ssa-225578
Vulnerability from csaf_siemens
Published
2022-07-12 00:00
Modified
2025-11-11 00:00
Summary
SSA-225578: Improper Access Control Vulnerability in SICAM GridEdge Before V2.7.3
Notes
Summary
SICAM GridEdge contains an improper access control vulnerability. This could allow persons with local access to the host system to inject an SSH key.
Siemens has released a new version for SICAM GridEdge (Classic) and recommends to update to the latest version.
General Recommendations
Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.
Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.
As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Recommended security guidelines can be found at:
https://www.siemens.com/gridsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
"tlp": {
"label": "WHITE"
}
},
"lang": "en",
"notes": [
{
"category": "summary",
"text": "SICAM GridEdge contains an improper access control vulnerability. This could allow persons with local access to the host system to inject an SSH key.\n\nSiemens has released a new version for SICAM GridEdge (Classic) and recommends to update to the latest version.",
"title": "Summary"
},
{
"category": "general",
"text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\nhttps://www.siemens.com/gridsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-225578: Improper Access Control Vulnerability in SICAM GridEdge Before V2.7.3 - HTML Version",
"url": "https://cert-portal.siemens.com/productcert/html/ssa-225578.html"
},
{
"category": "self",
"summary": "SSA-225578: Improper Access Control Vulnerability in SICAM GridEdge Before V2.7.3 - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-225578.json"
}
],
"title": "SSA-225578: Improper Access Control Vulnerability in SICAM GridEdge Before V2.7.3",
"tracking": {
"current_release_date": "2025-11-11T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-225578",
"initial_release_date": "2022-07-12T00:00:00Z",
"revision_history": [
{
"date": "2022-07-12T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
},
{
"date": "2025-11-11T00:00:00Z",
"legacy_version": "1.1",
"number": "2",
"summary": "Updated SSA to current data model and support of csaf; removed software-license based MLFB information; added CVSSv4 vector; changed CWE id from CWE-668 to CWE-552"
}
],
"status": "interim",
"version": "2"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:intdot/\u003c2.7.3",
"product": {
"name": "SICAM GridEdge (Classic)",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "SICAM GridEdge (Classic)"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2022-34464",
"cwe": {
"id": "CWE-552",
"name": "Files or Directories Accessible to External Parties"
},
"notes": [
{
"category": "summary",
"text": "The affected application uses an improperly protected file to import SSH keys. This could allow attackers with access to the filesystem of the host on which SICAM GridEdge runs to inject a custom SSH key to that file.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1"
]
},
"remediations": [
{
"category": "mitigation",
"details": "Restrict physical access to the device and limit access to the ssh port (22/tcp) to trusted IP addresses if possible.",
"product_ids": [
"1"
]
},
{
"category": "vendor_fix",
"details": "Update to V2.7.3 or later version",
"product_ids": [
"1"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109780559/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 6.3,
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:L/A:L",
"version": "3.1"
},
"products": [
"1"
]
}
],
"title": "CVE-2022-34464"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…