CVE-2014-5410 (GCVE-0-2014-5410)
Vulnerability from nvd
Published
2014-10-03 18:00
Modified
2025-11-04 22:30
Severity ?
VLAI Severity ?
EPSS score ?
CWE
Summary
The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.
References
Impacted products
| Vendor | Product | Version | ||
|---|---|---|---|---|
| Rockwell Automation | Allen-Bradley MicroLogix 1400 |
Version: 0 < Version: 0 < |
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-06T11:41:49.068Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_refsource_MISC",
"x_transferred"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-14-254-02"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Allen-Bradley MicroLogix 1400",
"vendor": "Rockwell Automation",
"versions": [
{
"lessThanOrEqual": "1766-Lxxxxx Series A FRN 7",
"status": "affected",
"version": "0",
"versionType": "custom"
},
{
"lessThanOrEqual": "1766-Lxxxxx Series B FRN 15.000",
"status": "affected",
"version": "0",
"versionType": "custom"
},
{
"status": "unaffected",
"version": "Series B FRN 15.001 or higher"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "finder",
"value": "Matthew Luallen of CYBATI"
}
],
"datePublic": "2014-09-30T06:00:00.000Z",
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cp\u003eThe DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.\u003c/p\u003e"
}
],
"value": "The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line."
}
],
"metrics": [
{
"cvssV2_0": {
"accessComplexity": "MEDIUM",
"accessVector": "NETWORK",
"authentication": "NONE",
"availabilityImpact": "COMPLETE",
"baseScore": 7.1,
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"vectorString": "AV:N/AC:M/Au:N/C:N/I:N/A:C",
"version": "2.0"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-20",
"description": "CWE-20",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2025-11-04T22:30:19.113Z",
"orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"shortName": "icscert"
},
"references": [
{
"url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295"
},
{
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-14-254-02"
},
{
"url": "https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2014/icsa-14-254-02.json"
}
],
"solutions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cp\u003eRockwell Automation has released a new version of MicroLogix 1400 \nSeries B firmware to address the vulnerability and reduce associated \nrisk to successful exploitation. Subsequent versions of MicroLogix 1400 \nSeries B firmware and newer will incorporate these same enhancements.\u003c/p\u003e\n\u003cp\u003eRockwell Automation recommends the following immediate mitigation \nstrategies (when possible, multiple strategies should be employed \nsimultaneously):\u003c/p\u003e\n\u003cul\u003e\n\u003cli\u003eUpgrade all MicroLogix 1400 Series B controllers to Series B FRN \n15.001 or higher. Current firmware for the MicroLogix 1400 Series B \nplatform can be obtained at the following web address:\u003c/li\u003e\n\u003c/ul\u003e\n\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page\"\u003ehttp://www.rockwellautomation.com/rockwellautomation/support/pcdc.page\u003c/a\u003e\u003c/p\u003e\n\n\n\u003cp\u003ePlease refer to Rockwell Automation\u2019s product disclosure (AID 620295) for more information on this topic available at:\u003c/p\u003e\n\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295\"\u003ehttps://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295\u003c/a\u003e\u003c/p\u003e\n\n\u003cbr\u003e"
}
],
"value": "Rockwell Automation has released a new version of MicroLogix 1400 \nSeries B firmware to address the vulnerability and reduce associated \nrisk to successful exploitation. Subsequent versions of MicroLogix 1400 \nSeries B firmware and newer will incorporate these same enhancements.\n\n\nRockwell Automation recommends the following immediate mitigation \nstrategies (when possible, multiple strategies should be employed \nsimultaneously):\n\n\n\n * Upgrade all MicroLogix 1400 Series B controllers to Series B FRN \n15.001 or higher. Current firmware for the MicroLogix 1400 Series B \nplatform can be obtained at the following web address:\n\n\n\n\n http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page \n\n\n\n\nPlease refer to Rockwell Automation\u2019s product disclosure (AID 620295) for more information on this topic available at:\n\n\n https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295"
}
],
"source": {
"advisory": "ICSA-14-254-02",
"discovery": "EXTERNAL"
},
"title": "Rockwell Automation Micrologix 1400 Improper Input Validation",
