icsa-25-254-08
Vulnerability from csaf_cisa
Published
2025-08-12 04:00
Modified
2025-09-09 04:00
Summary
Schneider Electric EcoStruxure
Notes
General Security Recommendations
We strongly recommend the following industry cybersecurity best practices.
* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.
* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.
* Place all controllers in locked cabinets and never leave them in the “Program” mode.
* Never connect programming software to any network other than the network intended for that device.
* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.
* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.
* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.
For more information refer to the Schneider Electric [Recommended Cybersecurity Best Practices](https://www.se.com/us/en/download/document/7EN52-0390/) document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.
For further information related to cybersecurity in Schneider Electric's products, visit the company's cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and
sustainability for all. We call this Life Is On.
Our mission is to be the trusted partner in Sustainability and Efficiency.
We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart
industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep
domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,
software and services, delivering digital twins to enable profitable growth for our customers.
We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries
to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our
meaningful purpose of a sustainable future for all.
www.se.com
Overview
Schneider Electric is aware of multiple vulnerabilities in EcoStruxure™ Building Operation Enterprise Server,
EcoStruxure™ Building Operation Enterprise Central, and EcoStruxure™ Workstation.
[EcoStruxure™ Building Operation (EBO)](https://www.se.com/us/en/product-range/62111-ecostruxure-building-operation-software/#overview) is an open and scalable software platform providing insight, control
and management of multiple building systems and devices in one mobile-enabled convenient view. It delivers
valuable data for decision-making to improve energy management and increase efficiency for better building
performance and comfort, reduced carbon, and more sustainable building environments.
Failure to apply the remediations below may risk credential theft and subsequent unauthorized access and
remote code execution from within the BMS network, which could result in data breaches, and operational disruptions.
September 2025 Update: Updated affected and fixed version details.
The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1
will be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without
incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score
the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as
the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed
by the vulnerabilities described in this document within a customer’s environment.
Customers should use appropriate patching methodologies when applying these patches to their systems. We
strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and
Development environment or on an offline infrastructure. Contact Schneider Electric's [Customer Care Center](https://www.se.com/us/en/work/support/contacts.jsp) if you need assistance removing a patch.
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Advisory Conversion Disclaimer
This ICSA is a verbatim republication of Schneider Electric CPCERT SEVD-2025-224-04 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Schneider Electric CPCERT directly for any questions regarding this advisory.
Critical infrastructure sectors
Critical Manufacturing, Energy
Countries/areas deployed
Worldwide
Company headquarters location
France
Recommended Practices
CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
{ "document": { "acknowledgments": [ { "organization": "Pentest Limited", "summary": "reporting these vulnerabilities to Schneider Electric." } ], "category": "csaf_security_advisory", "csaf_version": "2.0", "distribution": { "text": "Disclosure is not limited", "tlp": { "label": "WHITE", "url": "https://us-cert.cisa.gov/tlp/" } }, "lang": "en-US", "notes": [ { "category": "general", "text": "We strongly recommend the following industry cybersecurity best practices.\n\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\n\nFor more information refer to the Schneider Electric [Recommended Cybersecurity Best Practices](https://www.se.com/us/en/download/document/7EN52-0390/) document.", "title": "General Security Recommendations" }, { "category": "general", "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\n\nFor further information related to cybersecurity in Schneider Electric\u0027s products, visit the company\u0027s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp", "title": "For More Information" }, { "category": "legal_disclaimer", "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION", "title": "LEGAL DISCLAIMER" }, { "category": "general", "text": "Schneider\u0027s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com", "title": "About Schneider Electric" }, { "category": "summary", "text": "Schneider Electric is aware of multiple vulnerabilities in EcoStruxure\u2122 Building Operation Enterprise Server, \nEcoStruxure\u2122 Building Operation Enterprise Central, and EcoStruxure\u2122 Workstation.