ssa-830194
Vulnerability from csaf_siemens
Published
2021-08-10 00:00
Modified
2021-09-14 00:00
Summary
SSA-830194: Missing Authentication Vulnerability in S7-1200 Devices
Notes
Summary
SIMATIC S7-1200 PLC, version V4.5.0 fails to authenticate against configured passwords when the affected device was provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC.
Siemens has released an update for SIMATIC S7-1200 and recommends to update to the latest version.
General Recommendations
As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.
{
"document": {
"acknowledgments": [
{
"names": [
"Gao Jian"
],
"summary": "reporting the vulnerability"
}
],
"category": "Siemens Security Advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited.",
"tlp": {
"label": "WHITE"
}
},
"notes": [
{
"category": "summary",
"text": "SIMATIC S7-1200 PLC, version V4.5.0 fails to authenticate against configured passwords when the affected device was provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC.\n\nSiemens has released an update for SIMATIC S7-1200 and recommends to update to the latest version.",
"title": "Summary"
},
{
"category": "general",
"text": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-830194: Missing Authentication Vulnerability in S7-1200 Devices - PDF Version",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-830194.pdf"
},
{
"category": "self",
"summary": "SSA-830194: Missing Authentication Vulnerability in S7-1200 Devices - TXT Version",
"url": "https://cert-portal.siemens.com/productcert/txt/ssa-830194.txt"
},
{
"category": "self",
"summary": "SSA-830194: Missing Authentication Vulnerability in S7-1200 Devices - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-830194.json"
}
],
"title": "SSA-830194: Missing Authentication Vulnerability in S7-1200 Devices",
"tracking": {
"current_release_date": "2021-09-14T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-830194",
"initial_release_date": "2021-08-10T00:00:00Z",
"revision_history": [
{
"date": "2021-08-10T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
},
{
"date": "2021-09-14T00:00:00Z",
"legacy_version": "1.1",
"number": "2",
"summary": "Clarified that the use of TIA Portal V13 or later (not only V17 or later) could allow a successful attack"
}
],
"status": "final",
"version": "2"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "V4.5.0",
"product": {
"name": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2021-37172",
"cwe": {
"id": "CWE-287",
"name": "Improper Authentication"
},
"notes": [
{
"category": "summary",
"text": "Affected devices fail to authenticate against configured passwords when provisioned using TIA Portal V13. This could allow an attacker using TIA Portal V13 or later versions to bypass authentication and download arbitrary programs to the PLC. The vulnerability does not occur when TIA Portal V13 SP1 or any later version was used to provision the device.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1"
]
},
"references": [
{
"summary": "CVE-2021-37172 - SIMATIC S7-1200 CPU family (incl. SIPLUS variants)",
"url": "https://support.industry.siemens.com/cs/ww/en/view/109793280/"
},
{
"summary": "CVE-2021-37172 Mitre 5.0 json",
"url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2021-37172.json"
}
],
"remediations": [
{
"category": "vendor_fix",
"details": "Update to V4.5.1 or later version",
"product_ids": [
"1"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109793280/"
},
{
"category": "mitigation",
"details": "Update to TIA Portal V13 SP1 or any later version before provisioning S7-1200 V4.5.0 devices",
"product_ids": [
"1"
]
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 8.1,
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2021-37172"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…