SEVD-2024-044-01

Vulnerability from csaf_se - Published: 2024-02-13 12:41 - Updated: 2026-04-14 07:00
Summary
EcoStruxure™ Control Expert, EcoStruxure™ Process Expert and Modicon M340, M580 and M580 Safety PLCs
Notes
General Security Recommendations: We strongly recommend the following industry cybersecurity best practices. * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric [Recommended Cybersecurity Best Practices](https://www.se.com/us/en/download/document/7EN52-0390/) document.
For More Information: This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric's products, visit the company's cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER: THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric: Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and sustainability for all. We call this Life Is On. Our mission is to be the trusted partner in Sustainability and Efficiency. We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation, software and services, delivering digital twins to enable profitable growth for our customers. We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our meaningful purpose of a sustainable future for all. www.se.com
Overview: Schneider Electric is aware of multiple vulnerabilities in its EcoStruxure™ Control Expert , EcoStruxure™ Process Expert and Modicon M340, M580 PLCs (Programmable Logic Controllers). Modicon PLCs control and monitor industrial operations. EcoStruxure™ Control Expert is the common programming, debugging and operating software for Modicon PLCs. EcoStruxure™ Process Expert DCS is a single automation system to engineer, operate, and maintain an entire plant Infrastructure. Failure to apply the remediations provided below may risk unauthorized access to your PLC, which could result in the possibility of denial of service and loss of confidentiality, integrity of the controller. Note regarding vulnerability details: The severity of vulnerabilities was calculated using the CVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer’s environment
The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1 will be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer's environment.
Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric's [Customer Care Center](https://www.se.com/us/en/work/support/contacts.jsp) if you need assistance removing a patch.

A CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack.

CWE-924 - Improper Enforcement of Message Integrity During Transmission in a Communication Channel
Vendor Fix SV3.60 of Modicon M340 firmware includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/1468- modicon-m340 https://www.se.com/ww/en/product-range/1468-modic…
Vendor Fix SV4.20 of Modicon M580 firmware includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/62098- modicon-m580-epac/ - software-and-firmware https://www.se.com/ww/en/product-range/62098-%20m…
Vendor Fix Version 16.0 of EcoStruxure Control Expert includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/548- ecostruxure-control-expert-unity-pro/ Reboot the computer after installation is completed https://www.se.com/in/en/product-range/548-ecostr…
Vendor Fix Version 15.3 HF008 of EcoStruxure Control Expert includes the fix for these vulnerabilities and are available for download here: https://www.se.com/ww/en/product-range/548- ecostruxure-control-expert-unity-pro/ https://www.se.com/ww/en/product-range/548-ecostr…
Vendor Fix Firmware SV4.21 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/62098-modicon-m580-pac-controller/#software-andfirmware Important: customer needs to use version of EcoStruxure™ Control Expert v16.0 HF001 minimum to connect with the latest version of M580 CPU Safety. The software is available for download here: https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#software-andfirmware https://www.se.com/ww/en/product-range/62098-modi…
Mitigation Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M340 for Ethernet Communications Modules and Processors User Manual” in chapter “Messaging Configuration Parameters”: https://www.se.com/ww/en/download/document/31007131K01000/ • Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M340 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: • https://www.se.com/ww/en/download/document/EIO0000001999/ https://www.se.com/ww/en/download/document/310071…
Mitigation Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M580, Hardware, Reference Manual”: https://www.se.com/ww/en/download/document/EIO0000001578/ Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • use a BMENOC module and follow the instructions to configure IPSEC feature as described in the guideline “Modicon M580 - BMENOC03.1 Ethernet Communications Schneider Electric Security Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”: https://www.se.com/ww/en/download/document/HRB62665/ OR • Use a BMENUA0100 module and follow the instructions to configure IPSEC feature as described in the chapter “Configuring the BMENUA0100 Cybersecurity Settings”: https://www.se.com/ww/en/download/document/PHA83350 OR • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M580 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: https://www.schneiderelectric.com/en/download/document/EIO0000001999/ NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication. https://www.se.com/ww/en/download/document/EIO000…
Mitigation If customers choose not to apply the remediation then they are encouraged to immediately apply the following mitigations to reduce the risk of exploit: • Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M580, Hardware, Reference Manual”: https://www.se.com/ww/en/download/document/EIO0000001578/ • Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • use a BMENOC module and follow the instructions to configure IPSEC feature as described in the guideline “Modicon M580 - BMENOC03.1 Ethernet Communications Schneider Electric Security Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”: https://www.se.com/ww/en/download/document/HRB62665/ OR • Use a BMENUA0100 module and follow the instructions to configure IPSEC feature as described in the chapter “Configuring the BMENUA0100 Cybersecurity Settings”: https://www.se.com/ww/en/download/document/PHA83350 OR • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M580 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: https://www.schneiderelectric.com/en/download/document/EIO0000001999/ NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication. • To further reduce the attack surface on Modicon M580 CPU Safety: Ensure the CPU is running in Safety mode and maintenance input is configured to maintain this Safety mode during operation – refer to the document Modicon M580 - Safety System Planning Guide - in the chapter “Operating Mode Transitions”: https://www.se.com/ww/en/download/document/QGH60283/ https://www.se.com/ww/en/download/document/EIO000…
Mitigation Enable encryption on application project and store application files in secure location with restricted access only for legitimate users. • Schneider Electric recommends using McAfee Application and Change Control software for application control. Refer to the Cybersecurity Application Note available here. • Follow workstation, network and site-hardening guidelines in the Recommended Cybersecurity Best Practices available for download here. https://www.se.com/ww/en/download/document/EIO000…
