ICSA-25-028-06

Vulnerability from csaf_cisa - Published: 2025-01-14 00:00 - Updated: 2026-01-29 07:00
Summary
Schneider Electric RemoteConnect and SCADAPack x70 Utilities (Update A)

Notes

General Security Recommendations
We strongly recommend the following industry cybersecurity best practices. https://www.se.com/us/en/download/document/7EN52-0390/ * Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network. * Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks. * Place all controllers in locked cabinets and never leave them in the “Program” mode. * Never connect programming software to any network other than the network intended for that device. * Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks. * Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation. * Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet. * When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices. For more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document.
For More Information
This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process. For further information related to cybersecurity in Schneider Electric’s products, visit the company’s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp
LEGAL DISCLAIMER
THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS “NOTIFICATION”) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN “AS-IS” BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND. SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION
About Schneider Electric
Schneider's purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and sustainability for all. We call this Life Is On. Our mission is to be the trusted partner in Sustainability and Efficiency. We are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart industries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep domain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation, software and services, delivering digital twins to enable profitable growth for our customers. We are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries to ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our meaningful purpose of a sustainable future for all. www.se.com
Overview
Schneider Electric is aware of a vulnerability in its RemoteConnect and SCADAPack™ x70 Utilities software product. The RemoteConnect and SCADAPack™ x70 Utilities https://www.se.com/ww/en/product-category/6000-telemetry-and-remote-scada-systems/ product is a configuration software providing a user interface that allows users to configure and manage communications and operations for SCADAPack™ x70 devices. Failure to apply the Mitigations provided below may risk deserialization of untrusted data, which could result in loss of confidentiality, integrity and potential remote code execution on the compromised workstation.
The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1 will be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without incorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as the presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer's environment.
Customers should use appropriate patching methodologies when applying these patches to their systems. We strongly recommend the use of back-ups and evaluating the impact of these patches in a Test and Development environment or on an offline infrastructure. Contact Schneider Electric’s Technical Support at supportRO@se.com if you need assistance.
Legal Notice and Terms of Use
This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy & Use policy (https://www.cisa.gov/privacy-policy).
Advisory Conversion Disclaimer
This ICSA is a verbatim republication of Schneider Electric CPCERT SEVD-2025-014-06 from a direct conversion of the vendor's Common Security Advisory Framework (CSAF) advisory. This is republished to CISA's website as a means of increasing visibility and is provided "as-is" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory. Further, CISA does not endorse any commercial product or service. Please contact Schneider Electric CPCERT directly for any questions regarding this advisory.
Critical infrastructure sectors
Energy, Critical Manufacturing
Countries/areas deployed
Worldwide
Company headquarters location
France
Recommended Practices
CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.
Recommended Practices
Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.
Recommended Practices
Locate control system networks and remote devices behind firewalls and isolate them from business networks.
Recommended Practices
When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.
Recommended Practices
CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.
Recommended Practices
Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