"workarounds": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cp\u003eUsers with Series A and Series B controllers are also recommended to apply the following risk mitigations:\u003c/p\u003e\n\u003cul\u003e\n\u003cli\u003eDo not enable DNP3 communication in the product unless required.\u003c/li\u003e\n\u003cli\u003eWhere appropriate, prohibit DNP3 communication that originates \noutside the perimeter of the manufacturing zone from entry into the zone\n by blocking communication directed at Ethernet communication Port \n20000/TCP* and 20000/UDP* using appropriate security technology (e.g., a\n firewall, UTM devices, or other security appliance)\u003c/li\u003e\n\u003c/ul\u003e\n\u003cp\u003e\u0026nbsp; \u0026nbsp; \u0026nbsp; \u0026nbsp; \u0026nbsp; *Note: Ports 20000/TCP and 20000/UDP are factory defaults \nas per the DNP3 specification but can be reconfigured by the product \nowner.\u003c/p\u003e\n\u003cul\u003e\n\u003cli\u003eEmploy firewalls with ingress/egress filtering, intrusion \ndetection/prevention systems, and validate all configurations. Evaluate \nfirewall configurations to ensure other appropriate inbound and outbound\n traffic is blocked.\u003c/li\u003e\n\u003cli\u003eRestrict physical and electronic access to automation products, \nnetworks, and systems to only those individuals authorized to be in \ncontact with control system equipment.\u003c/li\u003e\u003cli\u003eEmploy layered security, defense-in-depth methods and network \nsegregation and segmentation practices in system design to restrict and \ncontrol access to individual products and control networks. Refer to \u003ca target=\"_blank\" rel=\"nofollow\" href=\"http://www.ab.com/networks/architectures.html%20\"\u003ehttp://www.ab.com/networks/architectures.html\u003c/a\u003e\u0026nbsp;for comprehensive information about implementing validated architectures designed to deliver these measures.\u003c/li\u003e\n\u003c/ul\u003e\n\u003cp\u003ePlease refer to Rockwell Automation\u2019s product disclosure (AID 620295) for more information on this topic available at:\u003c/p\u003e\n\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295\"\u003ehttps://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295\u003c/a\u003e\u003c/p\u003e\n\n\u003cbr\u003e"
}
],
"value": "Users with Series A and Series B controllers are also recommended to apply the following risk mitigations:\n\n\n\n * Do not enable DNP3 communication in the product unless required.\n\n * Where appropriate, prohibit DNP3 communication that originates \noutside the perimeter of the manufacturing zone from entry into the zone\n by blocking communication directed at Ethernet communication Port \n20000/TCP* and 20000/UDP* using appropriate security technology (e.g., a\n firewall, UTM devices, or other security appliance)\n\n\n\n\n\u00a0 \u00a0 \u00a0 \u00a0 \u00a0 *Note: Ports 20000/TCP and 20000/UDP are factory defaults \nas per the DNP3 specification but can be reconfigured by the product \nowner.\n\n\n\n * Employ firewalls with ingress/egress filtering, intrusion \ndetection/prevention systems, and validate all configurations. Evaluate \nfirewall configurations to ensure other appropriate inbound and outbound\n traffic is blocked.\n\n * Restrict physical and electronic access to automation products, \nnetworks, and systems to only those individuals authorized to be in \ncontact with control system equipment.\n * Employ layered security, defense-in-depth methods and network \nsegregation and segmentation practices in system design to restrict and \ncontrol access to individual products and control networks. Refer to http://www.ab.com/networks/architectures.html http://www.ab.com/networks/architectures.html%20 \u00a0for comprehensive information about implementing validated architectures designed to deliver these measures.\n\n\n\n\nPlease refer to Rockwell Automation\u2019s product disclosure (AID 620295) for more information on this topic available at:\n\n\n https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295"
}
],
"x_generator": {
"engine": "Vulnogram 0.5.0"
},
"x_legacyV4Record": {
"CVE_data_meta": {
"ASSIGNER": "ics-cert@hq.dhs.gov",
"ID": "CVE-2014-5410",
"STATE": "PUBLIC"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "n/a",
"version": {
"version_data": [
{
"version_value": "n/a"
}
]
}
}
]
},
"vendor_name": "n/a"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "n/a"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://ics-cert.us-cert.gov/advisories/ICSA-14-254-02",
"refsource": "MISC",
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-14-254-02"
}
]
}
}
}
},
"cveMetadata": {
"assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"assignerShortName": "icscert",
"cveId": "CVE-2014-5410",
"datePublished": "2014-10-03T18:00:00",
"dateReserved": "2014-08-22T00:00:00",
"dateUpdated": "2025-11-04T22:30:19.113Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.2"
}
CVE-2014-5410 (GCVE-0-2014-5410)
Vulnerability from cvelistv5
Published
2014-10-03 18:00
Modified
2025-11-04 22:30
Severity ?
VLAI Severity ?
EPSS score ?
CWE
Summary
The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.
