CVE-2025-0327 (GCVE-0-2025-0327)
Vulnerability from cvelistv5 – Published: 2025-02-13 06:20 – Updated: 2025-02-13 14:56- CWE-269 - Improper Privilege Management
| Vendor | Product | Version | |
|---|---|---|---|
| Schneider Electric | EcoStruxure Process Expert |
Affected:
Versions 2020R2
Affected: Versions 2021 & 2023 (prior to v4.8.0.5715) |
|
| Schneider Electric | EcoStruxure Process Expert for AVEVA System Platform |
Affected:
Versions 2020R2
Affected: Versions 2021 & 2023 |
{
"containers": {
"adp": [
{
"metrics": [
{
"other": {
"content": {
"id": "CVE-2025-0327",
"options": [
{
"Exploitation": "none"
},
{
"Automatable": "no"
},
{
"Technical Impact": "total"
}
],
"role": "CISA Coordinator",
"timestamp": "2025-02-13T14:55:58.362547Z",
"version": "2.0.3"
},
"type": "ssvc"
}
}
],
"providerMetadata": {
"dateUpdated": "2025-02-13T14:56:12.017Z",
"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"shortName": "CISA-ADP"
},
"title": "CISA ADP Vulnrichment"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "EcoStruxure Process Expert",
"vendor": "Schneider Electric",
"versions": [
{
"status": "affected",
"version": "Versions 2020R2"
},
{
"status": "affected",
"version": "Versions 2021 \u0026 2023 (prior to v4.8.0.5715)"
}
]
},
{
"defaultStatus": "unaffected",
"product": "EcoStruxure Process Expert for AVEVA System Platform",
"vendor": "Schneider Electric",
"versions": [
{
"status": "affected",
"version": "Versions 2020R2"
},
{
"status": "affected",
"version": "Versions 2021 \u0026 2023"
}
]
}
],
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality,\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\nexecutable path of the windows services. To be exploited, services need to be restarted.\n\n\n\u003cbr\u003e"
}
],
"value": "CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality,\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\nexecutable path of the windows services. To be exploited, services need to be restarted."
}
],
"metrics": [
{
"cvssV4_0": {
"Automatable": "NOT_DEFINED",
"Recovery": "NOT_DEFINED",
"Safety": "NOT_DEFINED",
"attackComplexity": "LOW",
"attackRequirements": "NONE",
"attackVector": "LOCAL",
"baseScore": 8.5,
"baseSeverity": "HIGH",
"privilegesRequired": "LOW",
"providerUrgency": "NOT_DEFINED",
"subAvailabilityImpact": "NONE",
"subConfidentialityImpact": "NONE",
"subIntegrityImpact": "NONE",
"userInteraction": "NONE",
"valueDensity": "NOT_DEFINED",
"vectorString": "CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N",
"version": "4.0",
"vulnAvailabilityImpact": "HIGH",
"vulnConfidentialityImpact": "HIGH",
"vulnIntegrityImpact": "HIGH",
"vulnerabilityResponseEffort": "NOT_DEFINED"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
},
{
"cvssV3_1": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-269",
"description": "CWE-269 Improper Privilege Management",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2025-02-13T06:20:26.852Z",
"orgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
"shortName": "schneider"
},
"references": [
{
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf"
}
],
"source": {
"discovery": "UNKNOWN"
},
"x_generator": {
"engine": "Vulnogram 0.2.0"
}
}
},
"cveMetadata": {
"assignerOrgId": "076d1eb6-cfab-4401-b34d-6dfc2a413bdb",
"assignerShortName": "schneider",
"cveId": "CVE-2025-0327",
"datePublished": "2025-02-13T06:20:26.852Z",
"dateReserved": "2025-01-08T13:34:15.419Z",
"dateUpdated": "2025-02-13T14:56:12.017Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.1",
"vulnerability-lookup:meta": {
"epss": {
"cve": "CVE-2025-0327",
"date": "2026-05-30",
"epss": "0.00153",
"percentile": "0.35718"
},
"nvd": "{\"cve\":{\"id\":\"CVE-2025-0327\",\"sourceIdentifier\":\"cybersecurity@se.com\",\"published\":\"2025-02-13T07:15:10.570\",\"lastModified\":\"2025-02-13T07:15:10.570\",\"vulnStatus\":\"Awaiting Analysis\",\"cveTags\":[],\"descriptions\":[{\"lang\":\"en\",\"value\":\"CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit\\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality,\\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\\nexecutable path of the windows services. To be exploited, services need to be restarted.\"},{\"lang\":\"es\",\"value\":\"CWE-269: Existe una vulnerabilidad de administraci\u00f3n inadecuada de privilegios para dos servicios (uno de los cuales administra los datos de registro de auditor\u00eda y el otro act\u00faa como servidor que administra las solicitudes de los clientes) que podr\u00eda provocar una p\u00e9rdida de confidencialidad, integridad y disponibilidad de la estaci\u00f3n de trabajo de ingenier\u00eda cuando un atacante con privilegios est\u00e1ndar modifica la ruta ejecutable de los servicios de Windows. Para explotarla, es necesario reiniciar los servicios.\"}],\"metrics\":{\"cvssMetricV40\":[{\"source\":\"cybersecurity@se.com\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"4.0\",\"vectorString\":\"CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X\",\"baseScore\":8.5,\"baseSeverity\":\"HIGH\",\"attackVector\":\"LOCAL\",\"attackComplexity\":\"LOW\",\"attackRequirements\":\"NONE\",\"privilegesRequired\":\"LOW\",\"userInteraction\":\"NONE\",\"vulnConfidentialityImpact\":\"HIGH\",\"vulnIntegrityImpact\":\"HIGH\",\"vulnAvailabilityImpact\":\"HIGH\",\"subConfidentialityImpact\":\"NONE\",\"subIntegrityImpact\":\"NONE\",\"subAvailabilityImpact\":\"NONE\",\"exploitMaturity\":\"NOT_DEFINED\",\"confidentialityRequirement\":\"NOT_DEFINED\",\"integrityRequirement\":\"NOT_DEFINED\",\"availabilityRequirement\":\"NOT_DEFINED\",\"modifiedAttackVector\":\"NOT_DEFINED\",\"modifiedAttackComplexity\":\"NOT_DEFINED\",\"modifiedAttackRequirements\":\"NOT_DEFINED\",\"modifiedPrivilegesRequired\":\"NOT_DEFINED\",\"modifiedUserInteraction\":\"NOT_DEFINED\",\"modifiedVulnConfidentialityImpact\":\"NOT_DEFINED\",\"modifiedVulnIntegrityImpact\":\"NOT_DEFINED\",\"modifiedVulnAvailabilityImpact\":\"NOT_DEFINED\",\"modifiedSubConfidentialityImpact\":\"NOT_DEFINED\",\"modifiedSubIntegrityImpact\":\"NOT_DEFINED\",\"modifiedSubAvailabilityImpact\":\"NOT_DEFINED\",\"Safety\":\"NOT_DEFINED\",\"Automatable\":\"NOT_DEFINED\",\"Recovery\":\"NOT_DEFINED\",\"valueDensity\":\"NOT_DEFINED\",\"vulnerabilityResponseEffort\":\"NOT_DEFINED\",\"providerUrgency\":\"NOT_DEFINED\"}}],\"cvssMetricV31\":[{\"source\":\"cybersecurity@se.com\",\"type\":\"Secondary\",\"cvssData\":{\"version\":\"3.1\",\"vectorString\":\"CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H\",\"baseScore\":7.8,\"baseSeverity\":\"HIGH\",\"attackVector\":\"LOCAL\",\"attackComplexity\":\"LOW\",\"privilegesRequired\":\"LOW\",\"userInteraction\":\"NONE\",\"scope\":\"UNCHANGED\",\"confidentialityImpact\":\"HIGH\",\"integrityImpact\":\"HIGH\",\"availabilityImpact\":\"HIGH\"},\"exploitabilityScore\":1.8,\"impactScore\":5.9}]},\"weaknesses\":[{\"source\":\"cybersecurity@se.com\",\"type\":\"Primary\",\"description\":[{\"lang\":\"en\",\"value\":\"CWE-269\"}]}],\"references\":[{\"url\":\"https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf\",\"source\":\"cybersecurity@se.com\"}]}}",
"vulnrichment": {
"containers": "{\"cna\": {\"affected\": [{\"defaultStatus\": \"unaffected\", \"product\": \"EcoStruxure Process Expert\", \"vendor\": \"Schneider Electric\", \"versions\": [{\"status\": \"affected\", \"version\": \"Versions 2020R2\"}, {\"status\": \"affected\", \"version\": \"Versions 2021 \u0026 2023 (prior to v4.8.0.5715)\"}]}, {\"defaultStatus\": \"unaffected\", \"product\": \"EcoStruxure Process Expert for AVEVA System Platform\", \"vendor\": \"Schneider Electric\", \"versions\": [{\"status\": \"affected\", \"version\": \"Versions 2020R2\"}, {\"status\": \"affected\", \"version\": \"Versions 2021 \u0026 2023\"}]}], \"descriptions\": [{\"lang\": \"en\", \"supportingMedia\": [{\"base64\": false, \"type\": \"text/html\", \"value\": \"CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit\\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality,\\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\\nexecutable path of the windows services. To be exploited, services need to be restarted.\\n\\n\\n\u003cbr\u003e\"}], \"value\": \"CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit\\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality,\\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\\nexecutable path of the windows services. To be exploited, services need to be restarted.\"}], \"metrics\": [{\"cvssV4_0\": {\"Automatable\": \"NOT_DEFINED\", \"Recovery\": \"NOT_DEFINED\", \"Safety\": \"NOT_DEFINED\", \"attackComplexity\": \"LOW\", \"attackRequirements\": \"NONE\", \"attackVector\": \"LOCAL\", \"baseScore\": 8.5, \"baseSeverity\": \"HIGH\", \"privilegesRequired\": \"LOW\", \"providerUrgency\": \"NOT_DEFINED\", \"subAvailabilityImpact\": \"NONE\", \"subConfidentialityImpact\": \"NONE\", \"subIntegrityImpact\": \"NONE\", \"userInteraction\": \"NONE\", \"valueDensity\": \"NOT_DEFINED\", \"vectorString\": \"CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N\", \"version\": \"4.0\", \"vulnAvailabilityImpact\": \"HIGH\", \"vulnConfidentialityImpact\": \"HIGH\", \"vulnIntegrityImpact\": \"HIGH\", \"vulnerabilityResponseEffort\": \"NOT_DEFINED\"}, \"format\": \"CVSS\", \"scenarios\": [{\"lang\": \"en\", \"value\": \"GENERAL\"}]}, {\"cvssV3_1\": {\"attackComplexity\": \"LOW\", \"attackVector\": \"LOCAL\", \"availabilityImpact\": \"HIGH\", \"baseScore\": 7.8, \"baseSeverity\": \"HIGH\", \"confidentialityImpact\": \"HIGH\", \"integrityImpact\": \"HIGH\", \"privilegesRequired\": \"LOW\", \"scope\": \"UNCHANGED\", \"userInteraction\": \"NONE\", \"vectorString\": \"CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H\", \"version\": \"3.1\"}, \"format\": \"CVSS\", \"scenarios\": [{\"lang\": \"en\", \"value\": \"GENERAL\"}]}], \"problemTypes\": [{\"descriptions\": [{\"cweId\": \"CWE-269\", \"description\": \"CWE-269 Improper Privilege Management\", \"lang\": \"en\", \"type\": \"CWE\"}]}], \"providerMetadata\": {\"orgId\": \"076d1eb6-cfab-4401-b34d-6dfc2a413bdb\", \"shortName\": \"schneider\", \"dateUpdated\": \"2025-02-13T06:20:26.852Z\"}, \"references\": [{\"url\": \"https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf\"}], \"source\": {\"discovery\": \"UNKNOWN\"}, \"x_generator\": {\"engine\": \"Vulnogram 0.2.0\"}}, \"adp\": [{\"title\": \"CISA ADP Vulnrichment\", \"metrics\": [{\"other\": {\"type\": \"ssvc\", \"content\": {\"id\": \"CVE-2025-0327\", \"role\": \"CISA Coordinator\", \"options\": [{\"Exploitation\": \"none\"}, {\"Automatable\": \"no\"}, {\"Technical Impact\": \"total\"}], \"version\": \"2.0.3\", \"timestamp\": \"2025-02-13T14:55:58.362547Z\"}}}], \"providerMetadata\": {\"orgId\": \"134c704f-9b21-4f2e-91b3-4a467353bcc0\", \"shortName\": \"CISA-ADP\", \"dateUpdated\": \"2025-02-13T14:56:07.309Z\"}}]}",
"cveMetadata": "{\"cveId\": \"CVE-2025-0327\", \"assignerOrgId\": \"076d1eb6-cfab-4401-b34d-6dfc2a413bdb\", \"state\": \"PUBLISHED\", \"assignerShortName\": \"schneider\", \"dateReserved\": \"2025-01-08T13:34:15.419Z\", \"datePublished\": \"2025-02-13T06:20:26.852Z\", \"dateUpdated\": \"2025-02-13T14:56:12.017Z\"}",
"dataType": "CVE_RECORD",
"dataVersion": "5.1"
}
}
}
CERTFR-2025-AVI-0112
Vulnerability from certfr_avis - Published: - Updated:
Une vulnérabilité a été découverte dans les produits Schneider Electric. Elle permet à un attaquant de provoquer une élévation de privilèges.
