gsd-2023-28489
Vulnerability from gsd
Modified
2023-12-13 01:20
Details
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter “Remote Operation” is enabled. The parameter is disabled by default.
The vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.
Aliases
Aliases
{
"GSD": {
"alias": "CVE-2023-28489",
"id": "GSD-2023-28489"
},
"gsd": {
"metadata": {
"exploitCode": "unknown",
"remediation": "unknown",
"reportConfidence": "confirmed",
"type": "vulnerability"
},
"osvSchema": {
"aliases": [
"CVE-2023-28489"
],
"details": "A vulnerability has been identified in CP-8031 MASTER MODULE (All versions \u003c CPCI85 V05), CP-8050 MASTER MODULE (All versions \u003c CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter \u201cRemote Operation\u201d is enabled. The parameter is disabled by default.\r\nThe vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.",
"id": "GSD-2023-28489",
"modified": "2023-12-13T01:20:48.940682Z",
"schema_version": "1.4.0"
}
},
"namespaces": {
"cve.org": {
"CVE_data_meta": {
"ASSIGNER": "productcert@siemens.com",
"ID": "CVE-2023-28489",
"STATE": "PUBLIC"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "CP-8031 MASTER MODULE",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions \u003c CPCI85 V05"
}
]
}
},
{
"product_name": "CP-8050 MASTER MODULE",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions \u003c CPCI85 V05"
}
]
}
}
]
},
"vendor_name": "Siemens"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "A vulnerability has been identified in CP-8031 MASTER MODULE (All versions \u003c CPCI85 V05), CP-8050 MASTER MODULE (All versions \u003c CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter \u201cRemote Operation\u201d is enabled. The parameter is disabled by default.\r\nThe vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device."
}
]
},
"impact": {
"cvss": [
{
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C",
"version": "3.1"
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"cweId": "CWE-77",
"lang": "eng",
"value": "CWE-77: Improper Neutralization of Special Elements used in a Command (\u0027Command Injection\u0027)"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-472454.pdf",
"refsource": "MISC",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-472454.pdf"
},
{
"name": "http://seclists.org/fulldisclosure/2023/Jul/14",
"refsource": "MISC",
"url": "http://seclists.org/fulldisclosure/2023/Jul/14"
},
{
"name": "http://packetstormsecurity.com/files/173370/Siemens-A8000-CP-8050-CP-8031-Code-Execution-Command-Injection.html",
"refsource": "MISC",
"url": "http://packetstormsecurity.com/files/173370/Siemens-A8000-CP-8050-CP-8031-Code-Execution-Command-Injection.html"
}
]
}
},
"nvd.nist.gov": {
"configurations": {
"CVE_data_version": "4.0",
"nodes": [
{
"children": [
{
"children": [],
"cpe_match": [
{
"cpe23Uri": "cpe:2.3:o:siemens:cp-8031_firmware:*:*:*:*:*:*:*:*",
"cpe_name": [],
"versionEndExcluding": "cpci85_v05",
"vulnerable": true
}
],
"operator": "OR"
},
{
"children": [],
"cpe_match": [
{
"cpe23Uri": "cpe:2.3:h:siemens:cp-8031:-:*:*:*:*:*:*:*",
"cpe_name": [],
"vulnerable": false
}
],
"operator": "OR"
}
],
"cpe_match": [],
"operator": "AND"
},
{
"children": [
{
"children": [],
"cpe_match": [
{
"cpe23Uri": "cpe:2.3:o:siemens:cp-8050_firmware:*:*:*:*:*:*:*:*",
"cpe_name": [],
"versionEndExcluding": "cpci85_v05",
"vulnerable": true
}
],
"operator": "OR"
},
{
"children": [],
"cpe_match": [
{
"cpe23Uri": "cpe:2.3:h:siemens:cp-8050:-:*:*:*:*:*:*:*",
"cpe_name": [],
"vulnerable": false
}
],
"operator": "OR"
}
],
"cpe_match": [],
"operator": "AND"
}
]
},
"cve": {
"CVE_data_meta": {
"ASSIGNER": "productcert@siemens.com",
"ID": "CVE-2023-28489"
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "en",
"value": "A vulnerability has been identified in CP-8031 MASTER MODULE (All versions \u003c CPCI85 V05), CP-8050 MASTER MODULE (All versions \u003c CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter \u201cRemote Operation\u201d is enabled. The parameter is disabled by default.\r\nThe vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "en",
"value": "CWE-77"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-472454.pdf",
"refsource": "MISC",
"tags": [
"Vendor Advisory"
],
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-472454.pdf"
},
{
"name": "http://seclists.org/fulldisclosure/2023/Jul/14",
"refsource": "MISC",
"tags": [],
"url": "http://seclists.org/fulldisclosure/2023/Jul/14"
},
{
"name": "http://packetstormsecurity.com/files/173370/Siemens-A8000-CP-8050-CP-8031-Code-Execution-Command-Injection.html",
"refsource": "MISC",
"tags": [],
"url": "http://packetstormsecurity.com/files/173370/Siemens-A8000-CP-8050-CP-8031-Code-Execution-Command-Injection.html"
}
]
}
},
"impact": {
"baseMetricV3": {
"cvssV3": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"exploitabilityScore": 3.9,
"impactScore": 5.9
}
},
"lastModifiedDate": "2023-07-11T18:15Z",
"publishedDate": "2023-04-11T10:15Z"
}
}
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…