Mitigation EcoStruxure Process Expert manages application files within its database in secure way. Do not export & store them outside the application. • Schneider Electric recommends using McAfee Application and Change Control software for application control. Refer to the Cybersecurity Application Note available here. • Follow workstation, network and site-hardening guidelines in the Recommended Cybersecurity Best Practices available for download here. https://www.se.com/ww/en/download/document/EIO000…
Mitigation Setup an application password in the project properties• Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP• Configure the Access Control List following the recommendations of the user manuals:• “Modicon MC80 Programmable Logic Controller (PLC) manual” in the chapter “Access Control List (ACL)”:https://www.se.com/ww/en/download/document/EIO0000002071/Setup a secure communication according to the following guideline “Modicon Controller Systems Cybersecurity, User Guide” in chapter “Set Up Encrypted Communication”: https://www.se.com/ww/en/download/document/EIO000…
Mitigation Setup an application password in the project properties• Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP• Setup a secure communication according to the following guideline “Modicon Controller Systems Cybersecurity, User Guide” in chapter “Set Up Encrypted Communication”: https://www.se.com/ww/en/download/document/EIO000…
Vendor Fix Firmware SV2.90 includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/535-modicon-momentum/ Important: customer needs to use version of EcoStruxure™ Control Expert v16.2 HF003 minimum to connect with the latest version of Modicon Momentum. The software is available for download here: https://www.se.com/ww/en/product-range/548-ecostruxure control-expert-unity-pro/#software-and-firmware https://www.se.com/ww/en/product-range/535-modico…

A CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to a project file protected with application password when opening the file with EcoStruxure Control Expert.

CWE-798 - Use of Hard-coded Credentials
Vendor Fix SV3.60 of Modicon M340 firmware includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/1468- modicon-m340 https://www.se.com/ww/en/product-range/1468-modic…
Vendor Fix SV4.20 of Modicon M580 firmware includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/62098- modicon-m580-epac/ - software-and-firmware https://www.se.com/ww/en/product-range/62098-%20m…
Vendor Fix Version 16.0 of EcoStruxure Control Expert includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/548- ecostruxure-control-expert-unity-pro/ Reboot the computer after installation is completed https://www.se.com/in/en/product-range/548-ecostr…
Vendor Fix Version 15.3 HF008 of EcoStruxure Control Expert includes the fix for these vulnerabilities and are available for download here: https://www.se.com/ww/en/product-range/548- ecostruxure-control-expert-unity-pro/ https://www.se.com/ww/en/product-range/548-ecostr…
Mitigation Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M340 for Ethernet Communications Modules and Processors User Manual” in chapter “Messaging Configuration Parameters”: https://www.se.com/ww/en/download/document/31007131K01000/ • Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M340 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: • https://www.se.com/ww/en/download/document/EIO0000001999/ https://www.se.com/ww/en/download/document/310071…
Mitigation Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M580, Hardware, Reference Manual”: https://www.se.com/ww/en/download/document/EIO0000001578/ Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • use a BMENOC module and follow the instructions to configure IPSEC feature as described in the guideline “Modicon M580 - BMENOC03.1 Ethernet Communications Schneider Electric Security Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”: https://www.se.com/ww/en/download/document/HRB62665/ OR • Use a BMENUA0100 module and follow the instructions to configure IPSEC feature as described in the chapter “Configuring the BMENUA0100 Cybersecurity Settings”: https://www.se.com/ww/en/download/document/PHA83350 OR • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M580 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: https://www.schneiderelectric.com/en/download/document/EIO0000001999/ NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication. https://www.se.com/ww/en/download/document/EIO000…
Mitigation Schneider Electric is establishing a remediation plan for all future versions of EcoStruxure™ Process Expert that will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M580, Hardware, Reference Manual”: https://www.se.com/ww/en/download/document/EIO0000001578/ • Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • use a BMENOC module and follow the instructions to configure IPSEC feature as described in the guideline “Modicon M580 - BMENOC03.1 Ethernet Communications Schneider Electric Security Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”: https://www.se.com/ww/en/download/document/HRB62665/ OR • Use a BMENUA0100 module and follow the instructions to configure IPSEC feature as described in the chapter “Configuring the BMENUA0100 Cybersecurity Settings”: https://www.se.com/ww/en/download/document/PHA83350 OR • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M580 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: https://www.schneiderelectric.com/en/download/document/EIO0000001999/ NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication. • To further reduce the attack surface on Modicon M580 CPU Safety: Ensure the CPU is running in Safety mode and maintenance input is configured to maintain this Safety mode during operation – refer to the document Modicon M580 - Safety System Planning Guide - in the chapter “Operating Mode Transitions”: https://www.se.com/ww/en/download/document/QGH60283/ https://www.se.com/ww/en/download/document/EIO000…
Mitigation Enable encryption on application project and store application files in secure location with restricted access only for legitimate users. • Schneider Electric recommends using McAfee Application and Change Control software for application control. Refer to the Cybersecurity Application Note available here. • Follow workstation, network and site-hardening guidelines in the Recommended Cybersecurity Best Practices available for download here. https://www.se.com/ww/en/download/document/EIO000…
Mitigation EcoStruxure Process Expert manages application files within its database in secure way. Do not export & store them outside the application. • Schneider Electric recommends using McAfee Application and Change Control software for application control. Refer to the Cybersecurity Application Note available here. • Follow workstation, network and site-hardening guidelines in the Recommended Cybersecurity Best Practices available for download here. https://www.se.com/ww/en/download/document/EIO000…

A CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause unauthorized access to the project file in EcoStruxure™ Control Expert when a local user tampers with the memory of the engineering workstation.