Solutions
Se référer au bulletin de sécurité de l'éditeur pour l'obtention des correctifs (cf. section Documentation).
| Vendor | Product | Description | ||
|---|---|---|---|---|
| Schneider Electric | N/A | EcoStruxure Process Expert 2023 versions antérieures à 4.8.0.5715 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System versions antérieures à 2023 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System versions antérieures à 2020 R2 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert versions antérieures à 2020 R2 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System versions antérieures à 2021 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert versions antérieures à 2021 pour la vulnérabilité CVE-2025-0327 |
| Title | Publication Time | Tags | |||
|---|---|---|---|---|---|
|
|||||
{
"$ref": "https://www.cert.ssi.gouv.fr/openapi.json",
"affected_systems": [
{
"description": "EcoStruxure Process Expert 2023 versions ant\u00e9rieures \u00e0 4.8.0.5715",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System versions ant\u00e9rieures \u00e0 2023 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System versions ant\u00e9rieures \u00e0 2020 R2 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert versions ant\u00e9rieures \u00e0 2020 R2 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System versions ant\u00e9rieures \u00e0 2021 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert versions ant\u00e9rieures \u00e0 2021 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
}
],
"affected_systems_content": "",
"content": "## Solutions\n\nSe r\u00e9f\u00e9rer au bulletin de s\u00e9curit\u00e9 de l\u0027\u00e9diteur pour l\u0027obtention des correctifs (cf. section Documentation).",
"cves": [
{
"name": "CVE-2025-0327",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-0327"
}
],
"links": [],
"reference": "CERTFR-2025-AVI-0112",
"revisions": [
{
"description": "Version initiale",
"revision_date": "2025-02-11T00:00:00.000000"
}
],
"risks": [
{
"description": "\u00c9l\u00e9vation de privil\u00e8ges"
}
],
"summary": "Une vuln\u00e9rabilit\u00e9 a \u00e9t\u00e9 d\u00e9couverte dans les produits Schneider Electric. Elle permet \u00e0 un attaquant de provoquer une \u00e9l\u00e9vation de privil\u00e8ges.",
"title": "Vuln\u00e9rabilit\u00e9 dans les produits Schneider Electric",
"vendor_advisories": [
{
"published_at": "2025-02-10",
"title": "Bulletin de s\u00e9curit\u00e9 Schneider Electric SEVD-2025-042-03",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf"
}
]
}
CERTFR-2025-AVI-0112
Vulnerability from certfr_avis - Published: - Updated:
Une vulnérabilité a été découverte dans les produits Schneider Electric. Elle permet à un attaquant de provoquer une élévation de privilèges.
Solutions
Se référer au bulletin de sécurité de l'éditeur pour l'obtention des correctifs (cf. section Documentation).
| Vendor | Product | Description | ||
|---|---|---|---|---|
| Schneider Electric | N/A | EcoStruxure Process Expert 2023 versions antérieures à 4.8.0.5715 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System versions antérieures à 2023 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System versions antérieures à 2020 R2 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert versions antérieures à 2020 R2 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System versions antérieures à 2021 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert versions antérieures à 2021 pour la vulnérabilité CVE-2025-0327 |
| Title | Publication Time | Tags | |||
|---|---|---|---|---|---|
|
|||||
{
"$ref": "https://www.cert.ssi.gouv.fr/openapi.json",
"affected_systems": [
{
"description": "EcoStruxure Process Expert 2023 versions ant\u00e9rieures \u00e0 4.8.0.5715",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System versions ant\u00e9rieures \u00e0 2023 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System versions ant\u00e9rieures \u00e0 2020 R2 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert versions ant\u00e9rieures \u00e0 2020 R2 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System versions ant\u00e9rieures \u00e0 2021 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert versions ant\u00e9rieures \u00e0 2021 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
}
],
"affected_systems_content": "",
"content": "## Solutions\n\nSe r\u00e9f\u00e9rer au bulletin de s\u00e9curit\u00e9 de l\u0027\u00e9diteur pour l\u0027obtention des correctifs (cf. section Documentation).",
"cves": [
{
"name": "CVE-2025-0327",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-0327"
}
],
"links": [],
"reference": "CERTFR-2025-AVI-0112",
"revisions": [
{
"description": "Version initiale",
"revision_date": "2025-02-11T00:00:00.000000"
}
],
"risks": [
{
"description": "\u00c9l\u00e9vation de privil\u00e8ges"
}
],
"summary": "Une vuln\u00e9rabilit\u00e9 a \u00e9t\u00e9 d\u00e9couverte dans les produits Schneider Electric. Elle permet \u00e0 un attaquant de provoquer une \u00e9l\u00e9vation de privil\u00e8ges.",
"title": "Vuln\u00e9rabilit\u00e9 dans les produits Schneider Electric",
"vendor_advisories": [
{
"published_at": "2025-02-10",
"title": "Bulletin de s\u00e9curit\u00e9 Schneider Electric SEVD-2025-042-03",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf"
}
]
}
CERTFR-2026-AVI-0566
Vulnerability from certfr_avis - Published: 2026-05-12 - Updated: 2026-05-12
De multiples vulnérabilités ont été découvertes dans les produits Schneider Electric. Certaines d'entre elles permettent à un attaquant de provoquer une élévation de privilèges, une atteinte à la confidentialité des données et une atteinte à l'intégrité des données.
Solutions
Se référer au bulletin de sécurité de l'éditeur pour l'obtention des correctifs (cf. section Documentation).
