SSA-673996
Vulnerability from csaf_siemens
Published
2024-09-10 00:00
Modified
2025-05-13 00:00
Summary
SSA-673996: Buffer Overflow Vulnerability in Third-Party Component in SICAM and SITIPE Products
Notes
Summary
Multiple SICAM products are affected by buffer overflow vulnerability in the IEC 61850 Client libraries from Triangle MicroWorks that could allow an unauthenticated remote attacker to create a denial of service condition by sending specially crafted MMS messages.
Affected SICAM and SITIPE products:
-
SICAM A8000 Device firmware
- ET85 for CP-8000/CP-8021/CP-8022
- ETI5 for CP-8031/CP-8050
-
SICAM EGS Device firmware
- ETI5
-
SICAM S8000
- ETI5
-
SICAM SCC
- SITIPE AT
Siemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is preparing further fix versions and recommends countermeasures for products where fixes are not, or not yet available.
General Recommendations
Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid's reliability can thus be minimized by virtue of the grid design.
Siemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment.
As a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.
Recommended security guidelines can be found at:
https://www.siemens.com/gridsecurity
Additional Resources
For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories
Terms of Use
The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.
{
"document": {
"category": "csaf_security_advisory",
"csaf_version": "2.0",
"distribution": {
"text": "Disclosure is not limited. (TLPv2: TLP:CLEAR)",
"tlp": {
"label": "WHITE"
}
},
"lang": "en",
"notes": [
{
"category": "summary",
"text": "Multiple SICAM products are affected by buffer overflow vulnerability in the IEC 61850 Client libraries from Triangle MicroWorks that could allow an unauthenticated remote attacker to create a denial of service condition by sending specially crafted MMS messages.\n\nAffected SICAM and SITIPE products:\n\n- \nSICAM A8000 Device firmware \n\n- ET85 for CP-8000/CP-8021/CP-8022\n- ETI5 for CP-8031/CP-8050\n\n\n- \nSICAM EGS Device firmware \n\n- ETI5\n\n\n- \nSICAM S8000\n\n- ETI5 \n\n\n- \nSICAM SCC\n\n\n- SITIPE AT\n\nSiemens has released new versions for several affected products and recommends to update to the latest versions. Siemens is preparing further fix versions and recommends countermeasures for products where fixes are not, or not yet available.",
"title": "Summary"
},
{
"category": "general",
"text": "Operators of critical power systems (e.g. TSOs or DSOs) worldwide are usually required by regulations to build resilience into the power grids by applying multi-level redundant secondary protection schemes. It is therefore recommended that the operators check whether appropriate resilient protection measures are in place. The risk of cyber incidents impacting the grid\u0027s reliability can thus be minimized by virtue of the grid design.\nSiemens strongly recommends applying the provided security updates using the corresponding tooling and documented procedures made available with the product. If supported by the product, an automated means to apply the security updates across multiple product instances may be used. Siemens strongly recommends prior validation of any security update before being applied, and supervision by trained staff of the update process in the target environment. \nAs a general security measure Siemens strongly recommends to protect network access with appropriate mechanisms (e.g. firewalls, segmentation, VPN). It is advised to configure the environment according to our operational guidelines in order to run the devices in a protected IT environment.\n\nRecommended security guidelines can be found at:\n\nhttps://www.siemens.com/gridsecurity",
"title": "General Recommendations"
},
{
"category": "general",
"text": "For further inquiries on security vulnerabilities in Siemens products and solutions, please contact the Siemens ProductCERT: https://www.siemens.com/cert/advisories",
"title": "Additional Resources"
},
{
"category": "legal_disclaimer",
"text": "The use of Siemens Security Advisories is subject to the terms and conditions listed on: https://www.siemens.com/productcert/terms-of-use.",
"title": "Terms of Use"
}
],
"publisher": {
"category": "vendor",
"contact_details": "productcert@siemens.com",
"name": "Siemens ProductCERT",
"namespace": "https://www.siemens.com"
},
"references": [
{
"category": "self",
"summary": "SSA-673996: Buffer Overflow Vulnerability in Third-Party Component in SICAM and SITIPE Products - HTML Version",