{
  "document": {
    "acknowledgments": [
      {
        "organization": "Schneider Electric CPCERT",
        "summary": "reported this vulnerability to CISA."
      }
    ],
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "text": "Disclosure is not limited",
      "tlp": {
        "label": "WHITE",
        "url": "https://www.cisa.gov/news-events/news/traffic-light-protocol-tlp-definitions-and-usage"
      }
    },
    "lang": "en-US",
    "notes": [
      {
        "category": "general",
        "text": "We strongly recommend the following industry cybersecurity best practices.\n\nhttps://www.se.com/us/en/download/document/7EN52-0390/\n* Locate control and safety system networks and remote devices behind firewalls and isolate them from the business network.\n* Install physical controls so no unauthorized personnel can access your industrial control and safety systems, components, peripheral equipment, and networks.\n* Place all controllers in locked cabinets and never leave them in the \u201cProgram\u201d mode.\n* Never connect programming software to any network other than the network intended for that device.\n* Scan all methods of mobile data exchange with the isolated network such as CDs, USB drives, etc. before use in the terminals or any node connected to these networks.\n* Never allow mobile devices that have connected to any other network besides the intended network to connect to the safety or control networks without proper sanitation.\n* Minimize network exposure for all control system devices and systems and ensure that they are not accessible from the Internet.\n* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs). Recognize that VPNs may have vulnerabilities and should be updated to the most current version available. Also, understand that VPNs are only as secure as the connected devices.\nFor more information refer to the Schneider Electric Recommended Cybersecurity Best Practices document. \n",
        "title": "General Security Recommendations"
      },
      {
        "category": "general",
        "text": "This document provides an overview of the identified vulnerability or vulnerabilities and actions required to mitigate. For more details and assistance on how to protect your installation, contact your local Schneider Electric representative or Schneider Electric Industrial Cybersecurity Services: https://www.se.com/ww/en/work/solutions/cybersecurity/. These organizations will be fully aware of this situation and can support you through the process.\nFor further information related to cybersecurity in Schneider Electric\u2019s products, visit the company\u2019s cybersecurity support portal page: https://www.se.com/ww/en/work/support/cybersecurity/overview.jsp",
        "title": "For More Information"
      },
      {
        "category": "legal_disclaimer",
        "text": "THIS NOTIFICATION DOCUMENT, THE INFORMATION CONTAINED HEREIN, AND ANY MATERIALS LINKED FROM IT (COLLECTIVELY, THIS \u201cNOTIFICATION\u201d) ARE INTENDED TO HELP PROVIDE AN OVERVIEW OF THE IDENTIFIED SITUATION AND SUGGESTED MITIGATION ACTIONS, REMEDIATION, FIX, AND/OR GENERAL SECURITY RECOMMENDATIONS AND IS PROVIDED ON AN \u201cAS-IS\u201d BASIS WITHOUT WARRANTY OR GUARANTEE OF ANY KIND.  SCHNEIDER ELECTRIC DISCLAIMS ALL WARRANTIES RELATING TO THIS NOTIFICATION, EITHER EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER ELECTRIC MAKES NO WARRANTY THAT THE NOTIFICATION WILL RESOLVE THE IDENTIFIED SITUATION. IN NO EVENT SHALL SCHNEIDER ELECTRIC BE LIABLE FOR ANY DAMAGES OR LOSSES WHATSOEVER IN CONNECTION WITH THIS NOTIFICATION, INCLUDING DIRECT, INDIRECT, INCIDENTAL, CONSEQUENTIAL, LOSS OF BUSINESS PROFITS OR SPECIAL DAMAGES, EVEN IF SCHNEIDER ELECTRIC HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. YOUR USE OF THIS NOTIFICATION IS AT YOUR OWN RISK, AND YOU ARE SOLELY LIABLE FOR ANY DAMAGES TO YOUR SYSTEMS OR ASSETS OR OTHER LOSSES THAT MAY RESULT FROM YOUR USE OF THIS NOTIFICATION. SCHNEIDER ELECTRIC RESERVES THE RIGHT TO UPDATE OR CHANGE THIS NOTIFICATION AT ANY TIME AND IN ITS SOLE DISCRETION",
        "title": "LEGAL DISCLAIMER"
      },
      {
        "category": "general",
        "text": "Schneider\u0027s purpose is to create Impact by empowering all to make the most of our energy and resources, bridging progress and\r\nsustainability for all. We call this Life Is On.\n\nOur mission is to be the trusted partner in Sustainability and Efficiency.\n\nWe are a global industrial technology leader bringing world-leading expertise in electrification, automation and digitization to smart\r\nindustries, resilient infrastructure, future-proof data centers, intelligent buildings, and intuitive homes. Anchored by our deep\r\ndomain expertise, we provide integrated end-to-end lifecycle AI enabled Industrial IoT solutions with connected products, automation,\r\nsoftware and services, delivering digital twins to enable profitable growth for our customers.\n\nWe are a people company with an ecosystem of 150,000 colleagues and more than a million partners operating in over 100 countries\r\nto ensure proximity to our customers and stakeholders. We embrace diversity and inclusion in everything we do, guided by our\r\nmeaningful purpose of a sustainable future for all. \n\n www.se.com",
