icsa-22-272-02
Vulnerability from csaf_cisa
Published
2022-09-29 00:00
Modified
2022-09-29 00:00
Summary
Hitachi Energy MicroSCADA Pro X SYS600

Notes

CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
Successful exploitation of these vulnerabilities could cause the affected modules in the product to stop working.
Critical infrastructure sectors
Energy
Countries/areas deployed
Worldwide
Company headquarters location
Switzerland
Recommended Practices
CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should:
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Exploitability
No known public exploits specifically target this vulnerability. This vulnerability is exploitable remotely. This vulnerability has a low attack complexity.



{
  "document": {
    "acknowledgments": [
      {
        "organization": "Hitachi Energy",
        "summary": "reporting these vulnerabilities to CISA"
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://us-cert.cisa.gov/tlp/"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
        "title": "CISA Disclaimer"
      },
      {
        "category": "legal_disclaimer",
        "text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
        "title": "Legal Notice"
      },
      {
        "category": "summary",
        "text": "Successful exploitation of these vulnerabilities could cause the affected modules in the product to stop working.",
        "title": "Risk evaluation"
      },
      {
        "category": "other",
        "text": "Energy",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "Switzerland",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability these vulnerabilities. Specifically, users should:",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage at cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "other",
        "text": "No known public exploits specifically target this vulnerability. This vulnerability is exploitable remotely. This vulnerability has a low attack complexity.",
        "title": "Exploitability"
      }
    ],
    "publisher": {
      "category": "coordinator",
      "contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-22-272-02 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2022/icsa-22-272-02.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-22-272-02 Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-272-02"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-22-272-02"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      }
    ],
    "title": "Hitachi Energy MicroSCADA Pro X SYS600",
    "tracking": {
      "current_release_date": "2022-09-29T00:00:00.000000Z",
      "generator": {
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.0.0"
        }
      },
      "id": "ICSA-22-272-02",
      "initial_release_date": "2022-09-29T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2022-09-29T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Publication Date"
        }
      ],
      "status": "final",
      "version": "1"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version",
                "name": "9.x",
                "product": {
                  "name": "SYS600: 9.x versions",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "SYS600"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "\u003c= 10.3.1",
                "product": {
                  "name": "SYS600: 10.3.1 and earlier",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "SYS600"
          }
        ],
        "category": "vendor",
        "name": "Hitachi Energy"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2020-25692",
      "cwe": {
        "id": "CWE-1357",
        "name": "Reliance on Insufficiently Trustworthy Component"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Hitachi Energy is aware of public reports of vulnerabilities in third-party open-source software components (OpenLDAP and OpenSSL) used in MicroSCADA Pro/X SYS600 products.CVE-2020-25692 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2020-25692"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "For SYS600 9.4: upgrade to at least SYS600 version 10.4.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "For SYS600 10.x: update to at least SYS600 version 10.4.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Hitachi Energy recommends following 1MRK511518 MicroSCADA X Cyber Security Deployment Guidelines.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "For additional information and support, users should contact Hitachi Energy service organization.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://www.hitachienergy.com/contact-us/"
        },
        {
          "category": "mitigation",
          "details": "Physically protect process control systems from unauthorized direct access.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Separate process control systems from the internet and other networks using firewall system with minimal open ports.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Process control systems should not be used for internet surfing, instant messaging, or email.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Portable computers and removable storage media should be carefully scanned for viruses connecting to a control system",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, see Hitachi Energy advisory 8DBD000107.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000107"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        }
      ]
    },
    {
      "cve": "CVE-2022-0778",
      "cwe": {
        "id": "CWE-1357",
        "name": "Reliance on Insufficiently Trustworthy Component"
      },
      "notes": [
        {
          "category": "summary",
          "text": "Hitachi Energy is aware of public reports of vulnerabilities in third-party open-source software components (OpenLDAP and OpenSSL) used in MicroSCADA Pro/X SYS600 products.CVE-2022-0778 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).",
          "title": "Vulnerability Summary"
        }
      ],
      "product_status": {
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "web.nvd.nist.gov",
          "url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2022-0778"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "For SYS600 9.4: upgrade to at least SYS600 version 10.4.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "vendor_fix",
          "details": "For SYS600 10.x: update to at least SYS600 version 10.4.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Hitachi Energy recommends following 1MRK511518 MicroSCADA X Cyber Security Deployment Guidelines.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "For additional information and support, users should contact Hitachi Energy service organization.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://www.hitachienergy.com/contact-us/"
        },
        {
          "category": "mitigation",
          "details": "Physically protect process control systems from unauthorized direct access.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Separate process control systems from the internet and other networks using firewall system with minimal open ports.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Process control systems should not be used for internet surfing, instant messaging, or email.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "Portable computers and removable storage media should be carefully scanned for viruses connecting to a control system",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        },
        {
          "category": "mitigation",
          "details": "For more information, see Hitachi Energy advisory 8DBD000107.",
          "product_ids": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ],
          "url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000107"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "baseScore": 7.5,
            "baseSeverity": "HIGH",
            "vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
            "version": "3.0"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        }
      ]
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
  • Confirmed: The vulnerability is confirmed from an analyst perspective.
  • Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
  • Patched: This vulnerability was successfully patched by the user reporting the sighting.
  • Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
  • Not confirmed: The user expresses doubt about the veracity of the vulnerability.
  • Not patched: This vulnerability was not successfully patched by the user reporting the sighting.