fkie_cve-2012-6442
Vulnerability from fkie_nvd
Published
2013-01-24 21:55
Modified
2025-06-30 22:15
Severity ?
Summary
When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the product to reset, a DoS can occur. This situation could cause loss of availability and a disruption of communication with other connected devices.
Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400
References
Impacted products
{
"configurations": [
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:rockwellautomation:ethernet\\/ip_firmware:-:*:*:*:*:*:*:*",
"matchCriteriaId": "073A26FB-39D2-4771-9277-B0FA21088924",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:rockwellautomation:1756-enbt:-:*:*:*:*:*:*:*",
"matchCriteriaId": "330E9A05-C869-41B1-BB28-FD2A7C7ED0CE",
"vulnerable": false
},
{
"criteria": "cpe:2.3:h:rockwellautomation:1756-eweb:-:*:*:*:*:*:*:*",
"matchCriteriaId": "2AD7D5DB-4A49-421A-8C6C-B9E6DA0A499B",
"vulnerable": false
},
{
"criteria": "cpe:2.3:h:rockwellautomation:1768-enbt:-:*:*:*:*:*:*:*",
"matchCriteriaId": "DD44B55C-BDD7-41CC-91A9-F31ED2FC69E2",
"vulnerable": false
},
{
"criteria": "cpe:2.3:h:rockwellautomation:1768-eweb:-:*:*:*:*:*:*:*",
"matchCriteriaId": "C91D5245-DED2-469C-A800-62109F8159C9",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:rockwellautomation:compactlogix_firmware:-:*:*:*:*:*:*:*",
"matchCriteriaId": "F56D3970-D62A-4D79-976C-A213532969C9",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:rockwellautomation:l32e:-:*:*:*:*:*:*:*",
"matchCriteriaId": "8C10816B-573D-49F1-AE34-CBC7FA47161F",
"vulnerable": false
},
{
"criteria": "cpe:2.3:h:rockwellautomation:l35e:-:*:*:*:*:*:*:*",
"matchCriteriaId": "62343222-0FAA-41B0-902C-CCFDD931211C",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:rockwellautomation:flexlogix_firmware:-:*:*:*:*:*:*:*",
"matchCriteriaId": "3AB205EC-6543-4F4D-A8DA-4B4374238C3B",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:rockwellautomation:1788-enbt:-:*:*:*:*:*:*:*",
"matchCriteriaId": "E5118BE5-1FBD-4A62-9B38-98CC0DE40649",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:rockwellautomation:flex_i\\/o_ethernet\\/ip__firmware:-:*:*:*:*:*:*:*",
"matchCriteriaId": "6802A420-A771-4FE8-A9CE-64EA3760B968",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:rockwellautomation:1794-aentr:-:*:*:*:*:*:*:*",
"matchCriteriaId": "707E2529-484B-42CC-B981-FDE323FDAF2A",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:rockwellautomation:micrologix_firmware:-:*:*:*:*:*:*:*",
"matchCriteriaId": "130E4BE6-373D-4CF4-AC04-106784EAE137",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
},
{
"cpeMatch": [
{
"criteria": "cpe:2.3:h:rockwellautomation:1100:-:*:*:*:*:*:*:*",
"matchCriteriaId": "5B5051E4-D45E-4879-ADBF-CF048591BA96",
"vulnerable": false
},
{
"criteria": "cpe:2.3:h:rockwellautomation:1400:-:*:*:*:*:*:*:*",
"matchCriteriaId": "B8153C27-B429-4A55-9CED-B6D81F55BC3C",
"vulnerable": false
}
],
"negate": false,
"operator": "OR"
}
],
"operator": "AND"
},
{
"nodes": [
{
"cpeMatch": [
{
"criteria": "cpe:2.3:o:rockwellautomation:compactlogix_controllers_firmware:19:*:*:*:*:*:*:*",
"matchCriteriaId": "E85B0C4C-5299-4C48-B06B-30E13A9DAFAB",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:rockwellautomation:compactlogix_firmware:18:*:*:*:*:*:*:*",
"matchCriteriaId": "0836F9A5-6487-4702-9D61-C85D5ADAC0C8",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:rockwellautomation:controllogix_controllers_firmware:20:*:*:*:*:*:*:*",
"matchCriteriaId": "7F9D7324-931A-4E46-8128-045C2C6C7E67",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:rockwellautomation:controllogix_firmware:18:*:*:*:*:*:*:*",
"matchCriteriaId": "4749D825-0323-40ED-9C26-5BB4886B487E",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:rockwellautomation:guardlogix_controllers_firmware:20:*:*:*:*:*:*:*",
"matchCriteriaId": "9DC8BA80-3E6B-402C-9984-CC3D9CD082CC",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:rockwellautomation:guardlogix_firmware:18:*:*:*:*:*:*:*",