        "title": "About Schneider Electric"
      },
      {
        "category": "summary",
        "text": "Schneider Electric is aware of a vulnerability in its RemoteConnect and SCADAPack\u2122 x70 Utilities software \r\nproduct. \r\nThe RemoteConnect and SCADAPack\u2122 x70 Utilities https://www.se.com/ww/en/product-category/6000-telemetry-and-remote-scada-systems/  product is a configuration software providing a user \r\ninterface that allows users to configure and manage communications and operations for SCADAPack\u2122 x70 \r\ndevices. \r\nFailure to apply the Mitigations provided below may risk deserialization of untrusted data, which could result in \r\nloss of confidentiality, integrity and potential remote code execution on the compromised workstation.",
        "title": "Overview"
      },
      {
        "category": "other",
        "text": "The severity of vulnerabilities was calculated using the CVSS Base metrics for 4.0 ([CVSS v4.0](https://www.first.org/cvss/calculator/4.0)). CVSS v3.1 \nwill be still evaluated until the adoption of CVSS v4.0 by the industry. The severity was calculated without \nincorporating the Temporal and Environmental metrics. Schneider Electric recommends that customers score the CVSS Environmental metrics, which are specific to end-user organizations, and consider factors such as \nthe presence of mitigations in that environment. Environmental metrics may refine the relative severity posed by the vulnerabilities described in this document within a customer\u0027s environment."
      },
      {
        "category": "other",
        "text": "Customers should use appropriate patching methodologies when applying these patches to their systems. We \nstrongly recommend the use of back-ups and evaluating the impact of these patches in a Test and \nDevelopment environment or on an offline infrastructure. Contact Schneider Electric\u2019s Technical Support at \nsupportRO@se.com if you need assistance. "
      },
      {
        "category": "legal_disclaimer",
        "text": "This product is provided subject to this Notification (https://www.cisa.gov/notification) and this Privacy \u0026 Use policy (https://www.cisa.gov/privacy-policy).",
        "title": "Legal Notice and Terms of Use"
      },
      {
        "category": "other",
        "text": "This ICSA is a verbatim republication of Schneider Electric CPCERT SEVD-2025-014-06 from a direct conversion of the vendor\u0027s Common Security Advisory Framework (CSAF) advisory. This is republished to CISA\u0027s website as a means of increasing visibility and is provided \"as-is\" for informational purposes only. CISA is not responsible for the editorial or technical accuracy of republished advisories and provides no warranties of any kind regarding any information contained within this advisory.  Further, CISA does not endorse any commercial product or service.  Please contact Schneider Electric CPCERT directly for any questions regarding this advisory.",
        "title": "Advisory Conversion Disclaimer"
      },
      {
        "category": "other",
        "text": "Energy, Critical Manufacturing",
        "title": "Critical infrastructure sectors"
      },
      {
        "category": "other",
        "text": "Worldwide",
        "title": "Countries/areas deployed"
      },
      {
        "category": "other",
        "text": "France",
        "title": "Company headquarters location"
      },
      {
        "category": "general",
        "text": "CISA recommends users take defensive measures to minimize the exploitation risk of these vulnerabilities.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Minimize network exposure for all control system devices and/or systems, and ensure they are not accessible from the internet.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Locate control system networks and remote devices behind firewalls and isolate them from business networks.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most recent version available. Also recognize VPN is only as secure as its connected devices.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets. Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies.",
        "title": "Recommended Practices"
      },
      {
        "category": "general",
        "text": "Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.",
        "title": "Recommended Practices"
      }
    ],
    "publisher": {
      "category": "other",
      "contact_details": "central@cisa.dhs.gov",
      "name": "CISA",