CWE-522 - Insufficiently Protected Credentials
Vendor Fix SV3.60 of Modicon M340 firmware includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/1468- modicon-m340 https://www.se.com/ww/en/product-range/1468-modic…
Vendor Fix SV4.20 of Modicon M580 firmware includes a fix for this vulnerability and is available for download here: https://www.se.com/ww/en/product-range/62098- modicon-m580-epac/ - software-and-firmware https://www.se.com/ww/en/product-range/62098-%20m…
Vendor Fix Version 16.0 of EcoStruxure Control Expert includes a fix for these vulnerabilities and is available for download here: https://www.se.com/ww/en/product-range/548- ecostruxure-control-expert-unity-pro/ Reboot the computer after installation is completed https://www.se.com/in/en/product-range/548-ecostr…
Vendor Fix Version 15.3 HF008 of EcoStruxure Control Expert includes the fix for these vulnerabilities and are available for download here: https://www.se.com/ww/en/product-range/548- ecostruxure-control-expert-unity-pro/ https://www.se.com/ww/en/product-range/548-ecostr…
Mitigation Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M340 for Ethernet Communications Modules and Processors User Manual” in chapter “Messaging Configuration Parameters”: https://www.se.com/ww/en/download/document/31007131K01000/ • Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M340 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: • https://www.se.com/ww/en/download/document/EIO0000001999/ https://www.se.com/ww/en/download/document/310071…
Mitigation Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M580, Hardware, Reference Manual”: https://www.se.com/ww/en/download/document/EIO0000001578/ Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • use a BMENOC module and follow the instructions to configure IPSEC feature as described in the guideline “Modicon M580 - BMENOC03.1 Ethernet Communications Schneider Electric Security Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”: https://www.se.com/ww/en/download/document/HRB62665/ OR • Use a BMENUA0100 module and follow the instructions to configure IPSEC feature as described in the chapter “Configuring the BMENUA0100 Cybersecurity Settings”: https://www.se.com/ww/en/download/document/PHA83350 OR • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M580 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: https://www.schneiderelectric.com/en/download/document/EIO0000001999/ NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication. https://www.se.com/ww/en/download/document/EIO000…
Mitigation Schneider Electric is establishing a remediation plan for all future versions of EcoStruxure™ Process Expert that will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit: • Setup an application password in the project properties • Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP • Configure the Access Control List following the recommendations of the user manuals: “Modicon M580, Hardware, Reference Manual”: https://www.se.com/ww/en/download/document/EIO0000001578/ • Setup a secure communication according to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual,” in chapter “Setup secured communications”: https://www.se.com/ww/en/download/document/EIO0000001999/ • use a BMENOC module and follow the instructions to configure IPSEC feature as described in the guideline “Modicon M580 - BMENOC03.1 Ethernet Communications Schneider Electric Security Notification Module, Installation and Configuration Guide” in the chapter “Configuring IPSEC communications”: https://www.se.com/ww/en/download/document/HRB62665/ OR • Use a BMENUA0100 module and follow the instructions to configure IPSEC feature as described in the chapter “Configuring the BMENUA0100 Cybersecurity Settings”: https://www.se.com/ww/en/download/document/PHA83350 OR • Consider use of external firewall devices such as EAGLE40-07 from Belden to establish VPN connections for M340 & M580 architectures. For more details refer to the chapter “How to protect M580 and M340 architectures with EAGLE40 using VPN”: https://www.se.com/ww/en/download/document/EIO0000001999/ • Ensure the M580 CPU is running with the memory protection activated by configuring the input bit to a physical input, for more details refer to the following guideline “Modicon Controllers Platform Cyber Security Reference Manual”, “CPU Memory Protection section”: https://www.schneiderelectric.com/en/download/document/EIO0000001999/ NOTE: The CPU memory protection cannot be configured with M580 Hot Standby CPUs. In such cases, use IPsec encrypted communication. • To further reduce the attack surface on Modicon M580 CPU Safety: Ensure the CPU is running in Safety mode and maintenance input is configured to maintain this Safety mode during operation – refer to the document Modicon M580 - Safety System Planning Guide - in the chapter “Operating Mode Transitions”: https://www.se.com/ww/en/download/document/QGH60283/ https://www.se.com/ww/en/download/document/EIO000…
Mitigation Enable encryption on application project and store application files in secure location with restricted access only for legitimate users. • Schneider Electric recommends using McAfee Application and Change Control software for application control. Refer to the Cybersecurity Application Note available here. • Follow workstation, network and site-hardening guidelines in the Recommended Cybersecurity Best Practices available for download here. https://www.se.com/ww/en/download/document/EIO000…