References
Impacted products
| Vendor | Product | Version | ||
|---|---|---|---|---|
| Rockwell Automation | Allen-Bradley MicroLogix 1400 |
Version: 0 < Version: 0 < |
{
"containers": {
"adp": [
{
"providerMetadata": {
"dateUpdated": "2024-08-06T11:41:49.068Z",
"orgId": "af854a3a-2127-422b-91ae-364da2661108",
"shortName": "CVE"
},
"references": [
{
"tags": [
"x_refsource_MISC",
"x_transferred"
],
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-14-254-02"
}
],
"title": "CVE Program Container"
}
],
"cna": {
"affected": [
{
"defaultStatus": "unaffected",
"product": "Allen-Bradley MicroLogix 1400",
"vendor": "Rockwell Automation",
"versions": [
{
"lessThanOrEqual": "1766-Lxxxxx Series A FRN 7",
"status": "affected",
"version": "0",
"versionType": "custom"
},
{
"lessThanOrEqual": "1766-Lxxxxx Series B FRN 15.000",
"status": "affected",
"version": "0",
"versionType": "custom"
},
{
"status": "unaffected",
"version": "Series B FRN 15.001 or higher"
}
]
}
],
"credits": [
{
"lang": "en",
"type": "finder",
"value": "Matthew Luallen of CYBATI"
}
],
"datePublic": "2014-09-30T06:00:00.000Z",
"descriptions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cp\u003eThe DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.\u003c/p\u003e"
}
],
"value": "The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line."
}
],
"metrics": [
{
"cvssV2_0": {
"accessComplexity": "MEDIUM",
"accessVector": "NETWORK",
"authentication": "NONE",
"availabilityImpact": "COMPLETE",
"baseScore": 7.1,
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"vectorString": "AV:N/AC:M/Au:N/C:N/I:N/A:C",
"version": "2.0"
},
"format": "CVSS",
"scenarios": [
{
"lang": "en",
"value": "GENERAL"
}
]
}
],
"problemTypes": [
{
"descriptions": [
{
"cweId": "CWE-20",
"description": "CWE-20",
"lang": "en",
"type": "CWE"
}
]
}
],
"providerMetadata": {
"dateUpdated": "2025-11-04T22:30:19.113Z",
"orgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"shortName": "icscert"
},
"references": [
{
"url": "https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295"
},
{
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-14-254-02"
},
{
"url": "https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2014/icsa-14-254-02.json"
}
],
"solutions": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cp\u003eRockwell Automation has released a new version of MicroLogix 1400 \nSeries B firmware to address the vulnerability and reduce associated \nrisk to successful exploitation. Subsequent versions of MicroLogix 1400 \nSeries B firmware and newer will incorporate these same enhancements.\u003c/p\u003e\n\u003cp\u003eRockwell Automation recommends the following immediate mitigation \nstrategies (when possible, multiple strategies should be employed \nsimultaneously):\u003c/p\u003e\n\u003cul\u003e\n\u003cli\u003eUpgrade all MicroLogix 1400 Series B controllers to Series B FRN \n15.001 or higher. Current firmware for the MicroLogix 1400 Series B \nplatform can be obtained at the following web address:\u003c/li\u003e\n\u003c/ul\u003e\n\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page\"\u003ehttp://www.rockwellautomation.com/rockwellautomation/support/pcdc.page\u003c/a\u003e\u003c/p\u003e\n\n\n\u003cp\u003ePlease refer to Rockwell Automation\u2019s product disclosure (AID 620295) for more information on this topic available at:\u003c/p\u003e\n\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295\"\u003ehttps://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295\u003c/a\u003e\u003c/p\u003e\n\n\u003cbr\u003e"
}
],
"value": "Rockwell Automation has released a new version of MicroLogix 1400 \nSeries B firmware to address the vulnerability and reduce associated \nrisk to successful exploitation. Subsequent versions of MicroLogix 1400 \nSeries B firmware and newer will incorporate these same enhancements.\n\n\nRockwell Automation recommends the following immediate mitigation \nstrategies (when possible, multiple strategies should be employed \nsimultaneously):\n\n\n\n * Upgrade all MicroLogix 1400 Series B controllers to Series B FRN \n15.001 or higher. Current firmware for the MicroLogix 1400 Series B \nplatform can be obtained at the following web address:\n\n\n\n\n http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page \n\n\n\n\nPlease refer to Rockwell Automation\u2019s product disclosure (AID 620295) for more information on this topic available at:\n\n\n https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295"
}
],
"source": {
"advisory": "ICSA-14-254-02",
"discovery": "EXTERNAL"
},
"title": "Rockwell Automation Micrologix 1400 Improper Input Validation",