      "namespace": "https://www.cisa.gov/"
    },
    "references": [
      {
        "category": "self",
        "summary": "RemoteConnect and SCADAPack\u2122 x70 Utilities - SEVD-2025-014-06 CSAF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-014-06\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=sevd-2025-014-06.json"
      },
      {
        "category": "self",
        "summary": "RemoteConnect and SCADAPack\u2122 x70 Utilities - SEVD-2025-014-06 PDF Version",
        "url": "https://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2025-014-06\u0026p_enDocType=Security+and+Safety+Notice\u0026p_File_Name=SEVD-2025-014-06.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Cybersecurity Best Practices",
        "url": "https://www.se.com/us/en/download/document/7EN52-0390"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-25-028-06 JSON",
        "url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2025/icsa-25-028-06.json"
      },
      {
        "category": "self",
        "summary": "ICS Advisory ICSA-25-028-06 - Web Version",
        "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-028-06"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/ics-alerts/ics-alert-10-301-01"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/resources-tools/resources/ics-recommended-practices"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/topics/industrial-control-systems"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-CERT_Defense_in_Depth_2016_S508C.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/sites/default/files/publications/Cybersecurity_Best_Practices_for_Industrial_Control_Systems.pdf"
      },
      {
        "category": "external",
        "summary": "Recommended Practices",
        "url": "https://www.cisa.gov/news-events/news/targeted-cyber-intrusion-detection-and-mitigation-strategies-update-b"
      }
    ],
    "title": "Schneider Electric RemoteConnect and SCADAPack x70 Utilities (Update A)",
    "tracking": {
      "current_release_date": "2026-01-29T07:00:00.000000Z",
      "generator": {
        "date": "2026-02-02T23:02:18.932180Z",
        "engine": {
          "name": "CISA CSAF Generator",
          "version": "1.5.0"
        }
      },
      "id": "ICSA-25-028-06",
      "initial_release_date": "2025-01-14T00:00:00.000000Z",
      "revision_history": [
        {
          "date": "2025-01-14T00:00:00.000000Z",
          "legacy_version": "Initial",
          "number": "1",
          "summary": "Original Release"
        },
        {
          "date": "2025-01-28T07:00:00.000000Z",
          "legacy_version": "Additional Release 1",
          "number": "2",
          "summary": "Initial Publication"
        },
        {
          "date": "2026-01-13T08:00:00.000000Z",
          "legacy_version": "Additional Release 2",
          "number": "3",
          "summary": "The affected versions for the RemoteConnect and Security Administrator has been identified, and a remediation is now available for the RemoteConnect configuration software included in the RemoteConnect and SCADAPack\u2122 x70 Utilities product bundle."
        },
        {
          "date": "2026-01-29T07:00:00.000000Z",
          "legacy_version": "Latest Updated CISA Republication",
          "number": "4",
          "summary": "CISA Republication update based on Schneider Electric CPCERT SEVD-2025-014-06 advisory"
        }
      ],
      "status": "final",
      "version": "4"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:generic/\u003cR3.4.2",
                "product": {
                  "name": "RemoteConnect and SCADAPack\u2122 x70 Utilities - RemoteConnect versions prior to R3.4.2",
                  "product_id": "CSAFPID-0001"
                }
              }
            ],
            "category": "product_name",
            "name": "RemoteConnect and SCADAPack\u2122 x70 Utilities - RemoteConnect"
          },
          {
            "branches": [
              {
                "category": "product_version_range",
                "name": "vers:all/*",
                "product": {
                  "name": "RemoteConnect and SCADAPack\u2122 x70 Utilities - Security Administrator All Versions",
                  "product_id": "CSAFPID-0002"
                }
              }
            ],
            "category": "product_name",
            "name": "RemoteConnect and SCADAPack\u2122 x70 Utilities - Security Administrator"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "R3.4.2",
                "product": {
                  "name": "RemoteConnect configuration software version R3.4.2",
                  "product_id": "CSAFPID-0003"
                }
              }
            ],
            "category": "product_name",
            "name": "RemoteConnect configuration software"
          }
        ],
        "category": "vendor",
        "name": "Schneider Electric"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2024-12703",