\n\n[EcoStruxure\u2122 Building Operation (EBO)](https://www.se.com/us/en/product-range/62111-ecostruxure-building-operation-software/#overview) is an open and scalable software platform providing insight, control \nand management of multiple building systems and devices in one mobile-enabled convenient view. It delivers \nvaluable data for decision-making to improve energy management and increase efficiency for better building \nperformance and comfort, reduced carbon, and more sustainable building environments.\n\nFailure to apply the remediations below may risk credential theft and subsequent unauthorized access and \nremote code execution from within the BMS network, which could result in data breaches, and operational disruptions.\n\nSeptember 2025 Update: Updated affected and fixed version details.", "title": "Overview" }, { "category": "other", "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1 \nwill be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without \nincorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score \nthe CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as \nthe presence of mitigations in that environment. Environmental metrics may refine the relative severity posed \nby the vulnerabilities described in this document within a customer\u2019s environment." }, { "category": "other", "text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We \nstrongly recommend the use of back-ups and evaluating the impact of these patches in a Test and \nDevelopment environment or on an offline infrastructure. Contact Schneider Electric\u0027s [Customer Care Center](https://www.se.com/us/en/work/support/contacts.jsp) if you need assistance removing a patch. " }, { "category": "legal_disclaimer", "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.", "title": "Legal Notice" }, { "category": "other", "text": "This ICSA is a verbatim republication of Schneider Electric CPCERT SEVD-2025-224-04 from a direct conversion of the vendor\u0027s Common Security Advisory Framework (CSAF) advisory. This is republished to CISA\u0027s website as a means of increasing visibility and is provided \"as-is\" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Schneider Electric CPCERT directly for any questions regarding this advisory.", "title": "Advisory Conversion Disclaimer" }, { "category": "other", "text": "Critical Manufacturing, Energy", "title": "Critical infrastructure sectors" }, { "category": "other", "text": "Worldwide", "title": "Countries/areas deployed" }, { "category": "other", "text": "France", "title": "Company headquarters location" }, { "category": "general", "text": "CISA recommends users take defensive measures to minimize the exploitation risk of this vulnerability.", "title": "Recommended Practices" }, { "category": "general", "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.", "title": "Recommended Practices" }, { "category": "general", "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.", "title": "Recommended Practices" }, { "category": "general", "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.", "title": "Recommended Practices" }, { "category": "general", "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.", "title": "Recommended Practices" } ], "publisher": { "category": "other", "contact_details": "central@cisa.dhs.gov", "name": "CISA", "namespace": "https://www.cisa.gov/" }, "references": [ { "category": "self", "summary": "EcoStruxure\u2122 Building Operation Enterprise Server, EcoStruxure\u2122 Building Operation Enterprise Central, and EcoStruxure\u2122 Workstation - SEVD-2025-224-04 CSAF Version", "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-224-04\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-224-04.json" }, { "category": "self", "summary": "EcoStruxure\u2122 Building Operation Enterprise Server, EcoStruxure\u2122 Building Operation Enterprise Central, and EcoStruxure\u2122 Workstation - SEVD-2025-224-04 PDF Version", "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-224-04\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-224-04.pdf" }, { "category": "external", "summary": "Recommended Cybersecurity Best Practices", "url": "https://www.se.com/us/en/download/document/7EN52-0390/" }, { "category": "self", "summary": "ICS Advisory ICSA-25-254-08 JSON", "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2025/icsa-25-254-08.json" }, { "category": "self", "summary": "ICS Advisory ICSA-25-254-08 - Web