"url": "https://cert-portal.siemens.com/productcert/html/ssa-673996.html"
},
{
"category": "self",
"summary": "SSA-673996: Buffer Overflow Vulnerability in Third-Party Component in SICAM and SITIPE Products - CSAF Version",
"url": "https://cert-portal.siemens.com/productcert/csaf/ssa-673996.json"
}
],
"title": "SSA-673996: Buffer Overflow Vulnerability in Third-Party Component in SICAM and SITIPE Products",
"tracking": {
"current_release_date": "2025-05-13T00:00:00Z",
"generator": {
"engine": {
"name": "Siemens ProductCERT CSAF Generator",
"version": "1"
}
},
"id": "SSA-673996",
"initial_release_date": "2024-09-10T00:00:00Z",
"revision_history": [
{
"date": "2024-09-10T00:00:00Z",
"legacy_version": "1.0",
"number": "1",
"summary": "Publication Date"
},
{
"date": "2024-12-10T00:00:00Z",
"legacy_version": "1.1",
"number": "2",
"summary": "Changed fix version for SICAM SCC from V10.0 to V9.14 HF2, which is now also released; Added ET85 for SICAM A8000 CP-8000/CP-8021/CP-8022 as affected product; Updated CVE data from meanwhile published official source (https://cveawg.mitre.org/api/cve/CVE-2024-34057)"
},
{
"date": "2025-05-13T00:00:00Z",
"legacy_version": "1.2",
"number": "3",
"summary": "Added fix for SITIPE AT and updated product name of \"SICAM 8 Software Solution\" to \"SICAM S8000\""
}
],
"status": "interim",
"version": "3"
}
},
"product_tree": {
"branches": [
{
"branches": [
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/*",
"product": {
"name": "ET85 Ethernet Interface IEC61850 Ed.2",
"product_id": "1"
}
}
],
"category": "product_name",
"name": "ET85 Ethernet Interface IEC61850 Ed.2"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/\u003cV05.30",
"product": {
"name": "ETI5 Ethernet Int. 1x100TX IEC61850",
"product_id": "2"
}
}
],
"category": "product_name",
"name": "ETI5 Ethernet Int. 1x100TX IEC61850"
},
{
"branches": [
{
"category": "product_version_range",
"name": "All versions \u003c V9.14 HF2",
"product": {
"name": "SICAM SCC",
"product_id": "3"
}
}
],
"category": "product_name",
"name": "SICAM SCC"
},
{
"branches": [
{
"category": "product_version_range",
"name": "vers:all/\u003cV3.21",
"product": {
"name": "SITIPE AT",
"product_id": "4"
}
}
],
"category": "product_name",
"name": "SITIPE AT"
}
],
"category": "vendor",
"name": "Siemens"
}
]
},
"vulnerabilities": [
{
"cve": "CVE-2024-34057",
"cwe": {
"id": "CWE-120",
"name": "Buffer Copy without Checking Size of Input (\u0027Classic Buffer Overflow\u0027)"
},
"notes": [
{
"category": "summary",
"text": "Triangle Microworks TMW IEC 61850 Client source code libraries before 12.2.0 lack a buffer size check when processing received messages. The resulting buffer overflow can cause a crash, resulting in a denial of service.",
"title": "Summary"
}
],
"product_status": {
"known_affected": [
"1",
"2",
"3",
"4"
]
},
"remediations": [
{
"category": "none_available",
"details": "Currently no fix is available",
"product_ids": [
"1"
]
},
{
"category": "vendor_fix",
"details": "Update to V9.14 HF2 or later version",
"product_ids": [
"3"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109745469/"
},
{
"category": "vendor_fix",
"details": "Update to V3.21 or later version",
"product_ids": [
"4"
],
"url": "https://support.industry.siemens.com/cs/ww/en/view/109895930/"
},
{
"category": "vendor_fix",
"details": "Update to V05.30 or later version\n\nThe firmware ETI5 V5.30 is present within \u201cCP-8031/CP-8050 Package\u201d V5.30\n\n\nhttps://support.industry.siemens.com/cs/ww/en/view/109804985/",
"product_ids": [
"2"
]
}
],
"scores": [
{
"cvss_v3": {
"baseScore": 8.2,
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:H",
"version": "3.1"
},
"products": [
"1",
"2",
"3",
"4"
]
}
],
"title": "CVE-2024-34057"
}
]
}
Loading…
Loading…
Sightings
| Author | Source | Type | Date |
|---|
Nomenclature
- Seen: The vulnerability was mentioned, discussed, or seen somewhere by the user.
- Confirmed: The vulnerability is confirmed from an analyst perspective.
- Published Proof of Concept: A public proof of concept is available for this vulnerability.
- Exploited: This vulnerability was exploited and seen by the user reporting the sighting.
- Patched: This vulnerability was successfully patched by the user reporting the sighting.
- Not exploited: This vulnerability was not exploited or seen by the user reporting the sighting.
- Not confirmed: The user expresses doubt about the veracity of the vulnerability.
- Not patched: This vulnerability was not successfully patched by the user reporting the sighting.
Loading…
Loading…