ICSA-20-196-03
Vulnerability from csaf_cisa
Published
2020-07-14 00:00
Modified
2020-07-14 00:00
Summary
Siemens SICAM MMU, SICAM T, and SICAM SGU

Notes

General Recommendations
Operators of critical power systems (e.g.'TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g.'firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines to Digital Grid Products can be found at:
Additional Resources
https://www.siemens.com/gridsecurity
Terms of Use
Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Advisory Conversion Disclaimer
This CISA CSAF advisory was converted from a Siemens ProductCERT's advisory.
Critical infrastructure sectors
Multiple
Countries/areas deployed
Worldwide
Company headquarters location
Germany
Recommended Practices
CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.



{
  "document": {
    "acknowledgments": [
      {
        "organization": "Siemens ProductCERT",
        "summary": "reporting these vulnerabilities to CISA."
      },
      {
        "names": [
          "Luca Simbrger",
          "Luca Hofschuster",
          "Lukas Kahnert",
          "Jakob Lachermeier",
          "Christian Costa",
          "Simon Huber",
          "Lukas Sas Brunschier",
          "Florian Freiberger",
          "Florian Burger",
          "Marie-Louise Oostveen",
          "Magdalena Thomeczek",
          "Johann Uhrmann"
        ],
        "organization": "Landshut University of Applied Sciences",
        "summary": "coordinating disclosure of CVE-2020-10037"
      },
      {
        "names": [
          "Max Hirschberger",
          "Simon Hofmann",
          "Peter Knauer"
        ],
        "organization": "Augsburg University of Applied Sciences",
        "summary": "for coordinating disclosure of CVE-2020-10038 to CVE-2020-10045"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en",
    "notes": [
      {
        "category": "general",
        "text": "Operators of critical power systems (e.g.\u0027TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design. Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g.\u0027firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment. Recommended security guidelines to Digital Grid Products can be found at:",
        "title": "General Recommendations"
      },
      {
        "category": "general",
        "text": "https://www.siemens.com/gridsecurity",
        "title": "Additional Resources"
      },
      {
        "category": "legal_disclaimer",
        "text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.",
        "title": "Terms of Use"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "other",
        "text": "This CISA CSAF advisory was converted from a Siemens ProductCERT\u0027s advisory.",
        "title": "Advisory Conversion Disclaimer"
      },
      {
        "category": "other",
        "text": "Multiple",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Germany",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "other",
      "contact_details": "central@cisa.dhs.gov",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "SSA-305120: Vulnerabilities in SICAM MMU, SICAM T and SICAM SGU - HTML Version",
        "url": "https://cert-portal.siemens.com/productcert/html/ssa-305120.html"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-20-196-03 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2020/icsa-20-196-03.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-20-196-03 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-20-196-03"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
      }
    ],
    "title": "Siemens SICAM MMU, SICAM T, and SICAM SGU",
    "tracking": {
      "current_release_date": "2020-07-14T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-20-196-03",
      "initial_release_date": "2020-07-14T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2020-07-14T00:00:00.000000Z",
          "legacy_version": "1.0",
          "number": "1",
          "summary": "Publication Date"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cV2.05",
                "product": {
                  "name": "Siemens SICAM MMU: All versions \u003c V2.05",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "SICAM MMU"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Siemens SICAM SGU: All versions",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "SICAM SGU"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003cV2.18",
                "product": {
                  "name": "Siemens SICAM T: All versions \u003c V2.18",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "SICAM T"
          }
        ],
        "category": "vendor",
        "name": "Siemens"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2020-10037",
      "cwe": {
        "id": "CWE-125",
        "name": "Out-of-bounds Read"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 5.9,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10037"
    },
    {
      "cve": "CVE-2020-10038",
      "cwe": {
        "id": "CWE-306",
        "name": "Missing Authentication for Critical Function"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10038"
    },
    {
      "cve": "CVE-2020-10039",
      "cwe": {
        "id": "CWE-311",
        "name": "Missing Encryption of Sensitive Data"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10039"
    },
    {
      "cve": "CVE-2020-10040",
      "cwe": {
        "id": "CWE-916",
        "name": "Use of Password Hash With Insufficient Computational Effort"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 6.2,
            "baseSeverity": "MEDIUM",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10040"
    },
    {
      "cve": "CVE-2020-10041",
      "cwe": {
        "id": "CWE-79",
        "name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.6,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:H/I:H/A:H/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10041"
    },
    {
      "cve": "CVE-2020-10042",
      "cwe": {
        "id": "CWE-120",
        "name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10042"
    },
    {
      "cve": "CVE-2020-10043",
      "cwe": {
        "id": "CWE-80",
        "name": "Improper Neutralization of Script-Related HTML Tags in a Web Page (Basic XSS)"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.8,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:H/A:L/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10043"
    },
    {
      "cve": "CVE-2020-10044",
      "cwe": {
        "id": "CWE-306",
        "name": "Missing Authentication for Critical Function"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10044"
    },
    {
      "cve": "CVE-2020-10045",
      "cwe": {
        "id": "CWE-294",
        "name": "Authentication Bypass by Capture-replay"
      },
      "notes": [
        {
          "category": "summary",
          "text": "By performing a flooding attack against the web server, an attacker might be able to gain read access to the device\u0027s memory, possibly revealing confidential information.",
          "title": "Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002",
          "CSAFPID-0003"
        ]
      },
      "remediations": [
        {
          "category": "mitigation",
          "details": "The firmware updates to SICAM T and SICAM MMU introduce authentication to the web application and remove some unnecessary functionality. The web authentication functionality reduces the risk of access to the device\u0027s web application for executing administrative commands by unauthenticated users.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Due to hardware constraints, encryption is not possible on the devices. Confidential data such as passwords handled by the devices need to be protected on the network by other means, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "The risk for remote code execution and unauthenticated firmware installation can be mitigated by ensuring encryption and authentication between the user and the device, e.g.\u0027by VPN.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "mitigation",
          "details": "Using a modern and up to date browser while accessing the web application might reduce the risk of Cross-Site-Scripting attacks.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.05 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0001"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "Update to V2.18 to introduce authentication in the web application to mitigate some web",
          "product_ids": [
            "CSAFPID-0003"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 8.3,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:H/A:H/E:P/RL:T/RC:C",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002",
            "CSAFPID-0003"
          ]
        }
      ],
      "title": "CVE-2020-10045"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.


Loading…

Loading…