icsa-17-101-01
Vulnerability from csaf_cisa
Published
2017-04-11 00:00
Modified
2017-04-11 00:00
Summary
Schneider Electric Modicon Modbus Protocol
Notes
CISA Disclaimer
This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov
Legal Notice
All information products included in https://us-cert.cisa.gov/ics are provided "as is" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.
Risk evaluation
ATTENTION: Remotely exploitable/low skill level to exploit.
Critical infrastructure sectors
Critical Manufacturing, Dams, Defense Industrial Base, Energy, Food and Agriculture, Government Facilities, Nuclear Reactors, Materials, and Waste, Transportation Systems, and Water and Wastewater Systems
Countries/areas deployed
Worldwide
Company headquarters location
Paris, France
Recommended Practices
NCCIC/ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:
Recommended Practices
ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.
Recommended Practices
ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.
Recommended Practices
Additional mitigation guidance and recommended practices are publicly available in the ICS -CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.
Recommended Practices
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
{
"document": {
"acknowledgments": [
{
"names": [
"Eran Goldstein"
],
"organization": "CRITIFENCE",
"summary": "reporting the identified vulnerabilities"
}
],
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited",
"tlp": {
"label": "WHITE",
"url": "https://us-cert.cisa.gov/tlp/"
}
},
"lang": "en-US",
"notes": [
{
"category": "general",
"text": "This CSAF advisory was extracted from unstructured data and may contain inaccuracies. If you notice any errors, please reach out to the designated contact at CISA CSAF: central@cisa.dhs.gov",
"title": "CISA Disclaimer"
},
{
"category": "legal_disclaimer",
"text": "All information products included in https://us-cert.cisa.gov/ics are provided \"as is\" for informational purposes only. The Department of Homeland Security (DHS) does not provide any warranties of any kind regarding any information contained within. DHS does not endorse any commercial product or service, referenced in this product or otherwise. Further dissemination of this product is governed by the Traffic Light Protocol (TLP) marking in the header. For more information about TLP, see https://us-cert.cisa.gov/tlp/.",
"title": "Legal Notice"
},
{
"category": "summary",
"text": "ATTENTION: Remotely exploitable/low skill level to exploit.",
"title": "Risk evaluation"
},
{
"category": "other",
"text": "Critical Manufacturing, Dams, Defense Industrial Base, Energy, Food and Agriculture, Government Facilities, Nuclear Reactors, Materials, and Waste, Transportation Systems, and Water and Wastewater Systems",
"title": "Critical infrastructure sectors"
},
{
"category": "other",
"text": "Worldwide",
"title": "Countries/areas deployed"
},
{
"category": "other",
"text": "Paris, France",
"title": "Company headquarters location"
},
{
"category": "general",
"text": "NCCIC/ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of these vulnerabilities. Specifically, users should:",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Additional mitigation guidance and recommended practices are publicly available in the ICS -CERT Technical Information Paper, ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.",
"title": "Recommended Practices"
},
{
"category": "general",
"text": "Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.",
"title": "Recommended Practices"
}
],
"publisher": {
"category": "coordinator",
"contact_details": "Email: CISAservicedesk@cisa.dhs.gov;\n Toll Free: 1-888-282-0870",
"name": "CISA",
"namespace": "https://www.cisa.gov/"
},
"references": [
{
"category": "self",
"summary": "ICS Advisory ICSA-17-101-01 JSON",
"url": "https://raw.githubusercontent.com/cisagov/CSAF/develop/csaf_files/OT/white/2017/icsa-17-101-01.json"
},
{
"category": "self",
"summary": "ICS Advisory ICSA-17-101-01 Web Version",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-17-101-01"
},
{
"category": "external",
"summary": "Recommended Practices",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-17-101-01"
}
],
"title": "Schneider Electric Modicon Modbus Protocol",
"tracking": {
"current_release_date": "2017-04-11T00:00:00.000000Z",
"generator": {
"engine": {
"name": "CISA CSAF Generator",
"version": "1.0.0"
}
},
"id": "ICSA-17-101-01",
"initial_release_date": "2017-04-11T00:00:00.000000Z",
"revision_history": [
{
"date": "2017-04-11T00:00:00.000000Z",
"legacy_version": "Initial",
"number": "1",
"summary": "ICSA-17-101-01 Schneider Electric Modicon Modbus Protocol"
}
],
"status": "final",
"version": "1"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version",
"name": "vers:all/*",
"product": {
"name": "Modicon Modbus protocol: all versions",
"product_id": "CSAFPID-0001"
}
}
],
"category": "product_name",
"name": "Modicon Modbus protocol"
}
],
"category": "vendor",
"name": "Schneider Electric Software, LLC"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2017-6034",