Mitigation EcoStruxure Process Expert manages application files within its database in secure way. Do not export & store them outside the application. • Schneider Electric recommends using McAfee Application and Change Control software for application control. Refer to the Cybersecurity Application Note available here. • Follow workstation, network and site-hardening guidelines in the Recommended Cybersecurity Best Practices available for download here. https://www.se.com/ww/en/download/document/EIO000…
Acknowledgments
Gao Jian
Jianshuang Ding
Kaikai Yang

{
  "document": {
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Public",
      "tlp": {
        "label": "WHITE"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\n\nFor more information refer to the Schneider Electric [Recommended Cybersecurity Best Practices](https://www.se.com/us/en/download/document/7EN52-0390/) document.",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\n\nFor further information related to cybersecurity in Schneider Electric\u0027s products, visit the company\u0027s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "Schneider\u0027s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of multiple vulnerabilities in its EcoStruxure\u2122 Control Expert ,\r\nEcoStruxure\u2122 Process Expert and Modicon M340, M580 PLCs (Programmable Logic\r\nControllers).\r\nModicon PLCs control and monitor industrial operations. EcoStruxure\u2122 Control Expert is the\r\ncommon programming, debugging and operating software for Modicon PLCs. EcoStruxure\u2122\r\nProcess Expert DCS is a single automation system to engineer, operate, and maintain an entire\r\nplant Infrastructure.\r\nFailure to apply the remediations provided below may risk unauthorized access to your PLC,\r\nwhich could result in the possibility of denial of service and loss of confidentiality, integrity of the\r\ncontroller.\r\n\r\nNote regarding vulnerability details: The severity of vulnerabilities was calculated using the\r\nCVSS Base metrics in version 3.1 (CVSS v3.1) without incorporating the Temporal and\r\nEnvironmental metrics. Schneider Electric recommends that customers score the CVSS\r\nEnvironmental metrics, which are specific to end-user organizations, and consider factors such\r\nas the presence of mitigations in that environment. Environmental metrics may refine the\r\nrelative severity posed by the vulnerabilities described in this document within a customer\u2019s \renvironment",
        "title": "Overview"
      },
      {
        "category": "other",
        "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1 \nwill be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without \nincorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as \nthe presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u0027s environment."
      },
      {
        "category": "other",
        "text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric\u0027s [Customer Care Center](https://www.se.com/us/en/work/support/contacts.jsp) if you need assistance removing a patch. "
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "cpcert@se.com",
      "name": "Schneider Electric CPCERT",
      "namespace": "https://www.se.com/ww/en/work/support/cybersecurity/security-notifications.jsp"
    },
    "references": [
      {
        "category": "self",
        "summary": "EcoStruxure\u2122 Control Expert, EcoStruxure\u2122 Process Expert and Modicon M340, M580 and M580 Safety PLCs - SEVD-2024-044-01 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-044-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2024-044-01.pdf"
      },
      {
        "category": "self",
        "summary": "EcoStruxure\u2122 Control Expert, EcoStruxure\u2122 Process Expert and Modicon M340, M580 and M580 Safety PLCs - SEVD-2024-044-01 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2024-044-01\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2024-044-01.json"
      },
      {
        "category": "external",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/ww/en/download/document/7EN52-0390/"
      }
    ],
    "title": "EcoStruxure\u2122 Control Expert, EcoStruxure\u2122 Process Expert and Modicon M340, M580 and M580 Safety PLCs",
    "tracking": {
      "current_release_date": "2026-04-14T07:00:00.000Z",
      "generator": {
        "date": "2026-04-13T13:08:28.226Z",
        "engine": {
          "name": "Schneider Electric CSAF Generator",
          "version": "1.2"
        }
      },
      "id": "SEVD-2024-044-01",
      "initial_release_date": "2024-02-13T12:41:43.000Z",
      "revision_history": [
        {
          "date": "2024-02-13T12:41:43.000Z",
          "number": "1.0.0",
          "summary": "Original Release"
        },
        {
          "date": "2024-07-09T00:00:00.000Z",
          "number": "2.0.0",
          "summary": "Modicon MC80 and Momentum M1E PLCs have been identified as impacted by the CVE-2023-6408. Mitigations are now available"
        },
        {
          "date": "2024-08-13T00:00:00.000Z",
          "number": "3.0.0",
          "summary": "A remediation is available for the Modicon M580 CPU Safety (page 3)."