Version", "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-254-08" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/topics/industrial-control-systems" }, { "category": "external", "summary": "Recommended Practices", "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf" }, { "category": "external", "summary": "Recommended Practices", "url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B" } ], "title": "Schneider Electric EcoStruxure", "tracking": { "current_release_date": "2025-09-09T04:00:00.000000Z", "generator": { "date": "2025-09-11T16:38:12.692499Z", "engine": { "name": "CISA CSAF Generator", "version": "1.0.0" } }, "id": "ICSA-25-254-08", "initial_release_date": "2025-08-12T04:00:00.000000Z", "revision_history": [ { "date": "2025-08-12T04:00:00.000000Z", "number": "1.0.0", "summary": "Original Release" }, { "date": "2025-09-09T04:00:00.000000Z", "number": "2.0.0", "summary": "Updated affected and fixed version details." } ], "status": "final", "version": "2.0.0" } }, "product_tree": { "branches": [ { "branches": [ { "branches": [ { "category": "product_version_range", "name": "\u003e=7.x|\u003c7.0.2.348", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Server All 7.x versions prior to 7.0.2.348", "product_id": "CSAFPID-0001" } }, { "category": "product_version", "name": "7.0.2.348", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Server Version 7.0.2.348", "product_id": "CSAFPID-0002" } }, { "category": "product_version_range", "name": "\u003e=6.x|\u003c6.0.4.10001CP8", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Server All 6.x versions prior to 6.0.4.10001 (CP8)", "product_id": "CSAFPID-0003" } }, { "category": "product_version", "name": "6.0.4.10001_CP8", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Server Version 6.0.4.10001 (CP8)", "product_id": "CSAFPID-0004" } }, { "category": "product_version_range", "name": "\u003e=5.x|\u003c5.0.3.17009CP16", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Server All 5.x versions prior to 5.0.3.17009 (CP16)", "product_id": "CSAFPID-0005" } }, { "category": "product_version", "name": "5.0.3.17009_CP16", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Server Version 5.0.3.17009 (CP16)", "product_id": "CSAFPID-0006" } } ], "category": "product_name", "name": "EcoStruxure\u2122 Building Operation Enterprise Server" }, { "branches": [ { "category": "product_version_range", "name": "\u003e=7.x|\u003c7.0.2.348", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Central All 7.x versions prior to 7.0.2.348", "product_id": "CSAFPID-0007" } }, { "category": "product_version", "name": "7.0.2.348", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Central Version 7.0.2.348", "product_id": "CSAFPID-0008" } }, { "category": "product_version_range", "name": "\u003e=6.x|\u003c6.0.4.10001CP8", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Central All 6.x versions prior to 6.0.4.10001 (CP8)", "product_id": "CSAFPID-0009" } }, { "category": "product_version", "name": "6.0.4.10001_CP8", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Central Version 6.0.4.10001 (CP8)", "product_id": "CSAFPID-0010" } }, { "category": "product_version_range", "name": "\u003e=5.x|\u003c5.0.3.17009CP16", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Central All 5.x versions prior to 5.0.3.17009 (CP16)", "product_id": "CSAFPID-0011" } }, { "category": "product_version", "name": "5.0.3.17009_CP16", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Enterprise Central Version 5.0.3.17009 (CP16)", "product_id": "CSAFPID-0012" } } ], "category": "product_name", "name": "EcoStruxure\u2122 Building Operation Enterprise Central" }, { "branches": [ { "category": "product_version_range", "name": "\u003e=7.x|\u003c7.0.2.348", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Workstation All 7.x versions prior to 7.0.2.348", "product_id": "CSAFPID-0013" } }, { "category": "product_version", "name": "7.0.2.348", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Workstation Version 7.0.2.348", "product_id": "CSAFPID-0014" } }, { "category": "product_version_range", "name": "\u003e=6.x|\u003c6.0.4.10001CP8", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Workstation All 6.x versions prior to 6.0.4.10001 (CP8)", "product_id": "CSAFPID-0015" } }, { "category": "product_version", "name": "6.0.4.10001_CP8", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Workstation Version 6.0.4.10001 (CP8)", "product_id": "CSAFPID-0016" } }, { "category": "product_version_range", "name": "\u003e=5.x|\u003c5.0.3.17009CP16", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Workstation All 5.x versions prior to 5.0.3.17009 (CP16)", "product_id": "CSAFPID-0017" } }, { "category": "product_version", "name": "5.0.3.17009_CP16", "product": { "name": "Schneider Electric EcoStruxure\u2122 Building Operation Workstation Version 5.0.3.17009 (CP16)", "product_id": "CSAFPID-0018" } } ], "category": "product_name", "name": "EcoStruxure\u2122 