icsa-25-259-01
Vulnerability from csaf_cisa
Published
2025-09-09 04:00
Modified
2025-09-09 04:00
Summary
Schneider Electric Multiple Altivar Process Drives and Communication Modules
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
https://www.se.com/us/en/download/document/7EN52-0390/
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and
sustainability for all. We call this Life Is On.
Our mission is to be the trusted partner in Sustainability and Efficiency.
We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart
industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep
domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,
software and services, delivering digital twins to enable profitable growth for our customers.
We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries
to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our
meaningful purpose of a sustainable future for all.
www.se.com
Overview
Schneider Electric is aware of a vulnerability in its ATVdPAC module / ATV6000 Medium Voltage Altivar
Process Drives / ATV630/650/660/680/6A0/6B0/6L0 Altivar Process Drives /
ATV930/950/955/960/980/9A0/9B0/9L0 Altivar Process Drives / ATV340E Altivar Machine Drives /ATS490
Altivar Soft Starter / Altivar Process Communication Modules product(s).
Failure to apply remediation/mitigations provided below may risk Cross-Site Scripting, which could result in
partial loss of confidentiality and integrity of the workstation running a Web browser.
The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 (CVSS v4.0) https://www.first.org/cvss/calculator/4.0 . CVSS v3.1 will be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer's environment.
Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric’s Customer Care Center https://www.se.com/us/en/work/support/contacts.jsp if you need assistance removing a patch.
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Advisory Conversion Disclaimer
This ICSA is a verbatim republication of Schneider Electric CPCERT SEVD-2025-252-01 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Schneider Electric CPCERT directly for any questions regarding this advisory.
Critical infrastructure sectors
Critical infrastructure
Countries/areas deployed
Worldwide
Company headquarters location
France
Recommended Practices
CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
{ "document": { "acknowledgments": [ { "organization": "Schneider Electric CPCERT", "summary": "reporting this vulnerability to CISA." } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n", "title": "General Security Recommendations" }, { "category": "general", "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp", "title": "For More Information" }, { "category": "legal_disclaimer", "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION", "title": "LEGAL DISCLAIMER" }, { "category": "general", "text": "Schneider\u0027s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com", "title": "About Schneider Electric" }, { "category": "summary", "text": "Schneider Electric is aware of a vulnerability in its ATVdPAC module / ATV6000 Medium Voltage Altivar \r\nProcess Drives / ATV630/650/660/680/6A0/6B0/6L0 Altivar Process Drives / \r\nATV930/950/955/960/980/9A0/9B0/9L0 Altivar Process Drives / ATV340E Altivar Machine Drives /ATS490 \r\nAltivar Soft Starter / Altivar Process Communication Modules product(s). \r\nFailure to apply remediation/mitigations provided below may risk Cross-Site Scripting, which could result in \r\npartial loss of confidentiality and integrity of the workstation running a Web browser.", "title": "Overview" }, { "category": "other", "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 (CVSS v4.0) https://www.first.org/cvss/calculator/4.0 . CVSS v3.1 will be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u0027s environment." }, { "category": "other", "text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric\u2019s Customer Care Center https://www.se.com/us/en/work/support/contacts.jsp if you need assistance removing a patch. " }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "other", "text": "This ICSA is a verbatim republication of Schneider Electric CPCERT SEVD-2025-252-01 from a direct conversion of the vendor\u0027s Common Security Advisory Framework (CSAF) advisory. This is republished to CISA\u0027s website as a means of increasing visibility and is provided \"as-is\" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Schneider Electric CPCERT directly for any questions regarding this advisory.", "title": "Advisory Conversion Disclaimer" }, { "category": "other", "text": "Critical infrastructure", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "France", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" } ], "publisher": { "category": "other", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "Multiple Altivar Process Drives and Communication Modules - SEVD-2025-252-01 CSAF Version", "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-252-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-252-01.json" }, { "category": "self", "summary": "Multiple Altivar Process Drives and Communication Modules - SEVD-2025-252-01 PDF Version", "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-252-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-252-01.pdf" }, { "category": "external", "summary": "Recommended