce4-0c27-4495-91c4-0db157728d17",
        "assignerShortName": "Hitachi Energy",
        "cveId": "CVE-2026-1773",
        "datePublished": "2026-02-24T13:13:17.990Z",
        "dateReserved": "2026-02-02T16:28:59.394Z",
        "dateUpdated": "2026-05-27T14:50:01.447Z",
        "state": "PUBLISHED"
      },
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }
  }
}



Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.

Loading…

Loading…

Loading…

Related by attack behaviour

Vulnerabilities whose description is nearest to this one in the vector space of the CIRCL/vulnerability-attack-technique-biencoder model. This is a similarity search over the bi-encoder space (plain cosine), not a classification, and it has no measured accuracy.


Loading…