"cwe": {
"id": "CWE-294",
"name": "Authentication Bypass by Capture-replay"
},
"notes": [
{
"category": "summary",
"text": "Sensitive information is transmitted in cleartext in the Modicon Modbus protocol, which may allow an attacker to replay the following commands: run, stop, upload, and download.CVE-2017-6034 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H)",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-6034"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Schneider Electric has reported that they have introduced compensating controls to limit the exploitability of the identified vulnerabilities in many of the PLCs in the Modicon family; however, Schneider Electric recommends that users apply security measures to improve resiliency.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Schneider Electric\u0027s Momentum M1E controllers (all versions of model 171CBU98090 and all versions of model 171CBU98091) do not have built-in compensating controls to limit the exploitability of the identified vulnerabilities ",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Protect access to M1E controllers by a firewall blocking all remote/external access to Port 502.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Enable protection based on an authentication to connect to PLC. This method relies on a feature named Application Password. Once enabled, password-based authentication is required whenever a user connects to change their application program",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Enable protection relying on an input (M340, Premium, Quantum) or a key switch in the front panel (Quantum) to reject remote connection or run/stop commands",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Enable the \u201cAccess Control List protection,\u201d where users are able to configure the restricted IP addresses that are pre-authorized to control the PLC.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "For additional information, Schneider Electric has released a Cybersecurity Notification",
"product_ids": [
"CSAFPID-0001"
],
"url": "http://www.schneider-electric.com/en/download/document/SEVD-2017-065-01/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 10.0,
"baseSeverity": "CRITICAL",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H",
"version": "3.0"
},
"products": [
"CSAFPID-0001"
]
}
]
},
{
"cve": "CVE-2017-6032",
"cwe": {
"id": "CWE-657",
"name": "Violation of Secure Design Principles"
},
"notes": [
{
"category": "summary",
"text": "The Modicon Modbus protocol has a session-related weakness making it susceptible to brute-force attacks.CVE-2017-6032 has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N).",
"title": "Vulnerability Summary"
}
],
"product_status": {
"known_affected": [
"CSAFPID-0001"
]
},
"references": [
{
"category": "external",
"summary": "web.nvd.nist.gov",
"url": "http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-6032"
},
{
"category": "external",
"summary": "www.first.org",
"url": "https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N"
}
],
"remediations": [
{
"category": "mitigation",
"details": "Schneider Electric has reported that they have introduced compensating controls to limit the exploitability of the identified vulnerabilities in many of the PLCs in the Modicon family; however, Schneider Electric recommends that users apply security measures to improve resiliency.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Schneider Electric\u0027s Momentum M1E controllers (all versions of model 171CBU98090 and all versions of model 171CBU98091) do not have built-in compensating controls to limit the exploitability of the identified vulnerabilities ",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Protect access to M1E controllers by a firewall blocking all remote/external access to Port 502.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Enable protection based on an authentication to connect to PLC. This method relies on a feature named Application Password. Once enabled, password-based authentication is required whenever a user connects to change their application program",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Enable protection relying on an input (M340, Premium, Quantum) or a key switch in the front panel (Quantum) to reject remote connection or run/stop commands",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "Enable the \u201cAccess Control List protection,\u201d where users are able to configure the restricted IP addresses that are pre-authorized to control the PLC.",
"product_ids": [
"CSAFPID-0001"
]
},
{
"category": "mitigation",
"details": "For additional information, Schneider Electric has released a Cybersecurity Notification",
"product_ids": [
"CSAFPID-0001"
],
"url": "http://www.schneider-electric.com/en/download/document/SEVD-2017-065-01/"
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
"version": "3.0"
},
"products": [
"CSAFPID-0001"
]
}
]
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.