Building Operation Workstation" } ], "category": "vendor", "name": "Schneider Electric" } ] }, "vulnerabilities": [ { "acknowledgments": [ { "organization": "Pentest Limited" } ], "cve": "CVE-2025-8449", "cwe": { "id": "CWE-400", "name": "Uncontrolled Resource Consumption" }, "notes": [ { "category": "description", "text": "CWE-400: Uncontrolled Resource Consumption vulnerability exists that could cause a denial of service when \r\nan authenticated user sends a specially crafted request to a specific endpoint from within the BMS network.", "title": "CVE Description" } ], "product_status": { "fixed": [ "CSAFPID-0002", "CSAFPID-0004", "CSAFPID-0006", "CSAFPID-0008", "CSAFPID-0010", "CSAFPID-0012", "CSAFPID-0014", "CSAFPID-0016", "CSAFPID-0018" ], "known_affected": [ "CSAFPID-0001", "CSAFPID-0003", "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0009", "CSAFPID-0011", "CSAFPID-0013", "CSAFPID-0015", "CSAFPID-0017" ] }, "remediations": [ { "category": "vendor_fix", "details": "The following versions of Enterprise Server, Enterprise Central, Workstation include a fix for these vulnerabilities: \n\n\u2022 7.0.2.348 \n\nStep1: Locate the appropriate version for your system on the [EcoExpert Software Center](https://ecoxpert.se.com/software-center/building-automation/ebo-system/building-operation-2025-version-7.0). \n\nStep 2: Follow the installation instructions provided in the accompanying readme file.\n\nAdditionally, ensure you are following the [EBO hardening guidelines](https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7).", "product_ids": [ "CSAFPID-0001", "CSAFPID-0007", "CSAFPID-0013" ], "restart_required": { "category": "none" }, "url": "https://ecoxpert.se.com/software-center/building-automation/ebo-system/building-operation-2025-version-7.0" }, { "category": "vendor_fix", "details": "The following versions of Enterprise Server, Enterprise Central, Workstation include a fix for these vulnerabilities: \n\n\u2022 6.0.4.10001 (CP8) \n\nStep1: Locate the appropriate version for your system on the [EcoExpert Software Center](https://ecoxpert.se.com/de/software-center/building-automation/ebo-system/building-operation-2024-version-6.0). \n\nStep 2: Follow the installation instructions provided in the accompanying readme file.\n\nAdditionally, ensure you are following the [EBO hardening guidelines](https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7).", "product_ids": [ "CSAFPID-0003", "CSAFPID-0009", "CSAFPID-0015" ], "restart_required": { "category": "none" }, "url": "https://ecoxpert.se.com/de/software-center/building-automation/ebo-system/building-operation-2024-version-6.0" }, { "category": "vendor_fix", "details": "The following versions of Enterprise Server, Enterprise Central, Workstation include a fix for these vulnerabilities: \n\n\u2022 5.0.3.17009 (CP16) \n\nStep1: Locate the appropriate version for your system on the [EcoExpert Software Center](https://ecoxpert.se.com/de/software-center/building-automation/ebo-system/building-operation-2023-version-5.0). \n\nStep 2: Follow the installation instructions provided in the accompanying readme file.\n\nAdditionally, ensure you are following the [EBO hardening guidelines](https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7).", "product_ids": [ "CSAFPID-0005", "CSAFPID-0011", "CSAFPID-0017" ], "restart_required": { "category": "none" }, "url": "https://ecoxpert.se.com/de/software-center/building-automation/ebo-system/building-operation-2023-version-5.0" }, { "category": "mitigation", "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following \r\nmitigations to reduce the risk of exploit: \r\n\n* Implement strong access controls to limit system access to authorized personnel. Use multi factor \r\nauthentication if using EBO version 7.0 or later\r\n\n* Use firewalls to segregate networks and protect the building management system \r\n\n* Regularly monitor system activity\r\n\n* Ensure you are following [EBO hardening guidelines](https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7).", "product_ids": [ "CSAFPID-0001", "CSAFPID-0003", "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0009", "CSAFPID-0011", "CSAFPID-0013", "CSAFPID-0015", "CSAFPID-0017" ], "restart_required": { "category": "none" }, "url": "https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7" } ], "scores": [ { "cvss_v3": { "attackComplexity": "HIGH", "attackVector": "ADJACENT_NETWORK", "availabilityImpact": "HIGH", "baseScore": 4.5, "baseSeverity": "MEDIUM", "confidentialityImpact": "NONE", "integrityImpact": "NONE", "privilegesRequired": "LOW", "scope": "UNCHANGED", "userInteraction": "REQUIRED", "vectorString": "CVSS:3.1/AV:A/AC:H/PR:L/UI:R/S:U/C:N/I:N/A:H", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0003", "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0009", "CSAFPID-0011", "CSAFPID-0013", "CSAFPID-0015", "CSAFPID-0017" ] } ], "title": "CVE-2025-8449" }, { "acknowledgments": [ { "organization": "Pentest