      "cwe": {
        "id": "CWE-502",
        "name": "Deserialization of Untrusted Data"
      },
      "notes": [
        {
          "category": "description",
          "text": "CWE-502: Deserialization of untrusted data vulnerability exists that could lead to loss of confidentiality, integrity\r\nand potential remote code execution on workstation when a non-admin authenticated user opens a malicious \r\nproject file.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "CSAFPID-0003"
        ],
        "known_affected": [
          "CSAFPID-0001",
          "CSAFPID-0002"
        ]
      },
      "references": [
        {
          "category": "external",
          "summary": "www.cve.org",
          "url": "https://www.cve.org/CVERecord?id=CVE-2024-12703"
        },
        {
          "category": "external",
          "summary": "cwe.mitre.org",
          "url": "https://cwe.mitre.org/data/definitions/502.html"
        },
        {
          "category": "external",
          "summary": "www.first.org",
          "url": "https://www.first.org/cvss/calculator/3.1#CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H"
        }
      ],
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Version R3.4.2 RemoteConnect configuration software includes a fix for this vulnerability and is available for download here:https://www.se.com/ww/en/download/document/RemoteConnect/",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/RemoteConnect/"
        },
        {
          "category": "mitigation",
          "details": "If customers choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit: Schneider Electric is establishing a remediation plan for all future versions of Security Administrator configuration software that will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit:\u2022 Only open project files received from a trusted source. \u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage.\u2022 Encrypt project file when stored and restrict the access to only trusted users. \u2022 When exchanging files over the network, use secure communication protocols. \u2022 Follow the SCADAPack\u2122 Security Guidelines",
          "product_ids": [
            "CSAFPID-0001"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/SCADAPack_Cybersecurity_Guide/"
        },
        {
          "category": "mitigation",
          "details": "Schneider Electric is establishing a remediation plan for all future versions of Security Administrator configuration software that will include a fix for this vulnerability. We will update this document when the remediation is available. Until then, customers should immediately apply the following mitigations to reduce the risk of exploit:\u2022 Only open project files received from a trusted source. \u2022 Compute a hash of the project files and regularly check the consistency of this hash to verify the integrity before usage.\u2022 Encrypt project file when stored and restrict the access to only trusted users. \u2022 When exchanging files over the network, use secure communication protocols. \u2022 Follow the SCADAPack\u2122 Security Guidelines",
          "product_ids": [
            "CSAFPID-0002"
          ],
          "restart_required": {
            "category": "none"
          },
          "url": "https://www.se.com/ww/en/download/document/SCADAPack_Cybersecurity_Guide/"
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "LOCAL",
            "availabilityImpact": "HIGH",
            "baseScore": 7.8,
            "baseSeverity": "HIGH",
            "confidentialityImpact": "HIGH",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "userInteraction": "REQUIRED",
            "vectorString": "CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-0001",
            "CSAFPID-0002"
          ]
        }
      ],
      "title": "CVE-2024-12703"
    }
  ]
}


Log in or create an account to share your comment.




Tags
Taxonomy of the tags.


Loading…

Loading…

Loading…

Sightings

Author Source Type Date

Nomenclature

  • Seen: The vulnerability was mentioned, discussed, or observed by the user.
  • Confirmed: The vulnerability has been validated from an analyst's perspective.
  • Published Proof of Concept: A public proof of concept is available for this vulnerability.
  • Exploited: The vulnerability was observed as exploited by the user who reported the sighting.
  • Patched: The vulnerability was observed as successfully patched by the user who reported the sighting.
  • Not exploited: The vulnerability was not observed as exploited by the user who reported the sighting.
  • Not confirmed: The user expressed doubt about the validity of the vulnerability.
  • Not patched: The vulnerability was not observed as successfully patched by the user who reported the sighting.


Loading…

Detection rules are retrieved from Rulezet.

Loading…

Loading…