        },
        {
          "date": "2026-04-14T07:00:00.000Z",
          "number": "4.0.0",
          "summary": "Remediation is available for Modicon Momentum controller "
        }
      ],
      "status": "final",
      "version": "4.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/\u003cSV3.60",
                "product": {
                  "name": "Modicon M340 CPU (part numbers BMXP34*) Versions prior to sv3.60",
                  "product_id": "1"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M340 CPU (part numbers BMXP34*)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/\u003cSV4.20",
                "product": {
                  "name": "Modicon M580 CPU (part numbers BMEP* and BMEH* excluding M580 CPU Safety) Versions prior to sv4.20",
                  "product_id": "2"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU (part numbers BMEP* and BMEH* excluding M580 CPU Safety)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/\u003cSV4.21",
                "product": {
                  "name": "Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) Versions prior to SV4.21",
                  "product_id": "3",
                  "product_identification_helper": {
                    "model_numbers": [
                      "BMEP58*S",
                      "BMEH58*S"
                    ]
                  }
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU Safety"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "vers:generic/SV4.21",
                "product": {
                  "name": "Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) Version SV4.21",
                  "product_id": "12",
                  "product_identification_helper": {
                    "model_numbers": [
                      "BMEP58*S",
                      "BMEH58*S"
                    ]
                  }
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU Safety"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:intdot/\u003c16.0",
                "product": {
                  "name": "EcoStruxure\u2122 Control Expert Versions prior to v16.0",
                  "product_id": "4"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Control Expert"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/\u003c2023",
                "product": {
                  "name": "EcoStruxure\u2122 Process Expert Versions prior to v2023",
                  "product_id": "5"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Process Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "SV3.60",
                "product": {
                  "name": "Modicon M340 CPU (part numbers BMXP34*) SV3.60",
                  "product_id": "6"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M340 CPU (part numbers BMXP34*)"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "SV4.20",
                "product": {
                  "name": "Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety)  SV4.20",
                  "product_id": "7"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon M580 CPU (part numbers BMEP* and BMEH*, excluding M580 CPU Safety)"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "16.0",
                "product": {
                  "name": "EcoStruxure\u2122 Control Expert Version 16.0",
                  "product_id": "8"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Control Expert"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "15.3 HF008",
                "product": {
                  "name": "EcoStruxure\u2122 Process Expert Version 15.3 HF008",
                  "product_id": "9"
                }
              }
            ],
            "category": "product_name",
            "name": "EcoStruxure\u2122 Process Expert"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "Modicon MC80 (part numbers BMKC80) All Versions",
                  "product_id": "10"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon MC80 (part numbers BMKC80)"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/\u003cSV2.90",
                "product": {
                  "name": "Modicon Momentum Unity M1E Processor Firmware Versions prior to SV2.90",
                  "product_id": "11"
                }
              },
              {
                "category": "product_version",
                "name": "SV2.90",
                "product": {
                  "name": "Modicon Momentum Unity M1E  Processor Firmware Version SV2.90",
                  "product_id": "13"
                }
              }
            ],
            "category": "product_name",
            "name": "Modicon Momentum Unity M1E Processor Firmware"
          },
          {
            "category": "product_name",
            "name": "Modicon Momentum Unity M1E Processor Controller",
            "product": {
              "name": "Modicon Momentum Unity M1E Processor Controller",
              "product_id": "14",
              "product_identification_helper": {
                "model_numbers": [
                  "171CBU*"
                ]
              }
            }
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ],
    "relationships": [
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Modicon Momentum Unity M1E Processor Firmware Versions prior to SV2.90 installed on Modicon Momentum Unity M1E Processor Controller",
          "product_id": "15",
          "product_identification_helper": {
            "model_numbers": [
              "171CBU*"
            ]
          }
        },
        "product_reference": "11",
        "relates_to_product_reference": "14"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Modicon Momentum Unity M1E Processor Firmware Version SV2.90 installed on Modicon Momentum Unity M1E Processor Controller",
          "product_id": "16",
          "product_identification_helper": {
            "model_numbers": [
              "171CBU*"
            ]
          }
        },
        "product_reference": "13",
        "relates_to_product_reference": "14"
      }
    ]
  },
  "vulnerabilities": [
    {
      "acknowledgments": [
        {
          "names": [
            "Gao Jian"
          ]
        }
      ],
      "cve": "CVE-2023-6408",
      "cwe": {
        "id": "CWE-924",
        "name": "Improper Enforcement of Message Integrity During Transmission in a Communication Channel"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-924: Improper Enforcement of Message Integrity During Transmission in a\r\nCommunication Channel vulnerability exists that could cause a denial of service and loss of\r\nconfidentiality, integrity of controllers when conducting a Man in the Middle attack.",
          "title": "CVE Description"
        },
        {
          "category": "details",
          "text": "CVSS v4.0 Base Score 9.2 | Critical | [CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:N/AC:H/AT:P/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N)",