Cybersecurity Best Practices", "url": "https://www.se.com/us/en/download/document/7EN52-0390/" }, { "category": "self", "summary": "ICS Advisory ICSA-25-259-01 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2025/icsa-25-259-01.json" }, { "category": "self", "summary": "ICS Advisory ICSA-25-259-01 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-259-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Schneider Electric Multiple Altivar Process Drives and Communication Modules", "tracking": { "current_release_date": "2025-09-09T04:00:00.000000Z", "generator": { "date": "2025-09-16T16:34:28.221332Z", "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-25-259-01", "initial_release_date": "2025-09-09T04:00:00.000000Z", "revision_history": [ { "date": "2025-09-09T04:00:00.000000Z", "number": "1.0.0", "summary": "Original Release" } ], "status": "final", "version": "1.0.0" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003c25.0", "product": { "name": "Schneider Electric ATVdPAC module Versions prior to 25.0", "product_id": "CSAFPID-0001", "product_identification_helper": { "model_numbers": [ "VW3A3530D" ] } } }, { "category": "product_version", "name": "25.0", "product": { "name": "Schneider Electric ATVdPAC module Version 25.0", "product_id": "CSAFPID-0002", "product_identification_helper": { "model_numbers": [ "VW3A3530D" ] } } } ], "category": "product_name", "name": "ATVdPAC module" }, { "branches": [ { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV630 Altivar Process Drives All Versions", "product_id": "CSAFPID-0003" } } ], "category": "product_name", "name": "ATV630" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV650 Altivar Process Drives All Versions", "product_id": "CSAFPID-0004" } } ], "category": "product_name", "name": "ATV650" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV660 Altivar Process Drives All Versions", "product_id": "CSAFPID-0005" } } ], "category": "product_name", "name": "ATV660" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV680 Altivar Process Drives All Versions", "product_id": "CSAFPID-0006" } } ], "category": "product_name", "name": "ATV680" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV6A0 Altivar Process Drives All Versions", "product_id": "CSAFPID-0007" } } ], "category": "product_name", "name": "ATV6A0" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV6B0 Altivar Process Drives All Versions", "product_id": "CSAFPID-0008" } } ], "category": "product_name", "name": "ATV6B0" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV6L0 Altivar Process Drives All Versions", "product_id": "CSAFPID-0009" } } ], "category": "product_name", "name": "ATV6L0" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV930 Altivar Process Drives All Versions", "product_id": "CSAFPID-0010" } } ], "category": "product_name", "name": "ATV930" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV950 Altivar Process Drives All Versions", "product_id": "CSAFPID-0011" } } ], "category": "product_name", "name": "ATV950" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV955 Altivar Process Drives All Versions", "product_id": "CSAFPID-0012" } } ], "category": "product_name", "name": "ATV955" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV960 Altivar Process Drives All Versions", "product_id": "CSAFPID-0013" } } ], "category": "product_name", "name": "ATV960" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV980 Altivar Process Drives All Versions", "product_id": "CSAFPID-0014" } } ], "category": "product_name", "name": "ATV980" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV9A0 Altivar Process Drives All Versions", "product_id": "CSAFPID-0015" } } ], "category": "product_name", "name": "ATV9A0" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV9B0 Altivar Process Drives All Versions", "product_id": "CSAFPID-0016" } } ], "category": "product_name", "name": "ATV9B0" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV9L0 Altivar Process Drives All Versions", "product_id": "CSAFPID-0017" } } ], "category": "product_name", "name": "ATV9L0" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV991 Altivar Process Drives All Versions", "product_id": "CSAFPID-0018" } } ], "category": "product_name", "name": "ATV991" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV992 Altivar Process Drives All Versions", "product_id": "CSAFPID-0019" } } ], "category": "product_name", "name": "ATV992" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV993 Altivar Process Drives All Versions", "product_id": "CSAFPID-0020" } } ], "category": "product_name", "name": "ATV993" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV6000 Medium Voltage Altivar Process Drives All Versions", "product_id": "CSAFPID-0021" } } ], "category": "product_name", "name": "ATV6000 Medium Voltage" } ], "category": "product_family", "name": "Altivar Process Drives" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ILC992 InterLink Converter All Versions", "product_id": "CSAFPID-0022" } } ], "category": "product_name", "name": "ILC992 InterLink Converter" }, { "branches": [ { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATV340E Altivar Machine Drives All Versions", "product_id": "CSAFPID-0023" } } ], "category": "product_name", "name": "ATV340E" } ], "category": "product_family", "name": "Altivar