GCVE Workshop - 22 September 2026 (14:00-18:00), Luxembourg Before The Vulnopticon Conference - Registration

CVE-2026-61884 (GCVE-0-2026-61884)

Vulnerability from cvelistv5 – Published: 2026-07-24 21:40 – Updated: 2026-09-04 21:28
VLAI
Title
Tycon Systems TPDIN-Monitor-WEB2 Missing Authentication for Critical Function
Summary
The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.
SSVC
Exploitation: none Automatable: yes Technical Impact: total
CISA Coordinator · CISA-ADP (v2.0.3)
Decision recorded 2026-07-27 14:32 UTC
CWE
Impacted products
Vendor Product Version CPE status
Tycon Systems TPDIN-Monitor-WEB2 Affected: 0 , < 2.4.5 (custom)
Unaffected: 2.4.5
guessed Create a notification for this product.
Show details on NVD website

{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2026-61884",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "yes"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2026-07-27T14:32:51.857132Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2026-07-27T14:33:00.776Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "TPDIN-Monitor-WEB2",
          "vendor": "Tycon Systems",
          "versions": [
            {
              "lessThan": "2.4.5",
              "status": "affected",
              "version": "0",
              "versionType": "custom"
            },
            {
              "status": "unaffected",
              "version": "2.4.5"
            }
          ]
        }
      ],
      "credits": [
        {
          "lang": "en",
          "type": "finder",
          "value": "Abdiwelli Guled reported this vulnerability to CISA."
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cdiv\u003e\u003cspan\u003eThe \u003c/span\u003eTycon Systems TPDIN-Monitor-WEB2\nships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.\n\n\u003c/div\u003e"
            }
          ],
          "value": "The Tycon Systems TPDIN-Monitor-WEB2\nships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment."
        }
      ],
      "metrics": [
        {
          "cvssV3_1": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        },
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "LOW",
            "attackRequirements": "NONE",
            "attackVector": "NETWORK",
            "baseScore": 9.3,
            "baseSeverity": "CRITICAL",
            "exploitMaturity": "NOT_DEFINED",
            "privilegesRequired": "NONE",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "NONE",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "NONE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "HIGH",
            "vulnIntegrityImpact": "HIGH",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-306",
              "description": "CWE-306",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2026-09-04T21:28:52.355Z",
        "orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
        "shortName": "icscert"
      },
      "references": [
        {
          "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-26-202-01"
        },
        {
          "url": "https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-202-01.json"
        }
      ],
      "solutions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "\u003cp\u003eTycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to security@tyconsystems.com.\u003cbr\u003e\u003cbr\u003eTycon Systems recommends setting an administrative username and strong password on the Network Configuration page and confirming in a private browser window that a login is required, for units still running firmware 2.4.4 or earlier. Repeat this after any factory reset.\u003cbr\u003e\u003cbr\u003eTycon Systems recommends not exposing the web interface to the Internet, as it is HTTP only. The unit should be kept on a private network, behind a firewall or VPN.\u003c/p\u003e"
            }
          ],
          "value": "Tycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to security@tyconsystems.com.\n\nTycon Systems recommends setting an administrative username and strong password on the Network Configuration page and confirming in a private browser window that a login is required, for units still running firmware 2.4.4 or earlier. Repeat this after any factory reset.\n\nTycon Systems recommends not exposing the web interface to the Internet, as it is HTTP only. The unit should be kept on a private network, behind a firewall or VPN."
        }
      ],
      "source": {
        "advisory": "ICSA-26-202-01",
        "discovery": "EXTERNAL"
      },
      "title": "Tycon Systems TPDIN-Monitor-WEB2 Missing Authentication for Critical Function",
      "x_generator": {