          "title": "CVSS v4.0 Score"
        }
      ],
      "product_status": {
        "fixed": [
          "6",
          "7",
          "8",
          "9",
          "12",
          "16"
        ],
        "known_affected": [
          "1",
          "2",
          "3",
          "4",
          "5",
          "10",
          "15"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "SV3.60 of Modicon M340 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/1468-\r\nmodicon-m340",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1468-modicon-m340"
        },
        {
          "category": "vendor_fix",
          "details": "SV4.20 of Modicon M580 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/62098-\r\nmodicon-m580-epac/ - software-and-firmware",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-%20modicon-m580-epac/%20-%20software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Version 16.0 of EcoStruxure Control Expert includes a fix\r\nfor these vulnerabilities and is available for download\r\nhere:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/\r\nReboot the computer after installation is completed",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/in/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "vendor_fix",
          "details": "Version 15.3 HF008 of EcoStruxure Control Expert\r\nincludes the fix for these vulnerabilities and are available\r\nfor download here:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SV4.21 includes a fix for this vulnerability and \r\nis available for download here: https://www.se.com/ww/en/product-range/62098-modicon-m580-pac-controller/#software-andfirmware\r\nImportant: customer needs to use version of \r\nEcoStruxure\u2122 Control Expert v16.0 HF001 minimum to \r\nconnect with the latest version of M580 CPU Safety. The \r\nsoftware is available for download here:\r\nhttps://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/#software-andfirmware",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-modicon-m580-pac-controller/#software-andfirmware"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M340 for Ethernet Communications Modules\r\nand Processors User Manual\u201d in chapter \u201cMessaging Configuration\r\nParameters\u201d:\r\nhttps://www.se.com/ww/en/download/document/31007131K01000/\r\n\u2022 Setup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M340 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\n\u2022 https://www.se.com/ww/en/download/document/EIO0000001999/",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/31007131K01000/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M580, Hardware, Reference Manual\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\nSetup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline \u201cModicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration\r\nGuide\u201d in the chapter \u201cConfiguring IPSEC communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter \u201cConfiguring the\r\nBMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580 Hot\r\nStandby CPUs. In such cases, use IPsec encrypted communication.",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation then they are encouraged to immediately apply the following mitigations to reduce the risk of exploit:\r\n\u2022 Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M580, Hardware, Reference Manual\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\n\u2022 Setup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline \u201cModicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration Guide\u201d in the chapter \u201cConfiguring IPSEC communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter \u201cConfiguring the\r\nBMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580\r\nHot Standby CPUs. In such cases, use IPsec encrypted\r\ncommunication.\r\n\u2022 To further reduce the attack surface on Modicon M580 CPU\r\nSafety:\r\nEnsure the CPU is running in Safety mode and maintenance input is\r\nconfigured to maintain this Safety mode during operation \u2013 refer to\r\nthe document Modicon M580 - Safety System Planning Guide - in\r\nthe chapter \u201cOperating Mode Transitions\u201d:\r\nhttps://www.se.com/ww/en/download/document/QGH60283/ ",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Enable encryption on application project and store application files in\r\nsecure location with restricted access only for legitimate users.\r\n\u2022 Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n\u2022 Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        },
        {
          "category": "mitigation",
          "details": "EcoStruxure Process Expert manages application files within its\r\ndatabase in secure way. Do not export \u0026 store them outside the\r\napplication.\r\n\u2022 Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n\u2022 Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\u2022 Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP\u2022 Configure the Access Control List following the recommendations of the user manuals:\u2022 \u201cModicon MC80 Programmable Logic Controller (PLC) manual\u201d in the chapter \u201cAccess Control List (ACL)\u201d:https://www.se.com/ww/en/download/document/EIO0000002071/Setup a secure communication according to the following guideline \u201cModicon Controller Systems Cybersecurity, User Guide\u201d in chapter \u201cSet Up Encrypted Communication\u201d:",
          "product_ids": [
            "10"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001999/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\u2022 Setup network segmentation and implement a firewall to block all unauthorized access to port 502/TCP\u2022 Setup a secure communication according to the following guideline \u201cModicon Controller Systems Cybersecurity, User Guide\u201d in chapter \u201cSet Up Encrypted Communication\u201d:",
          "product_ids": [
            "15"
          ],
          "url": "https://www.se.com/ww/en/download/document/EIO0000001999/"
        },
        {
          "category": "vendor_fix",
          "details": "Firmware SV2.90 includes a fix for this vulnerability and is \navailable for download here: \n \nhttps://www.se.com/ww/en/product-range/535-modicon-momentum/ \n \nImportant: customer needs to use version of EcoStruxure\u2122 \nControl Expert v16.2 HF003 minimum to connect with the latest \nversion of Modicon Momentum. The software is available for \ndownload here: \n \nhttps://www.se.com/ww/en/product-range/548-ecostruxure\ncontrol-expert-unity-pro/#software-and-firmware",
          "product_ids": [
            "15"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/ww/en/product-range/535-modicon-momentum/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "HIGH",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 8.1,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "1",