"matchCriteriaId": "29CA9FBB-DBDF-40ED-9583-8D619A377AA0",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:rockwellautomation:softlogix_controllers_firmware:19:*:*:*:*:*:*:*",
"matchCriteriaId": "BDBCE43A-0173-4A57-918C-5958782F4958",
"vulnerable": true
},
{
"criteria": "cpe:2.3:o:rockwellautomation:softlogix_firmware:18:*:*:*:*:*:*:*",
"matchCriteriaId": "33067DAD-1A7B-4A89-A726-05BAA9CFD023",
"vulnerable": true
}
],
"negate": false,
"operator": "OR"
}
]
}
],
"cveTags": [],
"descriptions": [
{
"lang": "en",
"value": "When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the product to reset, a DoS can occur. This situation could cause loss of availability and a disruption of communication with other connected devices.\n\n\n\nRockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400"
},
{
"lang": "es",
"value": "Los productos Rockwell Automation EtherNet/IP: 1756-ENBT, 1756-EWEB, 1768-ENBT, y los m\u00f3dulos de comunicaci\u00f3n 1768-EWEB; CompactLogix L32E y controladores L35E; adaptador 1788-ENBT FLEXLogix; adaptador 1794-AENTR FLEX I/O EtherNet/IP; ControlLogix 18 y anteriores; CompactLogix 18 y anteriores; GuardLogix 18 y anteriores; SoftLogix 18 y anteriores; controladores CompactLogix 19 y anteriores; controladores SoftLogix 19 y anteriores; controladores ControlLogix 20 y anteriores; controladores GuardLogix 20 y anteriores; y MicroLogix 1100 y 1400 permiten a atacantes remotos causar una denegaci\u00f3n de servicio (control y corte de la comunicaci\u00f3n) a trav\u00e9s de un mensaje CIP que especifica un reinicio."
}
],
"id": "CVE-2012-6442",
"lastModified": "2025-06-30T22:15:29.587",
"metrics": {
"cvssMetricV2": [
{
"acInsufInfo": false,
"baseSeverity": "HIGH",
"cvssData": {
"accessComplexity": "LOW",
"accessVector": "NETWORK",
"authentication": "NONE",
"availabilityImpact": "COMPLETE",
"baseScore": 7.8,
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:C",
"version": "2.0"
},
"exploitabilityScore": 10.0,
"impactScore": 6.9,
"obtainAllPrivilege": false,
"obtainOtherPrivilege": false,
"obtainUserPrivilege": false,
"source": "ics-cert@hq.dhs.gov",
"type": "Secondary",
"userInteractionRequired": false
},
{
"acInsufInfo": false,
"baseSeverity": "HIGH",
"cvssData": {
"accessComplexity": "LOW",
"accessVector": "NETWORK",
"authentication": "NONE",
"availabilityImpact": "COMPLETE",
"baseScore": 7.8,
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:C",
"version": "2.0"
},
"exploitabilityScore": 10.0,
"impactScore": 6.9,
"obtainAllPrivilege": false,
"obtainOtherPrivilege": false,
"obtainUserPrivilege": false,
"source": "nvd@nist.gov",
"type": "Primary",
"userInteractionRequired": false
}
]
},
"published": "2013-01-24T21:55:01.773",
"references": [
{
"source": "ics-cert@hq.dhs.gov",
"url": "http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102"
},
{
"source": "ics-cert@hq.dhs.gov",
"url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/470154"
},
{
"source": "ics-cert@hq.dhs.gov",
"url": "https://rockwellautomation.custhelp.com/app/answers/detail/aid/470155"
},
{
"source": "ics-cert@hq.dhs.gov",
"url": "https://rockwellautomation.custhelp.com/app/answers/detail/aid/470156"
},
{
"source": "ics-cert@hq.dhs.gov",
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-13-011-03"
},
{
"source": "nvd@nist.gov",
"tags": [
"Third Party Advisory"
],
"url": "https://tools.cisco.com/security/center/viewAlert.x?alertId=27862"
},
{
"source": "af854a3a-2127-422b-91ae-364da2661108",
"tags": [
"Broken Link",
"Third Party Advisory",
"US Government Resource"
],
"url": "http://www.us-cert.gov/control_systems/pdf/ICSA-13-011-03.pdf"
}
],
"sourceIdentifier": "ics-cert@hq.dhs.gov",
"vulnStatus": "Deferred",
"weaknesses": [
{
"description": [
{
"lang": "en",
"value": "CWE-284"
}
],
"source": "ics-cert@hq.dhs.gov",
"type": "Primary"
},
{
"description": [
{
"lang": "en",
"value": "CWE-119"
}
],
"source": "nvd@nist.gov",
"type": "Secondary"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…