None| Vendor | Product | Description | ||
|---|---|---|---|---|
| Schneider Electric | N/A | EcoStruxure Power Automation System Gateway (EPAS-GTW) versions antérieures ou égales à 6.4.616.200.100 | ||
| Schneider Electric | N/A | Easergy MiCOM P532 vers:generic/ versions antérieures ou égales à P532.678.700 pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert 2023 versions antérieures à 4.8.0.5715 | ||
| Schneider Electric | N/A | Easergy MiCOM P634 versions antérieures à P634.680.700 | ||
| Schneider Electric | N/A | EcoStruxure Panel Server PAS800V2 versions antérieures ou égales à 002.005.000 | ||
| Schneider Electric | N/A | Easergy MiCOM P138 vers:generic/ versions antérieures ou égales à P138.677.700 | ||
| Schneider Electric | N/A | Easergy MiCOM P40 Series toutes versions pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | Easergy MiCOM P631 vers:generic/ versions antérieures ou égales à P631.678.700 pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | Easergy MiCOM P638 vers:generic/ versions antérieures ou égales à P638.677.700 pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System Platform versions antérieures à 2023 | ||
| Schneider Electric | N/A | Easergy MiCOM P632 vers:generic/ versions antérieures ou égales à P632.678.700 | ||
| Schneider Electric | N/A | EcoStruxure Power Automation System User Interface (EPAS-UI) versions antérieures ou égales à 3.0.3 pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | Easergy MiCOM P539 vers:generic/ versions antérieures ou égales à P539.678.700 | ||
| Schneider Electric | N/A | Easergy MiCOM P634 vers:generic/ versions antérieures ou égales à P634.678.700 | ||
| Schneider Electric | N/A | Easergy MiCOM P436 vers:generic/ versions antérieures ou égales à P436.677.701 pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | Easergy MiCOM C264 vers:generic/ versions antérieures ou égales à D7.33 | ||
| Schneider Electric | N/A | Easergy MiCOM P439 vers:generic/ versions antérieures ou égales à P439.678.700 | ||
| Schneider Electric | N/A | EcoStruxure Panel Server PAS600 versions antérieures ou égales à 002.005.000 | ||
| Schneider Electric | N/A | Easergy C5 versions antérieures ou égales à 1.1.17 | ||
| Schneider Electric | N/A | Easergy MiCOM P139 vers:generic/ versions antérieures ou égales à P139.678.700 pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | Easergy MiCOM P437 vers:generic/ versions antérieures ou égales à P437.678.700 pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | Easergy MiCOM P438 vers:generic/ versions antérieures ou égales à P438.677.701 pour la vulnérabilité CVE-2026-4827 | ||
| Schneider Electric | N/A | EcoStruxure Panel Server PAS400 versions antérieures ou égales à 002.005.000 | ||
| Schneider Electric | N/A | EcoStruxure Panel Server PAS600V2 versions antérieures ou égales à 002.005.000 | ||
| Schneider Electric | N/A | Easergy MiCOM C434 vers:generic/ versions antérieures ou égales à C434.679.700 | ||
| Schneider Electric | N/A | Ecostruxure Machine Expert HVAC versions antérieures à 1.10.0 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert versions antérieures à 2020 R2 pour la vulnérabilité CVE-2025-0327 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System Platform versions antérieures à 2021 | ||
| Schneider Electric | N/A | Easergy MiCOM P633 versions antérieures à P633.680.700 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert for AVEVA System Platform versions antérieures à 2020 R2 | ||
| Schneider Electric | N/A | EcoStruxure Power Operation vers:generic/ versions antérieures ou égales à 2024 CU2 | ||
| Schneider Electric | N/A | EcoStruxure Power Operation vers:generic/ versions antérieures ou égales à 2022 CU6 | ||
| Schneider Electric | N/A | Easergy MiCOM P633 vers:generic/ versions antérieures ou égales à P633.678.700 | ||
| Schneider Electric | N/A | EcoStruxure Panel Server PAS800 versions antérieures ou égales à 002.005.000 | ||
| Schneider Electric | N/A | EcoStruxure Process Expert versions antérieures à 2021 pour la vulnérabilité CVE-2025-0327 |
| Title | Publication Time | Tags | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
||||||||||||||
{
"$ref": "https://www.cert.ssi.gouv.fr/openapi.json",
"affected_systems": [
{
"description": "EcoStruxure Power Automation System Gateway (EPAS-GTW) versions ant\u00e9rieures ou \u00e9gales \u00e0 6.4.616.200.100",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P532 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P532.678.700 pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert 2023 versions ant\u00e9rieures \u00e0 4.8.0.5715",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P634 versions ant\u00e9rieures \u00e0 P634.680.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Panel Server PAS800V2 versions ant\u00e9rieures ou \u00e9gales \u00e0 002.005.000",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P138 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P138.677.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P40 Series toutes versions pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P631 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P631.678.700 pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P638 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P638.677.700 pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System Platform versions ant\u00e9rieures \u00e0 2023",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P632 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P632.678.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Power Automation System User Interface (EPAS-UI) versions ant\u00e9rieures ou \u00e9gales \u00e0 3.0.3 pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P539 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P539.678.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P634 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P634.678.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P436 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P436.677.701 pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM C264 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 D7.33",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P439 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P439.678.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Panel Server PAS600 versions ant\u00e9rieures ou \u00e9gales \u00e0 002.005.000",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy C5 versions ant\u00e9rieures ou \u00e9gales \u00e0 1.1.17",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P139 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P139.678.700 pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P437 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P437.678.700 pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P438 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P438.677.701 pour la vuln\u00e9rabilit\u00e9 CVE-2026-4827",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Panel Server PAS400 versions ant\u00e9rieures ou \u00e9gales \u00e0 002.005.000",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Panel Server PAS600V2 versions ant\u00e9rieures ou \u00e9gales \u00e0 002.005.000",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM C434 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 C434.679.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Ecostruxure Machine Expert HVAC versions ant\u00e9rieures \u00e0 1.10.0",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert versions ant\u00e9rieures \u00e0 2020 R2 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System Platform versions ant\u00e9rieures \u00e0 2021",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P633 versions ant\u00e9rieures \u00e0 P633.680.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert for AVEVA System Platform versions ant\u00e9rieures \u00e0 2020 R2",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Power Operation vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 2024 CU2",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Power Operation vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 2022 CU6",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "Easergy MiCOM P633 vers:generic/ versions ant\u00e9rieures ou \u00e9gales \u00e0 P633.678.700",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Panel Server PAS800 versions ant\u00e9rieures ou \u00e9gales \u00e0 002.005.000",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