            "2",
            "3",
            "4",
            "5",
            "10",
            "15"
          ]
        }
      ],
      "title": "CVE-2023-6408"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Jianshuang Ding"
          ]
        }
      ],
      "cve": "CVE-2023-6409",
      "cwe": {
        "id": "CWE-798",
        "name": "Use of Hard-coded Credentials"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized\r\naccess to a project file protected with application password when opening the file with\r\nEcoStruxure Control Expert.",
          "title": "CVE Description"
        },
        {
          "category": "details",
          "text": "CVSS v4.0 Base Score 8.5 | High | [CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N)",
          "title": "CVSS v4.0 Score"
        }
      ],
      "product_status": {
        "fixed": [
          "8",
          "9"
        ],
        "known_affected": [
          "4",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "SV3.60 of Modicon M340 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/1468-\r\nmodicon-m340",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1468-modicon-m340"
        },
        {
          "category": "vendor_fix",
          "details": "SV4.20 of Modicon M580 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/62098-\r\nmodicon-m580-epac/ - software-and-firmware",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-%20modicon-m580-epac/%20-%20software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Version 16.0 of EcoStruxure Control Expert includes a fix\r\nfor these vulnerabilities and is available for download\r\nhere:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/\r\nReboot the computer after installation is completed",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/in/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "vendor_fix",
          "details": "Version 15.3 HF008 of EcoStruxure Control Expert\r\nincludes the fix for these vulnerabilities and are available\r\nfor download here:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M340 for Ethernet Communications Modules\r\nand Processors User Manual\u201d in chapter \u201cMessaging Configuration\r\nParameters\u201d:\r\nhttps://www.se.com/ww/en/download/document/31007131K01000/\r\n\u2022 Setup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M340 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\n\u2022 https://www.se.com/ww/en/download/document/EIO0000001999/",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/31007131K01000/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M580, Hardware, Reference Manual\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\nSetup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline \u201cModicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration\r\nGuide\u201d in the chapter \u201cConfiguring IPSEC communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter \u201cConfiguring the\r\nBMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580 Hot\r\nStandby CPUs. In such cases, use IPsec encrypted communication.",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric is establishing a remediation plan for all future versions\r\nof EcoStruxure\u2122 Process Expert that will include a fix for this vulnerability.\r\nWe will update this document when the remediation is available. Until then,\r\ncustomers should immediately apply the following mitigations to reduce the\r\nrisk of exploit:\r\n\u2022 Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M580, Hardware, Reference Manual\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\n\u2022 Setup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline \u201cModicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration Guide\u201d in the chapter \u201cConfiguring IPSEC communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter \u201cConfiguring the\r\nBMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580\r\nHot Standby CPUs. In such cases, use IPsec encrypted\r\ncommunication.\r\n\u2022 To further reduce the attack surface on Modicon M580 CPU\r\nSafety:\r\nEnsure the CPU is running in Safety mode and maintenance input is\r\nconfigured to maintain this Safety mode during operation \u2013 refer to\r\nthe document Modicon M580 - Safety System Planning Guide - in\r\nthe chapter \u201cOperating Mode Transitions\u201d:\r\nhttps://www.se.com/ww/en/download/document/QGH60283/ ",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Enable encryption on application project and store application files in\r\nsecure location with restricted access only for legitimate users.\r\n\u2022 Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n\u2022 Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        },
        {
          "category": "mitigation",
          "details": "EcoStruxure Process Expert manages application files within its\r\ndatabase in secure way. Do not export \u0026 store them outside the\r\napplication.\r\n\u2022 Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n\u2022 Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "NONE",
            "baseScore": 7.7,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "4",
            "5"
          ]
        }
      ],
      "title": "CVE-2023-6409"
    },
    {
      "acknowledgments": [
        {
          "names": [
            "Kaikai Yang"
          ]
        }
      ],
      "cve": "CVE-2023-27975",
      "cwe": {
        "id": "CWE-522",
        "name": "Insufficiently Protected Credentials"
      },
      "notes": [
        {
          "category": "description",
          "text": "A CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause\r\nunauthorized access to the project file in EcoStruxure\u2122 Control Expert when a local user\r\ntampers with the memory of the engineering workstation.",
          "title": "CVE Description"
        },
        {
          "category": "details",
          "text": "CVSS v4.0 Base Score 7.2 | High | [CVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N](https://www.first.org/cvss/calculator/4.0#CVSS:4.0/AV:L/AC:L/AT:P/PR:L/UI:N/VC:H/VI:H/VA:N/SC:N/SI:N/SA:N)",
          "title": "CVSS v4.0 Score"
        }
      ],
      "product_status": {
        "fixed": [
          "8",
          "9"
        ],
        "known_affected": [
          "4",
          "5"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "SV3.60 of Modicon M340 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/1468-\r\nmodicon-m340",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/1468-modicon-m340"
        },
        {
          "category": "vendor_fix",
