ssa-594364
Vulnerability from csaf_siemens
Published
2021-05-11 00:00
Modified
2021-05-11 00:00
Summary
SSA-594364: Denial-of-Service Vulnerability in SNMP Implementation of WinCC Runtime
Notes
Summary
A denial-of-service vulnerability in WinCC Runtime could allow an unauthenticated attacker with network access to cause a denial-of-service condition in the SNMP service by sending crafted SNMP packets to port 161/udp.
Siemens has released updates for the affected products and recommends to update to the latest versions.
General Recommendations
As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens' operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
Siemens Security Advisories are subject to the terms and conditions contained in Siemens' underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter "License Terms"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens' Global Website (https://www.siemens.com/terms_of_use, hereinafter "Terms of Use"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.
{
"document": {
"acknowledgments": [
{
"names": [
"Younes Dragoni",
"Alessandro Di Pinto"
],
"organization": "Nozomi Networks",
"summary": "coordinated disclosure"
}
],
"category": "Siemens Security Advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited.",
"tlp": {
"label": "WHITE"
}
},
"notes": [
{
"category": "summary",
"text": "A denial-of-service vulnerability in WinCC Runtime could allow an unauthenticated attacker with network access to cause a denial-of-service condition in the SNMP service by sending crafted SNMP packets to port 161/udp.\n\nSiemens has released updates for the affected products and recommends to update to the latest versions.",
"title": "Summary"
},
{
"category": "general",
"text": "As a general security measure, Siemens strongly recommends to protect network access to devices with appropriate mechanisms. In order to operate the devices in a protected IT environment, Siemens recommends to configure the environment according to Siemens\u0027 operational guidelines for Industrial Security (Download: https://www.siemens.com/cert/operational-guidelines-industrial-security), and to follow the recommendations in the product manuals.\n\nAdditional information on Industrial Security by Siemens can be found at: https://www.siemens.com/industrialsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "Siemens Security Advisories are subject to the terms and conditions contained in Siemens\u0027 underlying license terms or other applicable agreements previously agreed to with Siemens (hereinafter \"License Terms\"). To the extent applicable to information, software or documentation made available in or through a Siemens Security Advisory, the Terms of Use of Siemens\u0027 Global Website (https://www.siemens.com/terms_of_use, hereinafter \"Terms of Use\"), in particular Sections 8-10 of the Terms of Use, shall apply additionally. In case of conflicts, the License Terms shall prevail over the Terms of Use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-594364: Denial-of-Service Vulnerability in SNMP Implementation of WinCC Runtime - PDF Version",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-594364.pdf"
},
{
"category": "self",
"summary": "SSA-594364: Denial-of-Service Vulnerability in SNMP Implementation of WinCC Runtime - TXT Version",
"url": "https://cert-portal.siemens.com/productcert/txt/ssa-594364.txt"
},
{
"category": "self",
"summary": "SSA-594364: Denial-of-Service Vulnerability in SNMP Implementation of WinCC Runtime - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-594364.json"
}
],
"title": "SSA-594364: Denial-of-Service Vulnerability in SNMP Implementation of WinCC Runtime",
"tracking": {
"current_release_date": "2021-05-11T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-594364",
"initial_release_date": "2021-05-11T00:00:00Z",
"revision_history": [
{
"date": "2021-05-11T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c V16 Update 4",
"product": {
"name": "SIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants)",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "SIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants)"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c V16 Update 4",
"product": {
"name": "SIMATIC HMI KTP Mobile Panels",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "SIMATIC HMI KTP Mobile Panels"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2019-19276",
"cwe": {
"id": "CWE-787",
"name": "Out-of-bounds Write"
},
"notes": [
{
"category": "summary",
"text": "Specially crafted packets sent to port 161/udp can cause the SNMP service of affected devices to crash. A manual restart of the device is required to resume operation of the service.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1",
"2"
]
},
"references": [
{
"summary": "CVE-2019-19276 - SIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants)",
"url": "https://support.industry.siemens.com/cs/ww/en/view/109775861/"
},
{
"summary": "CVE-2019-19276 - SIMATIC HMI KTP Mobile Panels",
"url": "https://support.industry.siemens.com/cs/ww/en/view/109775861/"
},
{
"summary": "CVE-2019-19276 Mitre 5.0 json",
"url": "https://cert-portal.siemens.com/productcert/mitre/CVE-2019-19276.json"
}
],
"remediations": [
{
"category": "vendor_fix",
"details": "Update to V16 Update 4 or later version",
"product_ids": [
"1",
"2"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109775861/"
},
{
"category": "mitigation",
"details": "Disable SNMP if this is supported by the product. Disabling SNMP fully mitigates the vulnerability",
"product_ids": [
"1",
"2"
]
},
{
"category": "mitigation",
"details": "Restrict network access to port 161/udp of affected devices to trusted devices or IP addresses",
"product_ids": [
"1",
"2"
]
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L/E:P/RL:O/RC:C",
"version": "3.1"
},
"products": [
"1",
"2"
]
}
],
"title": "CVE-2019-19276"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…