},
{
"description": "EcoStruxure Process Expert versions ant\u00e9rieures \u00e0 2021 pour la vuln\u00e9rabilit\u00e9 CVE-2025-0327",
"product": {
"name": "N/A",
"vendor": {
"name": "Schneider Electric",
"scada": true
}
}
}
],
"affected_systems_content": null,
"content": "## Solutions\n\nSe r\u00e9f\u00e9rer au bulletin de s\u00e9curit\u00e9 de l\u0027\u00e9diteur pour l\u0027obtention des correctifs (cf. section Documentation).",
"cves": [
{
"name": "CVE-2026-6866",
"url": "https://www.cve.org/CVERecord?id=CVE-2026-6866"
},
{
"name": "CVE-2025-0327",
"url": "https://www.cve.org/CVERecord?id=CVE-2025-0327"
},
{
"name": "CVE-2026-4827",
"url": "https://www.cve.org/CVERecord?id=CVE-2026-4827"
},
{
"name": "CVE-2026-6332",
"url": "https://www.cve.org/CVERecord?id=CVE-2026-6332"
}
],
"initial_release_date": "2026-05-12T00:00:00",
"last_revision_date": "2026-05-12T00:00:00",
"links": [],
"reference": "CERTFR-2026-AVI-0566",
"revisions": [
{
"description": "Version initiale",
"revision_date": "2026-05-12T00:00:00.000000"
}
],
"risks": [
{
"description": "Atteinte \u00e0 l\u0027int\u00e9grit\u00e9 des donn\u00e9es"
},
{
"description": "Contournement de la politique de s\u00e9curit\u00e9"
},
{
"description": "Atteinte \u00e0 la confidentialit\u00e9 des donn\u00e9es"
},
{
"description": "\u00c9l\u00e9vation de privil\u00e8ges"
}
],
"summary": "De multiples vuln\u00e9rabilit\u00e9s ont \u00e9t\u00e9 d\u00e9couvertes dans les produits Schneider Electric. Certaines d\u0027entre elles permettent \u00e0 un attaquant de provoquer une \u00e9l\u00e9vation de privil\u00e8ges, une atteinte \u00e0 la confidentialit\u00e9 des donn\u00e9es et une atteinte \u00e0 l\u0027int\u00e9grit\u00e9 des donn\u00e9es.",
"title": "Multiples vuln\u00e9rabilit\u00e9s dans les produits Schneider Electric",
"vendor_advisories": [
{
"published_at": "2026-05-12",
"title": "Bulletin de s\u00e9curit\u00e9 Schneider Electric SEVD-2026-132-02",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2026-132-02\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2026-132-02.pdf"
},
{
"published_at": "2026-05-12",
"title": "Bulletin de s\u00e9curit\u00e9 Schneider Electric SEVD-2026-132-04",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2026-132-04\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2026-132-04.pdf"
},
{
"published_at": "2026-05-12",
"title": "Bulletin de s\u00e9curit\u00e9 Schneider Electric SEVD-2025-042-03",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf"
},
{
"published_at": "2026-05-12",
"title": "Bulletin de s\u00e9curit\u00e9 Schneider Electric SEVD-2026-132-01",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2026-132-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2026-132-01.pdf"
}
]
}
FKIE_CVE-2025-0327
Vulnerability from fkie_nvd - Published: 2025-02-13 07:15 - Updated: 2026-04-15 00:35| Vendor | Product | Version |
|---|
{
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality,\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\nexecutable path of the windows services. To be exploited, services need to be restarted."
},
{
"lang": "es",
"value": "CWE-269: Existe una vulnerabilidad de administraci\u00f3n inadecuada de privilegios para dos servicios (uno de los cuales administra los datos de registro de auditor\u00eda y el otro act\u00faa como servidor que administra las solicitudes de los clientes) que podr\u00eda provocar una p\u00e9rdida de confidencialidad, integridad y disponibilidad de la estaci\u00f3n de trabajo de ingenier\u00eda cuando un atacante con privilegios est\u00e1ndar modifica la ruta ejecutable de los servicios de Windows. Para explotarla, es necesario reiniciar los servicios."
}
],
"id": "CVE-2025-0327",
"lastModified": "2026-04-15T00:35:42.020",
"metrics": {
"cvssMetricV31": [
{
"cvssData": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"exploitabilityScore": 1.8,
"impactScore": 5.9,
"source": "cybersecurity@se.com",
"type": "Secondary"
}
],
"cvssMetricV40": [
{
"cvssData": {
"Automatable": "NOT_DEFINED",
"Recovery": "NOT_DEFINED",
"Safety": "NOT_DEFINED",
"attackComplexity": "LOW",
"attackRequirements": "NONE",
"attackVector": "LOCAL",
"availabilityRequirement": "NOT_DEFINED",
"baseScore": 8.5,
"baseSeverity": "HIGH",
"confidentialityRequirement": "NOT_DEFINED",
"exploitMaturity": "NOT_DEFINED",
"integrityRequirement": "NOT_DEFINED",
"modifiedAttackComplexity": "NOT_DEFINED",
"modifiedAttackRequirements": "NOT_DEFINED",
"modifiedAttackVector": "NOT_DEFINED",
"modifiedPrivilegesRequired": "NOT_DEFINED",
"modifiedSubAvailabilityImpact": "NOT_DEFINED",
"modifiedSubConfidentialityImpact": "NOT_DEFINED",
"modifiedSubIntegrityImpact": "NOT_DEFINED",
"modifiedUserInteraction": "NOT_DEFINED",
"modifiedVulnAvailabilityImpact": "NOT_DEFINED",
"modifiedVulnConfidentialityImpact": "NOT_DEFINED",
"modifiedVulnIntegrityImpact": "NOT_DEFINED",
"privilegesRequired": "LOW",
"providerUrgency": "NOT_DEFINED",
"subAvailabilityImpact": "NONE",
"subConfidentialityImpact": "NONE",
"subIntegrityImpact": "NONE",
"userInteraction": "NONE",
"valueDensity": "NOT_DEFINED",
"vectorString": "CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X",
"version": "4.0",
"vulnAvailabilityImpact": "HIGH",
"vulnConfidentialityImpact": "HIGH",
"vulnIntegrityImpact": "HIGH",
"vulnerabilityResponseEffort": "NOT_DEFINED"
},
"source": "cybersecurity@se.com",
"type": "Secondary"
}
]
},
"published": "2025-02-13T07:15:10.570",
"references": [
{
"source": "cybersecurity@se.com",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf"
}
],
"sourceIdentifier": "cybersecurity@se.com",
"vulnStatus": "Deferred",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-269"
}
],
"source": "cybersecurity@se.com",
"type": "Secondary"
}
]
}
GHSA-4V4V-FCFX-X6MG
Vulnerability from github – Published: 2025-02-13 09:31 – Updated: 2025-02-13 09:31CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit trail data and the other acting as server managing client request) that could cause a loss of Confidentiality, Integrity and Availability of engineering workstation when an attacker with standard privilege modifies the executable path of the windows services. To be exploited, services need to be restarted.
{
"affected": [],
"aliases": [
"CVE-2025-0327"
],
"database_specific": {
"cwe_ids": [
"CWE-269"
],
"github_reviewed": false,
"github_reviewed_at": null,
"nvd_published_at": "2025-02-13T07:15:10Z",
"severity": "HIGH"
},
"details": "CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality,\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\nexecutable path of the windows services. To be exploited, services need to be restarted.",
"id": "GHSA-4v4v-fcfx-x6mg",
"modified": "2025-02-13T09:31:26Z",
"published": "2025-02-13T09:31:26Z",
"references": [
{
"type": "ADVISORY",
"url": "https://nvd.nist.gov/vuln/detail/CVE-2025-0327"
},
{
"type": "WEB",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf"
}
],
"schema_version": "1.4.0",
"severity": [
{
"score": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"type": "CVSS_V3"
},
{
"score": "CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X",
"type": "CVSS_V4"
}
]
}
ICSA-25-079-01
Vulnerability from csaf_cisa - Published: 2025-02-11 06:00 - Updated: 2025-02-11 06:00CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit trail data and the other acting as server managing client request) that could cause a loss of Confidentiality, Integrity and Availability of engineering workstation when an attacker with standard privilege modifies the executable path of the windows services. To be exploited, services need to be restarted.