Limited" } ], "cve": "CVE-2025-8448", "cwe": { "id": "CWE-200", "name": "Exposure of Sensitive Information to an Unauthorized Actor" }, "notes": [ { "category": "description", "text": "CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists that could cause \r\nunauthorized access to sensitive credential data when an attacker is able to capture local SMB traffic between \r\na valid user within the BMS network and the vulnerable products.", "title": "CVE Description" } ], "product_status": { "fixed": [ "CSAFPID-0002", "CSAFPID-0004", "CSAFPID-0006", "CSAFPID-0008", "CSAFPID-0010", "CSAFPID-0012", "CSAFPID-0014", "CSAFPID-0016", "CSAFPID-0018" ], "known_affected": [ "CSAFPID-0001", "CSAFPID-0003", "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0009", "CSAFPID-0011", "CSAFPID-0013", "CSAFPID-0015", "CSAFPID-0017" ] }, "remediations": [ { "category": "vendor_fix", "details": "The following versions of Enterprise Server, Enterprise Central, Workstation include a fix for these vulnerabilities: \n\n\u2022 7.0.2.348 \n\nStep1: Locate the appropriate version for your system on the [EcoExpert Software Center](https://ecoxpert.se.com/software-center/building-automation/ebo-system/building-operation-2025-version-7.0). \n\nStep 2: Follow the installation instructions provided in the accompanying readme file.\n\nAdditionally, ensure you are following the [EBO hardening guidelines](https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7).", "product_ids": [ "CSAFPID-0001", "CSAFPID-0007", "CSAFPID-0013" ], "restart_required": { "category": "none" }, "url": "https://ecoxpert.se.com/software-center/building-automation/ebo-system/building-operation-2025-version-7.0" }, { "category": "vendor_fix", "details": "The following versions of Enterprise Server, Enterprise Central, Workstation include a fix for these vulnerabilities: \n\n\u2022 6.0.4.10001 (CP8) \n\nStep1: Locate the appropriate version for your system on the [EcoExpert Software Center](https://ecoxpert.se.com/de/software-center/building-automation/ebo-system/building-operation-2024-version-6.0). \n\nStep 2: Follow the installation instructions provided in the accompanying readme file.\n\nAdditionally, ensure you are following the [EBO hardening guidelines](https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7).", "product_ids": [ "CSAFPID-0003", "CSAFPID-0009", "CSAFPID-0015" ], "restart_required": { "category": "none" }, "url": "https://ecoxpert.se.com/de/software-center/building-automation/ebo-system/building-operation-2024-version-6.0" }, { "category": "vendor_fix", "details": "The following versions of Enterprise Server, Enterprise Central, Workstation include a fix for these vulnerabilities: \n\n\u2022 5.0.3.17009 (CP16) \n\nStep1: Locate the appropriate version for your system on the [EcoExpert Software Center](https://ecoxpert.se.com/de/software-center/building-automation/ebo-system/building-operation-2023-version-5.0). \n\nStep 2: Follow the installation instructions provided in the accompanying readme file.\n\nAdditionally, ensure you are following the [EBO hardening guidelines](https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7).", "product_ids": [ "CSAFPID-0005", "CSAFPID-0011", "CSAFPID-0017" ], "restart_required": { "category": "none" }, "url": "https://ecoxpert.se.com/de/software-center/building-automation/ebo-system/building-operation-2023-version-5.0" }, { "category": "mitigation", "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following \r\nmitigations to reduce the risk of exploit: \r\n\n* Implement strong access controls to limit system access to authorized personnel. Use multi factor \r\nauthentication if using EBO version 7.0 or later\r\n\n* Use firewalls to segregate networks and protect the building management system \r\n\n* Regularly monitor system activity\r\n\n* Ensure you are following [EBO hardening guidelines](https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7).", "product_ids": [ "CSAFPID-0001", "CSAFPID-0003", "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0009", "CSAFPID-0011", "CSAFPID-0013", "CSAFPID-0015", "CSAFPID-0017" ], "restart_required": { "category": "none" }, "url": "https://ecostruxure-building-help.se.com/bms/Topics/show.castle?id=14923\u0026productversion=7" } ], "scores": [ { "cvss_v3": { "attackComplexity": "HIGH", "attackVector": "ADJACENT_NETWORK", "availabilityImpact": "NONE", "baseScore": 2.3, "baseSeverity": "LOW", "confidentialityImpact": "LOW", "integrityImpact": "NONE", "privilegesRequired": "LOW", "scope": "UNCHANGED", "userInteraction": "REQUIRED", "vectorString": "CVSS:3.1/AV:A/AC:H/PR:L/UI:R/S:U/C:L/I:N/A:N", "version": "3.1" }, "products": [ "CSAFPID-0001", "CSAFPID-0003", "CSAFPID-0005", "CSAFPID-0007", "CSAFPID-0009", "CSAFPID-0011", "CSAFPID-0013", "CSAFPID-0015", "CSAFPID-0017" ] } ], "title": "CVE-2025-8448" } ] }
Loading…
Loading…
Sightings
Author | Source | Type | Date |
---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…