Summary
SSA-631336: Multiple Web Server Vulnerabilities in SICAM GridEdge Before V2.6.6
Notes
Summary
Multiple vulnerabilities were identified in the web server of the SICAM GridEdge application which includes missing authentication for critical API functions, absent cross-origin resource sharing restrictions and access to credentials.
Siemens has released a new version for SICAM GridEdge (Classic) and recommends to update to the latest version.
General Recommendations
Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.
Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.
As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Recommended security guidelines can be found at:
https://www.siemens.com/gridsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
"tlp": {
"label": "WHITE"
}
},
"lang": "en",
"notes": [
{
"category": "summary",
"text": "Multiple vulnerabilities were identified in the web server of the SICAM GridEdge application which includes missing authentication for critical API functions, absent cross-origin resource sharing restrictions and access to credentials.\n\nSiemens has released a new version for SICAM GridEdge (Classic) and recommends to update to the latest version.",
"title": "Summary"
},
{
"category": "general",
"text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\nhttps://www.siemens.com/gridsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-631336: Multiple Web Server Vulnerabilities in SICAM GridEdge Before V2.6.6 - HTML Version",
"url": "https://cert-portal.siemens.com/productcert/html/ssa-631336.html"
},
{
"category": "self",
"summary": "SSA-631336: Multiple Web Server Vulnerabilities in SICAM GridEdge Before V2.6.6 - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-631336.json"
}
],
"title": "SSA-631336: Multiple Web Server Vulnerabilities in SICAM GridEdge Before V2.6.6",
"tracking": {
"current_release_date": "2025-11-11T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-631336",
"initial_release_date": "2022-06-14T00:00:00Z",
"revision_history": [
{
"date": "2022-06-14T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
},
{
"date": "2025-11-11T00:00:00Z",
"legacy_version": "1.1",
"number": "2",
"summary": "Updated SSA to current data model and support of csaf; removed software-license based MLFB information; revised CVSSv3.1 vectors and added CVSSv4 vectors"
}
],
"status": "interim",
"version": "2"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:intdot/\u003c2.6.6",
"product": {
"name": "SICAM GridEdge (Classic)",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "SICAM GridEdge (Classic)"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2022-30228",
"cwe": {
"id": "CWE-346",
"name": "Origin Validation Error"
},
"notes": [
{
"category": "summary",
"text": "The affected software does not apply cross-origin resource sharing (CORS) restrictions for critical operations. In case an attacker tricks a legitimate user into accessing a special resource a malicious request could be executed.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Limit access to port 8900/tcp to trusted users and systems only",
"product_ids": [
"1"
]
},
{
"category": "vendor_fix",
"details": "Update to V2.6.6 or later version",
"product_ids": [
"1"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109780559/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 8.8,
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-30228"
},
{
"cve": "CVE-2022-30229",
"cwe": {
"id": "CWE-306",
"name": "Missing Authentication for Critical Function"
},
"notes": [
{
"category": "summary",
"text": "The affected application does not require authenticated access for privileged functions. This could allow an unauthenticated attacker to change data of a user, such as credentials, in case that user\u0027s id is known.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Limit access to port 8900/tcp to trusted users and systems only",
"product_ids": [
"1"
]
},
{
"category": "vendor_fix",
"details": "Update to V2.6.6 or later version",
"product_ids": [
"1"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109780559/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 7.2,
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-30229"
},
{
"cve": "CVE-2022-30230",
"cwe": {
"id": "CWE-306",
"name": "Missing Authentication for Critical Function"
},
"notes": [
{
"category": "summary",
"text": "The affected application does not require authenticated access for privileged functions. This could allow an unauthenticated attacker to create a new user with administrative permissions.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Limit access to port 8900/tcp to trusted users and systems only",
"product_ids": [
"1"
]
},
{
"category": "vendor_fix",
"details": "Update to V2.6.6 or later version",
"product_ids": [
"1"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109780559/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 9.8,
"baseSeverity": "CRITICAL",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-30230"
},
{
"cve": "CVE-2022-30231",
"cwe": {
"id": "CWE-402",
"name": "Transmission of Private Resources into a New Sphere (\u0027Resource Leak\u0027)"
},
"notes": [
{
"category": "summary",
"text": "The affected application discloses password hashes of other users upon request. This could allow an authenticated user to retrieve another user\u0027s password hash.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Limit access to port 8900/tcp to trusted users and systems only",
"product_ids": [
"1"
]
},
{
"category": "vendor_fix",
"details": "Update to V2.6.6 or later version",
"product_ids": [
"1"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109780559/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 4.9,
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:N/A:N",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-30231"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…