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
Schneider Electric EcoStruxure™ Process Expert 2023 v4.8.0.5715
Schneider Electric / EcoStruxure™ Process Expert 2023
|
4.8.0.5715 |
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
Schneider Electric EcoStruxure™ Process Expert version 2020 R2
Schneider Electric / EcoStruxure™ Process Expert
|
2020_R2 |
Vendor Fix
fix
Mitigation
fix
|
|
|
Schneider Electric EcoStruxure™ Process Expert version 2021
Schneider Electric / EcoStruxure™ Process Expert
|
2021 |
Vendor Fix
fix
Mitigation
fix
|
|
|
Schneider Electric EcoStruxure™ Process Expert 2023 versions prior to v4.8.0.5715
Schneider Electric / EcoStruxure™ Process Expert 2023
|
<4.8.0.5715 |
Vendor Fix
fix
Mitigation
fix
|
|
|
Schneider Electric EcoStruxure™ Process Expert for AVEVA System version 2020 R2
Schneider Electric / EcoStruxure™ Process Expert for AVEVA System
|
2020_R2 |
Mitigation
fix
|
|
|
Schneider Electric EcoStruxure™ Process Expert for AVEVA System version 2021
Schneider Electric / EcoStruxure™ Process Expert for AVEVA System
|
2021 |
Mitigation
fix
|
|
|
Schneider Electric EcoStruxure™ Process Expert for AVEVA System version 2023
Schneider Electric / EcoStruxure™ Process Expert for AVEVA System
|
2023 |
Mitigation
fix
|
{
"document": {
"acknowledgments": [
{
"names": [
"Charit Misra"
],
"organization": "DNV Cyber",
"summary": "reporting this vulnerability to Schneider Electric."
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited",
"tlp": {
"label": "WHITE",
"url": "https://us-cert.cisa.gov/tlp/"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\n\n Customers should use appropriate patching methodologies when applying these patches to their systems. We\r\nstrongly recommend the use of back-ups and evaluating the impact of these patches in a Test and\r\nDevelopment environment or on an offline infrastructure. Contact Schneider Electric\u2019s Customer Care Center if\r\nyou need assistance removing a patch.\n\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "Schneider\u2019s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of a vulnerability in its EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process \r\nExpert for AVEVA System Platform products. \r\nThe EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process Expert for AVEVA System Platform products are \r\nengineering tools that facilitates and automates the design, maintenance, commissioning, and operation of \r\nControl projects for Modicon controllers and the associated Supervision projects for SCADA software \r\nregrouped in a system.. \r\nFailure to apply the Fix/Mitigations provided below may risk a local privilege escalation, which could result in \r\nloss of confidentiality, integrity and availability of the engineering workstation.",
"title": "Overview"
},
{
"category": "legal_disclaimer",
"text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
"title": "Legal Notice"
},
{
"category": "other",
"text": "This CISA CSAF advisory was converted from Schneider Electric CPCERT\u0027s CSAF advisory.",
"title": "Advisory Conversion Disclaimer"
},
{
"category": "other",
"text": "Commercial Facilities, Critical Manufacturing, Energy, Water and Wastewater Systems",
"title": "Critical infrastructure sectors"
},
{
"category": "other",
"text": "Worldwide",
"title": "Countries/areas deployed"
},
{
"category": "other",
"text": "France",
"title": "Company headquarters location"
},
{
"category": "general",
"text": "CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
"title": "Recommended Practices"
}
],
"publisher": {
"category": "other",
"contact_details": "central@cisa.dhs.gov",
"name": "CISA",
"namespace": "https://www.cisa.gov/"
},
"references": [
{
"category": "self",
"summary": "EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process Expert for AVEVA - SEVD-2025-042-03 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-042-03.json"
},
{
"category": "self",
"summary": "EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process Expert for AVEVA - SEVD-2025-042-03 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-042-03.pdf"
},
{
"category": "external",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-25-079-01 JSON",
"url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2025/icsa-25-079-01.json"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-25-079-01 - Web Version",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-079-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/ics/alerts/ICS-ALERT-10-301-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/topics/industrial-control-systems"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://us-cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/uscert/ics/tips/ICS-TIP-12-146-01B"
}
],
"title": "Schneider Electric EcoStruxure\u00e2\u201e\u00a2",
"tracking": {
"current_release_date": "2025-02-11T06:00:00.000000Z",
"generator": {
"date": "2025-02-05T06:00:00.000000Z",
"engine": {
"name": "CISA CSAF Generator",
"version": "1.0.0"
}
},
"id": "ICSA-25-079-01",
"initial_release_date": "2025-02-11T06:00:00.000000Z",
"revision_history": [
{
"date": "2025-02-11T06:00:00.000000Z",
"number": "1.0.0",
"summary": "Original Release"
}
],
"status": "final",
"version": "1.0.0"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version",
"name": "2020_R2",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Process Expert version 2020 R2",
"product_id": "CSAFPID-0001"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Process Expert"
},
{
"branches": [
{
"category": "product_version",
"name": "2021",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Process Expert version 2021",
"product_id": "CSAFPID-0002"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Process Expert"
},
{
"branches": [
{
"category": "product_version_range",
"name": "\u003c4.8.0.5715",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Process Expert 2023 versions prior to v4.8.0.5715",
"product_id": "CSAFPID-0003"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Process Expert 2023"
},
{
"branches": [
{
"category": "product_version",
"name": "2020_R2",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Process Expert for AVEVA System version 2020 R2",
"product_id": "CSAFPID-0004"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Process Expert for AVEVA System "
},
{
"branches": [
{
"category": "product_version",
"name": "2021",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Process Expert for AVEVA System version 2021",
"product_id": "CSAFPID-0005"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Process Expert for AVEVA System "
},
{
"branches": [
{
"category": "product_version",
"name": "2023",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Process Expert for AVEVA System version 2023",
"product_id": "CSAFPID-0006"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Process Expert for AVEVA System "
},
{
"branches": [
{
"category": "product_version",
"name": "4.8.0.5715",
"product": {
"name": "Schneider Electric EcoStruxure\u2122 Process Expert 2023 v4.8.0.5715",