Machine Drives" }, { "branches": [ { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric ATS490 Altivar Soft Starter All Versions", "product_id": "CSAFPID-0024" } } ], "category": "product_name", "name": "ATS490" } ], "category": "product_family", "name": "Altivar Soft Starter" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric Altivar Process Communication Mudules All Versions", "product_id": "CSAFPID-0025", "product_identification_helper": { "model_numbers": [ "VW3A3720" ] } } } ], "category": "product_name", "name": "Altivar Process Communication Mudules" }, { "branches": [ { "category": "product_version_range", "name": "vers:all/*", "product": { "name": "Schneider Electric Altivar Process Communication Mudules All Versions", "product_id": "CSAFPID-0026", "product_identification_helper": { "model_numbers": [ "VW3A3721" ] } } } ], "category": "product_name", "name": "Altivar Process Communication Mudules" } ], "category": "vendor", "name": "Schneider Electric" } ] }, "vulnerabilities": [ { "acknowledgments": [ { "names": [ "Thomas Weber", "David Blagojevic" ], "organization": "CyberDanube" } ], "cve": "CVE-2025-7746", "cwe": { "id": "CWE-79", "name": "Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027)" }, "notes": [ { "category": "description", "text": "CWE-79: Improper Neutralization of Input During Web Page Generation (\u0027Cross-site Scripting\u0027) vulnerability \r\nexists that could cause an unvalidated data injected by a malicious user potentially leading to modify or read \r\ndata in a victim\u2019s browser.", "title": "CVE Description" } ], "product_status": { "fixed": [ "CSAFPID-0002" ], "known_affected": [ "CSAFPID-0001", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008", "CSAFPID-0009", "CSAFPID-0010", "CSAFPID-0011", "CSAFPID-0012", "CSAFPID-0013", "CSAFPID-0014", "CSAFPID-0015", "CSAFPID-0016", "CSAFPID-0017", "CSAFPID-0018", "CSAFPID-0019", "CSAFPID-0020", "CSAFPID-0022", "CSAFPID-0023", "CSAFPID-0021", "CSAFPID-0024", "CSAFPID-0025", "CSAFPID-0026" ] }, "remediations": [ { "category": "vendor_fix", "details": "Version 25.0 of VW3A3530D: ATVdPAC module includes a \r\nfix for this vulnerability and is available upon request from \r\nSchneider Electric\u2019s Customer Care Center.", "product_ids": [ "CSAFPID-0001" ], "restart_required": { "category": "none" } }, { "category": "mitigation", "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following \r\nmitigations to reduce the risk of exploit:\r\n\u2022 End user cybersecurity awareness and \r\nworkstation protections\r\n\u2022 Deactivate the Webserver after use when \r\nnot needed. \r\n\u2022 Setup network segmentation and \r\nimplement a firewall to block all \r\nunauthorized access to port 80/HTTP \r\n\u2022 Use VPN (Virtual Private Networks) \r\ntunnels if remote access is required", "product_ids": [ "CSAFPID-0001" ], "restart_required": { "category": "none" } }, { "category": "mitigation", "details": "Schneider Electric is establishing a remediation \r\nplan for all future versions of \r\n\u2022 ATV6000 Medium Voltage Altivar Process \r\nDrives\r\n\u2022 ATV630/650/660/680/6A0/6B0 Altivar \r\nProcess Drives\r\n\u2022 ATV930/950/955/960/980/9A0/9B0/9L0/99\r\n1/992/993 Altivar Process Drives\r\n\u2022 ILC992 InterLink Converter \r\n\u2022 ATV340E Altivar Machine Drives\r\n\u2022 ATS490 Altivar Soft Starter\r\n\u2022 VW3A3720 \u0026 VW3A3721 Altivar Process \r\nCommunication Modules\r\nthat will include a fix for this vulnerability. We will \r\nupdate this document when the remediation is \r\navailable. Until then, customers should \r\nimmediately apply the following mitigations to \r\nreduce the risk of exploit:\r\n\u2022 End user cybersecurity awareness and \r\nworkstation protections\r\n\u2022 Deactivate the Webserver after use when \r\nnot needed. \r\n\u2022 Setup network segmentation and \r\nimplement a firewall to block all \r\nunauthorized access to port 80/HTTP \r\n\u2022 Use VPN (Virtual Private Networks) \r\ntunnels if remote access is required", "product_ids": [ "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008", "CSAFPID-0009", "CSAFPID-0010", "CSAFPID-0011", "CSAFPID-0012", "CSAFPID-0013", "CSAFPID-0014", "CSAFPID-0015", "CSAFPID-0016", "CSAFPID-0017", "CSAFPID-0018", "CSAFPID-0019", "CSAFPID-0020", "CSAFPID-0022", "CSAFPID-0023", "CSAFPID-0021", "CSAFPID-0024", "CSAFPID-0025" ], "restart_required": { "category": "none" } } ], "scores": [ { "cvss_v3": { "attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "NONE", "baseScore": 6.1, "baseSeverity": "MEDIUM", "confidentialityImpact": "LOW", "integrityImpact": "LOW", "privilegesRequired": "NONE", "scope": "CHANGED", "userInteraction": "REQUIRED", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:N", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0003", "CSAFPID-0004", "CSAFPID-0005", "CSAFPID-0006", "CSAFPID-0007", "CSAFPID-0008", "CSAFPID-0009", "CSAFPID-0010", "CSAFPID-0011", "CSAFPID-0012", "CSAFPID-0013", "CSAFPID-0014", "CSAFPID-0015", "CSAFPID-0016", "CSAFPID-0017", "CSAFPID-0018", "CSAFPID-0019", "CSAFPID-0020", "CSAFPID-0022", "CSAFPID-0023", "CSAFPID-0021", "CSAFPID-0024", "CSAFPID-0025", "CSAFPID-0026" ] } ], "title": "CVE-2025-7746" } ] }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…