        "engine": "Vulnogram 1.0.4"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
    "assignerShortName": "icscert",
    "cveId": "CVE-2026-61884",
    "datePublished": "2026-07-24T21:40:40.449Z",
    "dateReserved": "2026-07-13T18:17:10.040Z",
    "dateUpdated": "2026-09-04T21:28:52.355Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.2",
  "vulnerability-lookup:meta": {
    "epss": {
      "cve": "CVE-2026-61884",
      "date": "2026-09-10",
      "epss": "0.00448",
      "percentile": "0.37722"
    },
    "nvd": "{\"cve\":{\"id\":\"CVE-2026-61884\",\"sourceIdentifier\":\"ics-cert@hq.dhs.gov\",\"published\":\"2026-07-24T22:16:50.963\",\"lastModified\":\"2026-09-04T22:17:17.723\",\"vulnStatus\":\"Deferred\",\"cveTags\":[],\"descriptions\":[{\"lang\":\"en\",\"value\":\"The Tycon Systems TPDIN-Monitor-WEB2\\nships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.\"}],\"affected\":[{\"source\":\"ics-cert@hq.dhs.gov\",\"affectedData\":[{\"vendor\":\"Tycon Systems\",\"product\":\"TPDIN-Monitor-WEB2\",\"defaultStatus\":\"unaffected\",\"versions\":[{\"version\":\"0\",\"lessThan\":\"2.4.5\",\"versionType\":\"custom\",\"status\":\"affected\"},{\"version\":\"2.4.5\",\"status\":\"unaffected\"}]}]}],\"metrics\":{\"cvssMetricV40\":[{\"source\":\"ics-cert@hq.dhs.gov\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"4.0\",\"vectorString\":\"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X\",\"baseScore\":9.3,\"baseSeverity\":\"CRITICAL\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"attackRequirements\":\"NONE\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"vulnConfidentialityImpact\":\"HIGH\",\"vulnIntegrityImpact\":\"HIGH\",\"vulnAvailabilityImpact\":\"HIGH\",\"subConfidentialityImpact\":\"NONE\",\"subIntegrityImpact\":\"NONE\",\"subAvailabilityImpact\":\"NONE\",\"exploitMaturity\":\"NOT_DEFINED\",\"confidentialityRequirement\":\"NOT_DEFINED\",\"integrityRequirement\":\"NOT_DEFINED\",\"availabilityRequirement\":\"NOT_DEFINED\",\"modifiedAttackVector\":\"NOT_DEFINED\",\"modifiedAttackComplexity\":\"NOT_DEFINED\",\"modifiedAttackRequirements\":\"NOT_DEFINED\",\"modifiedPrivilegesRequired\":\"NOT_DEFINED\",\"modifiedUserInteraction\":\"NOT_DEFINED\",\"modifiedVulnConfidentialityImpact\":\"NOT_DEFINED\",\"modifiedVulnIntegrityImpact\":\"NOT_DEFINED\",\"modifiedVulnAvailabilityImpact\":\"NOT_DEFINED\",\"modifiedSubConfidentialityImpact\":\"NOT_DEFINED\",\"modifiedSubIntegrityImpact\":\"NOT_DEFINED\",\"modifiedSubAvailabilityImpact\":\"NOT_DEFINED\",\"Safety\":\"NOT_DEFINED\",\"Automatable\":\"NOT_DEFINED\",\"Recovery\":\"NOT_DEFINED\",\"valueDensity\":\"NOT_DEFINED\",\"vulnerabilityResponseEffort\":\"NOT_DEFINED\",\"providerUrgency\":\"NOT_DEFINED\"}}],\"cvssMetricV31\":[{\"source\":\"ics-cert@hq.dhs.gov\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H\",\"baseScore\":9.8,\"baseSeverity\":\"CRITICAL\",\"attackVector\":\"NETWORK\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"NONE\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"HIGH\",\"integrityImpact\":\"HIGH\",\"availabilityImpact\":\"HIGH\"},\"exploitabilityScore\":3.9,\"impactScore\":5.9}],\"ssvcV203\":[{\"source\":\"134c704f-9b21-4f2e-91b3-4a467353bcc0\",\"ssvcData\":{\"timestamp\":\"2026-07-27T14:32:51.857132Z\",\"id\":\"CVE-2026-61884\",\"options\":[{\"exploitation\":\"none\"},{\"automatable\":\"yes\"},{\"technicalImpact\":\"total\"}],\"role\":\"CISA Coordinator\",\"version\":\"2.0.3\"}}]},\"weaknesses\":[{\"source\":\"ics-cert@hq.dhs.gov\",\"type\":\"Primary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-306\"}]}],\"references\":[{\"url\":\"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-202-01.json\",\"source\":\"ics-cert@hq.dhs.gov\"},{\"url\":\"https://www.cisa.gov/news-events/ics-advisories/icsa-26-202-01\",\"source\":\"ics-cert@hq.dhs.gov\"}]}}",
    "vulnrichment": {
      "containers": "{\"adp\": [{\"title\": \"CISA ADP Vulnrichment\", \"metrics\": [{\"other\": {\"type\": \"ssvc\", \"content\": {\"id\": \"CVE-2026-61884\", \"role\": \"CISA Coordinator\", \"options\": [{\"Exploitation\": \"none\"}, {\"Automatable\": \"yes\"}, {\"Technical Impact\": \"total\"}], \"version\": \"2.0.3\", \"timestamp\": \"2026-07-27T14:32:51.857132Z\"}}}], \"providerMetadata\": {\"orgId\": \"134c704f-9b21-4f2e-91b3-4a467353bcc0\", \"shortName\": \"CISA-ADP\", \"dateUpdated\": \"2026-07-27T14:32:57.239Z\"}}], \"cna\": {\"title\": \"Tycon Systems TPDIN-Monitor-WEB2 Missing Authentication for Critical Function\", \"source\": {\"advisory\": \"ICSA-26-202-01\", \"discovery\": \"EXTERNAL\"}, \"credits\": [{\"lang\": \"en\", \"type\": \"finder\", \"value\": \"Abdiwelli Guled reported this vulnerability to CISA.