"product_id": "CSAFPID-0007"
}
}
],
"category": "product_name",
"name": "EcoStruxure\u2122 Process Expert 2023"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"acknowledgments": [
{
"names": [
"Charit Misra"
],
"organization": "Applied Risk (DNV Cyber)"
}
],
"cve": "CVE-2025-0327",
"cwe": {
"id": "CWE-269",
"name": "Improper Privilege Management"
},
"notes": [
{
"category": "description",
"text": "CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit \r\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality, \r\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\r\nexecutable path of the windows services. To be exploited, services need to be restarted.",
"title": "CVE Description"
}
],
"product_status": {
"fixed": [
"CSAFPID-0007"
],
"known_affected": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version v4.8.0.5715 of EcoStruxure\u2122 Process Expert 2023 Software \r\nPackage includes a fix for this vulnerability and is available for download \r\nhere:\r\nhttps://www.se.com/au/en/product-range/65406-ecostruxure-process\u0002expert/#software-and-firmware\r\nUninstall Previous Version 2023 (v4.8.0.5115) before installing Version \r\n2023 (v4.8.0.5715).\r\nVersion string could be found on engineering server console.",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/au/en/product-range/65406-ecostruxure-process-expert/#software-and-firmware"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\n\n\u2022 Allow execute permission for service control Windows utility only to \r\nadmin user.\r\n\u2022 McAfee Application and Change Control software for application control\r\nto allow execution of whitelisted applications only. Refer to the \r\nCybersecurity Application Note available\r\nhttps://www.se.com/ww/en/download/document/EIO0000004778/",
"product_ids": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
},
{
"category": "mitigation",
"details": "Schneider Electric is establishing a remediation plan for all future versions of \r\nEcoStruxure\u2122 Process Expert for AVEVA System Platform that will include a fix \r\nfor this vulnerability. We will update this document when the remediation is \r\navailable. Until then, customers should immediately apply the following \r\nmitigations to reduce the risk of exploit:\n\n\u2022 Allow only admin user to configure windows service by restricting \r\nexecute permission of sc.exe windows utility. \n\n\u2022 McAfee Application and Change Control software for application control \r\nto allow execution of whitelisted applications only. Refer to the \r\nCybersecurity Application Note available\r\nhttps://www.se.com/ww/en/download/document/EIO0000004778/",
"product_ids": [
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"CSAFPID-0001",
"CSAFPID-0002",
"CSAFPID-0003",
"CSAFPID-0004",
"CSAFPID-0005",
"CSAFPID-0006"
]
}
],
"title": "CVE-2025-0327"
}
]
}
SEVD-2025-042-03
Vulnerability from csaf_se - Published: 2025-02-11 06:00 - Updated: 2026-05-12 07:00CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit trail data and the other acting as server managing client request) that could cause a loss of Confidentiality, Integrity and Availability of engineering workstation when an attacker with standard privilege modifies the executable path of the windows services. To be exploited, services need to be restarted.
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
EcoStruxure Process Expert 2023 v4.8.0.5715
Schneider Electric / EcoStruxure Process Expert 2023
|
4.8.0.5715 | ||
|
EcoStruxure Process Expert for AVEVA System Platform version 2025
Schneider Electric / EcoStruxure Process Expert for AVEVA System Platform
|
2025 |
| Product | Identifier | Version | Remediation |
|---|---|---|---|
|
EcoStruxure Process Expert version 2020 R2
Schneider Electric / EcoStruxure Process Expert
|
2020 R2 |
Vendor Fix
fix
Mitigation
fix
|
|
|
EcoStruxure Process Expert version 2021
Schneider Electric / EcoStruxure Process Expert
|
2021 |
Vendor Fix
fix
Mitigation
fix
|
|
|
EcoStruxure Process Expert 2023 versions prior to v4.8.0.5715
Schneider Electric / EcoStruxure Process Expert 2023
|
vers:intdot/<4.8.0.5715 |
Vendor Fix
fix
Mitigation
fix
|
|
|
EcoStruxure Process Expert for AVEVA System Platform version 2020 R2
Schneider Electric / EcoStruxure Process Expert for AVEVA System Platform
|
2020 R2 |
Vendor Fix
fix
Mitigation
fix
|
|
|
EcoStruxure Process Expert for AVEVA System Platform version 2021
Schneider Electric / EcoStruxure Process Expert for AVEVA System Platform
|
2021 |
Vendor Fix
fix
Mitigation
fix
|
|
|
EcoStruxure Process Expert for AVEVA System Platform 2023
Schneider Electric / EcoStruxure Process Expert for AVEVA System Platform
|
2023 |
Vendor Fix
fix
Mitigation
fix
|
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Public",
"tlp": {
"label": "WHITE"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
"title": "General Security Recommendations"
},
{
"category": "general",
"text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\n\n Customers should use appropriate patching methodologies when applying these patches to their systems. We\r\nstrongly recommend the use of back-ups and evaluating the impact of these patches in a Test and\r\nDevelopment environment or on an offline infrastructure. Contact Schneider Electric\u2019s Customer Care Center if\r\nyou need assistance removing a patch.\n\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
"title": "For More Information"
},
{
"category": "legal_disclaimer",
"text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
"title": "LEGAL DISCLAIMER"
},
{
"category": "general",
"text": "Schneider\u2019s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com",
"title": "About Schneider Electric"
},
{
"category": "summary",
"text": "Schneider Electric is aware of a vulnerability in its EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process \r\nExpert for AVEVA System Platform products. \r\nThe EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process Expert for AVEVA System Platform products are \r\nengineering tools that facilitates and automates the design, maintenance, commissioning, and operation of \r\nControl projects for Modicon controllers and the associated Supervision projects for SCADA software \r\nregrouped in a system.. \r\nFailure to apply the Fix/Mitigations provided below may risk a local privilege escalation, which could result in \r\nloss of confidentiality, integrity and availability of the engineering workstation.",
"title": "Overview"
},
{
"category": "other",
"text": "The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1 \nwill be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without \nincorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as \nthe presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u0027s environment."
},
{
"category": "other",
"text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric\u0027s [Customer Care Center](https://www.se.com/us/en/work/support/contacts.jsp) if you need assistance removing a patch."