          "details": "SV4.20 of Modicon M580 firmware includes a fix for this\r\nvulnerability and is available for download here:\r\nhttps://www.se.com/ww/en/product-range/62098-\r\nmodicon-m580-epac/ - software-and-firmware",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/62098-%20modicon-m580-epac/%20-%20software-and-firmware"
        },
        {
          "category": "vendor_fix",
          "details": "Version 16.0 of EcoStruxure Control Expert includes a fix\r\nfor these vulnerabilities and is available for download\r\nhere:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/\r\nReboot the computer after installation is completed",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "system"
          },
          "url": "https://www.se.com/in/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "vendor_fix",
          "details": "Version 15.3 HF008 of EcoStruxure Control Expert\r\nincludes the fix for these vulnerabilities and are available\r\nfor download here:\r\nhttps://www.se.com/ww/en/product-range/548-\r\necostruxure-control-expert-unity-pro/",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/product-range/548-ecostruxure-control-expert-unity-pro/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M340 for Ethernet Communications Modules\r\nand Processors User Manual\u201d in chapter \u201cMessaging Configuration\r\nParameters\u201d:\r\nhttps://www.se.com/ww/en/download/document/31007131K01000/\r\n\u2022 Setup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M340 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\n\u2022 https://www.se.com/ww/en/download/document/EIO0000001999/",
          "product_ids": [
            "1"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/31007131K01000/"
        },
        {
          "category": "mitigation",
          "details": "Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M580, Hardware, Reference Manual\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\nSetup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline \u201cModicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration\r\nGuide\u201d in the chapter \u201cConfiguring IPSEC communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter \u201cConfiguring the\r\nBMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580 Hot\r\nStandby CPUs. In such cases, use IPsec encrypted communication.",
          "product_ids": [
            "2"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric is establishing a remediation plan for all future versions\r\nof EcoStruxure\u2122 Process Expert that will include a fix for this vulnerability.\r\nWe will update this document when the remediation is available. Until then,\r\ncustomers should immediately apply the following mitigations to reduce the\r\nrisk of exploit:\r\n\u2022 Setup an application password in the project properties\r\n\u2022 Setup network segmentation and implement a firewall to block all\r\nunauthorized access to port 502/TCP\r\n\u2022 Configure the Access Control List following the recommendations of the\r\nuser manuals: \u201cModicon M580, Hardware, Reference Manual\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001578/\r\n\u2022 Setup a secure communication according to the following guideline\r\n\u201cModicon Controllers Platform Cyber Security Reference Manual,\u201d in\r\nchapter \u201cSetup secured communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 use a BMENOC module and follow the instructions to configure\r\nIPSEC feature as described in the guideline \u201cModicon M580 -\r\nBMENOC03.1 Ethernet Communications Schneider Electric\r\nSecurity Notification Module, Installation and Configuration Guide\u201d in the chapter \u201cConfiguring IPSEC communications\u201d:\r\nhttps://www.se.com/ww/en/download/document/HRB62665/\r\nOR\r\n\u2022 Use a BMENUA0100 module and follow the instructions to configure\r\nIPSEC feature as described in the chapter \u201cConfiguring the\r\nBMENUA0100 Cybersecurity Settings\u201d:\r\nhttps://www.se.com/ww/en/download/document/PHA83350\r\nOR\r\n\u2022 Consider use of external firewall devices such as EAGLE40-07 from\r\nBelden to establish VPN connections for M340 \u0026 M580 architectures.\r\nFor more details refer to the chapter \u201cHow to protect M580 and M340\r\narchitectures with EAGLE40 using VPN\u201d:\r\nhttps://www.se.com/ww/en/download/document/EIO0000001999/\r\n\u2022 Ensure the M580 CPU is running with the memory protection activated\r\nby configuring the input bit to a physical input, for more details refer to\r\nthe following guideline \u201cModicon Controllers Platform Cyber Security\r\nReference Manual\u201d, \u201cCPU Memory Protection section\u201d:\r\nhttps://www.schneiderelectric.com/en/download/document/EIO0000001999/\r\nNOTE: The CPU memory protection cannot be configured with M580\r\nHot Standby CPUs. In such cases, use IPsec encrypted\r\ncommunication.\r\n\u2022 To further reduce the attack surface on Modicon M580 CPU\r\nSafety:\r\nEnsure the CPU is running in Safety mode and maintenance input is\r\nconfigured to maintain this Safety mode during operation \u2013 refer to\r\nthe document Modicon M580 - Safety System Planning Guide - in\r\nthe chapter \u201cOperating Mode Transitions\u201d:\r\nhttps://www.se.com/ww/en/download/document/QGH60283/ ",
          "product_ids": [
            "3"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000001578/"
        },
        {
          "category": "mitigation",
          "details": "Enable encryption on application project and store application files in\r\nsecure location with restricted access only for legitimate users.\r\n\u2022 Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n\u2022 Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "4"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        },
        {
          "category": "mitigation",
          "details": "EcoStruxure Process Expert manages application files within its\r\ndatabase in secure way. Do not export \u0026 store them outside the\r\napplication.\r\n\u2022 Schneider Electric recommends using McAfee Application and Change\r\nControl software for application control. Refer to the Cybersecurity\r\nApplication Note available here.\r\n\u2022 Follow workstation, network and site-hardening guidelines in the\r\nRecommended Cybersecurity Best Practices available for download\r\nhere.",
          "product_ids": [
            "5"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/EIO0000004778/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "NONE",
            "baseScore": 7.1,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "LOW",
            "scope": "UNCHANGED",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:N",
            "version": "3.1"
          },
          "products": [
            "4",
            "5"
          ]
        }
      ],
      "title": "CVE-2023-27975"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.