\"}], \"metrics\": [{\"format\": \"CVSS\", \"cvssV3_1\": {\"scope\": \"UNCHANGED\", \"version\": \"3.1\", \"baseScore\": 9.8, \"attackVector\": \"NETWORK\", \"baseSeverity\": \"CRITICAL\", \"vectorString\": \"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H\", \"integrityImpact\": \"HIGH\", \"userInteraction\": \"NONE\", \"attackComplexity\": \"LOW\", \"availabilityImpact\": \"HIGH\", \"privilegesRequired\": \"NONE\", \"confidentialityImpact\": \"HIGH\"}, \"scenarios\": [{\"lang\": \"en\", \"value\": \"GENERAL\"}]}, {\"format\": \"CVSS\", \"cvssV4_0\": {\"Safety\": \"NOT_DEFINED\", \"version\": \"4.0\", \"Recovery\": \"NOT_DEFINED\", \"baseScore\": 9.3, \"Automatable\": \"NOT_DEFINED\", \"attackVector\": \"NETWORK\", \"baseSeverity\": \"CRITICAL\", \"valueDensity\": \"NOT_DEFINED\", \"vectorString\": \"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N\", \"exploitMaturity\": \"NOT_DEFINED\", \"providerUrgency\": \"NOT_DEFINED\", \"userInteraction\": \"NONE\", \"attackComplexity\": \"LOW\", \"attackRequirements\": \"NONE\", \"privilegesRequired\": \"NONE\", \"subIntegrityImpact\": \"NONE\", \"vulnIntegrityImpact\": \"HIGH\", \"subAvailabilityImpact\": \"NONE\", \"vulnAvailabilityImpact\": \"HIGH\", \"subConfidentialityImpact\": \"NONE\", \"vulnConfidentialityImpact\": \"HIGH\", \"vulnerabilityResponseEffort\": \"NOT_DEFINED\"}, \"scenarios\": [{\"lang\": \"en\", \"value\": \"GENERAL\"}]}], \"affected\": [{\"vendor\": \"Tycon Systems\", \"product\": \"TPDIN-Monitor-WEB2\", \"versions\": [{\"status\": \"affected\", \"version\": \"0\", \"lessThan\": \"2.4.5\", \"versionType\": \"custom\"}, {\"status\": \"unaffected\", \"version\": \"2.4.5\"}], \"defaultStatus\": \"unaffected\"}], \"solutions\": [{\"lang\": \"en\", \"value\": \"Tycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to security@tyconsystems.com.\\n\\nTycon Systems recommends setting an administrative username and strong password on the Network Configuration page and confirming in a private browser window that a login is required, for units still running firmware 2.4.4 or earlier. Repeat this after any factory reset.\\n\\nTycon Systems recommends not exposing the web interface to the Internet, as it is HTTP only. The unit should be kept on a private network, behind a firewall or VPN.\", \"supportingMedia\": [{\"type\": \"text/html\", \"value\": \"\u003cp\u003eTycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to security@tyconsystems.com.\u003cbr\u003e\u003cbr\u003eTycon Systems recommends setting an administrative username and strong password on the Network Configuration page and confirming in a private browser window that a login is required, for units still running firmware 2.4.4 or earlier. Repeat this after any factory reset.\u003cbr\u003e\u003cbr\u003eTycon Systems recommends not exposing the web interface to the Internet, as it is HTTP only. The unit should be kept on a private network, behind a firewall or VPN.\u003c/p\u003e\", \"base64\": false}]}], \"references\": [{\"url\": \"https://www.cisa.gov/news-events/ics-advisories/icsa-26-202-01\"}, {\"url\": \"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-202-01.json\"}], \"x_generator\": {\"engine\": \"Vulnogram 1.0.4\"}, \"descriptions\": [{\"lang\": \"en\", \"value\": \"The Tycon Systems TPDIN-Monitor-WEB2\\nships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.\", \"supportingMedia\": [{\"type\": \"text/html\", \"value\": \"\u003cdiv\u003e\u003cspan\u003eThe \u003c/span\u003eTycon Systems TPDIN-Monitor-WEB2\\nships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.\\n\\n\u003c/div\u003e\", \"base64\": false}]}], \"problemTypes\": [{\"descriptions\": [{\"lang\": \"en\", \"type\": \"CWE\", \"cweId\": \"CWE-306\", \"description\": \"CWE-306\"}]}], \"providerMetadata\": {\"orgId\": \"7d14cffa-0d7d-4270-9dc0-52cabd5a23a6\", \"shortName\": \"icscert\", \"dateUpdated\": \"2026-09-04T21:28:52.355Z\"}}}",
      "cveMetadata": "{\"cveId\": \"CVE-2026-61884\", \"state\": \"PUBLISHED\", \"dateUpdated\": \"2026-09-04T21:28:52.355Z\", \"dateReserved\": \"2026-07-13T18:17:10.040Z\", \"assignerOrgId\": \"7d14cffa-0d7d-4270-9dc0-52cabd5a23a6\", \"datePublished\": \"2026-07-24T21:40:40.449Z\", \"assignerShortName\": \"icscert\"}",
      "dataType": "CVE_RECORD",
      "dataVersion": "5.2"
    }
  }
}



Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Forecast uses a logistic model when the trend is rising, or an exponential decay model when the trend is falling. Fitted via linearized least squares.

Sightings

Author Source Type Date Other

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.

Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…

Loading…