}
],
"publisher": {
"category": "vendor",
"contact_details": "cpcert@se.com",
"name": "Schneider Electric CPCERT",
"namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
},
"references": [
{
"category": "self",
"summary": "EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process Expert for AVEVA - SEVD-2025-042-03 PDF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-042-03.pdf"
},
{
"category": "self",
"summary": "EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process Expert for AVEVA - SEVD-2025-042-03 CSAF Version",
"url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-042-03\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-042-03.json"
},
{
"category": "external",
"summary": "Recommended Cybersecurity Best Practices",
"url": "https://www.se.com/us/en/download/document/7EN52-0390"
}
],
"title": "EcoStruxure\u2122 Process Expert, EcoStruxure\u2122 Process Expert for AVEVA System Platform",
"tracking": {
"current_release_date": "2026-05-12T07:00:00.000Z",
"generator": {
"date": "2026-05-05T06:00:00Z",
"engine": {
"name": "Schneider Electric CSAF Generator",
"version": "1.2"
}
},
"id": "SEVD-2025-042-03",
"initial_release_date": "2025-02-11T06:00:00.000Z",
"revision_history": [
{
"date": "2025-02-11T06:00:00.000Z",
"number": "1.0.0",
"summary": "Original Release"
},
{
"date": "2026-05-12T07:00:00.000Z",
"number": "2.0.0",
"summary": "A remediation is available for EcoStruxure\u2122 Process Expert for AVEVA System Platform"
}
],
"status": "final",
"version": "2.0.0"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version",
"name": "2020 R2",
"product": {
"name": "EcoStruxure Process Expert version 2020 R2",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "EcoStruxure Process Expert"
},
{
"branches": [
{
"category": "product_version",
"name": "2021",
"product": {
"name": "EcoStruxure Process Expert version 2021",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "EcoStruxure Process Expert"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:intdot/\u003c4.8.0.5715",
"product": {
"name": "EcoStruxure Process Expert 2023 versions prior to v4.8.0.5715",
"product_id": "3"
}
}
],
"category": "product_name",
"name": "EcoStruxure Process Expert 2023"
},
{
"branches": [
{
"category": "product_version",
"name": "2020 R2",
"product": {
"name": "EcoStruxure Process Expert for AVEVA System Platform version 2020 R2",
"product_id": "4"
}
}
],
"category": "product_name",
"name": "EcoStruxure Process Expert for AVEVA System Platform"
},
{
"branches": [
{
"category": "product_version",
"name": "2021",
"product": {
"name": "EcoStruxure Process Expert for AVEVA System Platform version 2021",
"product_id": "5"
}
}
],
"category": "product_name",
"name": "EcoStruxure Process Expert for AVEVA System Platform"
},
{
"branches": [
{
"category": "product_version_range",
"name": "2023",
"product": {
"name": "EcoStruxure Process Expert for AVEVA System Platform 2023",
"product_id": "6"
}
}
],
"category": "product_name",
"name": "EcoStruxure Process Expert for AVEVA System Platform"
},
{
"branches": [
{
"category": "product_version",
"name": "2025",
"product": {
"name": "EcoStruxure Process Expert for AVEVA System Platform version 2025",
"product_id": "8"
}
}
],
"category": "product_name",
"name": "EcoStruxure Process Expert for AVEVA System Platform"
},
{
"branches": [
{
"category": "product_version",
"name": "4.8.0.5715",
"product": {
"name": "EcoStruxure Process Expert 2023 v4.8.0.5715",
"product_id": "7"
}
}
],
"category": "product_name",
"name": "EcoStruxure Process Expert 2023"
}
],
"category": "vendor",
"name": "Schneider Electric"
}
]
},
"vulnerabilities": [
{
"acknowledgments": [
{
"names": [
"Charit Misra"
],
"organization": "Applied Risk (DNV Cyber)"
}
],
"cve": "CVE-2025-0327",
"cwe": {
"id": "CWE-269",
"name": "Improper Privilege Management"
},
"notes": [
{
"category": "description",
"text": "CWE-269: Improper Privilege Management vulnerability exists for two services (of which one managing audit \r\ntrail data and the other acting as server managing client request) that could cause a loss of Confidentiality, \r\nIntegrity and Availability of engineering workstation when an attacker with standard privilege modifies the\r\nexecutable path of the windows services. To be exploited, services need to be restarted.",
"title": "CVE Description"
},
{
"category": "details",
"text": "CVSS v4.0 Base Score 8.5 | High | [CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N)",
"title": "CVSS v4.0 Score"
}
],
"product_status": {
"fixed": [
"7",
"8"
],
"known_affected": [
"1",
"2",
"3",
"4",
"5",
"6"
]
},
"remediations": [
{
"category": "vendor_fix",
"details": "Version v4.8.0.5715 of EcoStruxure\u2122 Process Expert 2023 Software \r\nPackage includes a fix for this vulnerability and is available for download \r\nhere:\r\nhttps://www.se.com/ww/en/product-range/65406-ecostruxure-process\u0002expert/#software-and-firmware\r\nUninstall Previous Version 2023 (v4.8.0.5115) before installing Version \r\n2023 (v4.8.0.5715).\r\nVersion string could be found on engineering server console.",
"product_ids": [
"1",
"2",
"3"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/ww/en/product-range/65406-ecostruxure-process-expert/#software-and-firmware"
},
{
"category": "vendor_fix",
"details": "Version 2025 of EcoStruxure\u2122 Process Expert for AVEVA System Platform 2025 Software Package includes a fix for this vulnerability and is available for download here:https://www.se.com/ww/en/product-range/55570689-ecostruxure-process-expert-for-aveva-system-platform/#software-and-firmware",
"product_ids": [
"4",
"5",
"6"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/ww/en/product-range/55570689-ecostruxure-process-expert-for-aveva-system-platform/#software-and-firmware"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:\n\n\u2022 Allow execute permission for service control Windows utility only to \r\nadmin user.\r\n\u2022 McAfee Application and Change Control software for application control\r\nto allow execution of whitelisted applications only. Refer to the \r\nCybersecurity Application Note available\r\nhttps://www.se.com/ww/en/download/document/EIO0000004778/",
"product_ids": [
"1",
"2",
"3"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
},
{
"category": "mitigation",
"details": "If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: \u2022 Allow only admin user to configure windows service by restricting \r\nexecute permission of sc.exe windows utility. \n\n\u2022 McAfee Application and Change Control software for application control \r\nto allow execution of whitelisted applications only. Refer to the \r\nCybersecurity Application Note available\r\nhttps://www.se.com/ww/en/download/document/EIO0000004778/",
"product_ids": [
"4",
"5",
"6"
],
"restart_required": {
"category": "none"
},
"url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
}
],
"scores": [
{
"cvss_v3": {
"attackComplexity": "LOW",
"attackVector": "LOCAL",
"availabilityImpact": "HIGH",
"baseScore": 7.8,
"baseSeverity": "HIGH",
"confidentialityImpact": "HIGH",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1",
"2",
"3",
"4",
"5",
"6"
]
}
],
"title": "CVE-2025-0327"
}
]
}
Sightings
| Author | Source | Type | Date | Other |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or observed by the user.
- Confirmed: The vulnerability has been validated from an analyst's perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
- Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
- Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
- Not confirmed: The user expressed doubt about the validity of the vulnerability.
- Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.