"workarounds": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\u003cp\u003eUsers with Series A and Series B controllers are also recommended to apply the following risk mitigations:\u003c/p\u003e\n\u003cul\u003e\n\u003cli\u003eDo not enable DNP3 communication in the product unless required.\u003c/li\u003e\n\u003cli\u003eWhere appropriate, prohibit DNP3 communication that originates \noutside the perimeter of the manufacturing zone from entry into the zone\n by blocking communication directed at Ethernet communication Port \n20000/TCP* and 20000/UDP* using appropriate security technology (e.g., a\n firewall, UTM devices, or other security appliance)\u003c/li\u003e\n\u003c/ul\u003e\n\u003cp\u003e\u0026nbsp; \u0026nbsp; \u0026nbsp; \u0026nbsp; \u0026nbsp; *Note: Ports 20000/TCP and 20000/UDP are factory defaults \nas per the DNP3 specification but can be reconfigured by the product \nowner.\u003c/p\u003e\n\u003cul\u003e\n\u003cli\u003eEmploy firewalls with ingress/egress filtering, intrusion \ndetection/prevention systems, and validate all configurations. Evaluate \nfirewall configurations to ensure other appropriate inbound and outbound\n traffic is blocked.\u003c/li\u003e\n\u003cli\u003eRestrict physical and electronic access to automation products, \nnetworks, and systems to only those individuals authorized to be in \ncontact with control system equipment.\u003c/li\u003e\u003cli\u003eEmploy layered security, defense-in-depth methods and network \nsegregation and segmentation practices in system design to restrict and \ncontrol access to individual products and control networks. Refer to \u003ca target=\"_blank\" rel=\"nofollow\" href=\"http://www.ab.com/networks/architectures.html%20\"\u003ehttp://www.ab.com/networks/architectures.html\u003c/a\u003e\u0026nbsp;for comprehensive information about implementing validated architectures designed to deliver these measures.\u003c/li\u003e\n\u003c/ul\u003e\n\u003cp\u003ePlease refer to Rockwell Automation\u2019s product disclosure (AID 620295) for more information on this topic available at:\u003c/p\u003e\n\u003cp\u003e\u003ca target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295\"\u003ehttps://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295\u003c/a\u003e\u003c/p\u003e\n\n\u003cbr\u003e"
}
],
"value": "Users with Series A and Series B controllers are also recommended to apply the following risk mitigations:\n\n\n\n * Do not enable DNP3 communication in the product unless required.\n\n * Where appropriate, prohibit DNP3 communication that originates \noutside the perimeter of the manufacturing zone from entry into the zone\n by blocking communication directed at Ethernet communication Port \n20000/TCP* and 20000/UDP* using appropriate security technology (e.g., a\n firewall, UTM devices, or other security appliance)\n\n\n\n\n\u00a0 \u00a0 \u00a0 \u00a0 \u00a0 *Note: Ports 20000/TCP and 20000/UDP are factory defaults \nas per the DNP3 specification but can be reconfigured by the product \nowner.\n\n\n\n * Employ firewalls with ingress/egress filtering, intrusion \ndetection/prevention systems, and validate all configurations. Evaluate \nfirewall configurations to ensure other appropriate inbound and outbound\n traffic is blocked.\n\n * Restrict physical and electronic access to automation products, \nnetworks, and systems to only those individuals authorized to be in \ncontact with control system equipment.\n * Employ layered security, defense-in-depth methods and network \nsegregation and segmentation practices in system design to restrict and \ncontrol access to individual products and control networks. Refer to http://www.ab.com/networks/architectures.html http://www.ab.com/networks/architectures.html%20 \u00a0for comprehensive information about implementing validated architectures designed to deliver these measures.\n\n\n\n\nPlease refer to Rockwell Automation\u2019s product disclosure (AID 620295) for more information on this topic available at:\n\n\n https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295"
}
],
"x_generator": {
"engine": "Vulnogram 0.5.0"
},
"x_legacyV4Record": {
"CVE_data_meta": {
"ASSIGNER": "ics-cert@hq.dhs.gov",
"ID": "CVE-2014-5410",
"STATE": "PUBLIC"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "n/a",
"version": {
"version_data": [
{
"version_value": "n/a"
}
]
}
}
]
},
"vendor_name": "n/a"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "n/a"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://ics-cert.us-cert.gov/advisories/ICSA-14-254-02",
"refsource": "MISC",
"url": "https://ics-cert.us-cert.gov/advisories/ICSA-14-254-02"
}
]
}
}
}
},
"cveMetadata": {
"assignerOrgId": "7d14cffa-0d7d-4270-9dc0-52cabd5a23a6",
"assignerShortName": "icscert",
"cveId": "CVE-2014-5410",
"datePublished": "2014-10-03T18:00:00",
"dateReserved": "2014-08-22T00:00:00",
"dateUpdated": "2025-11-04T22:30:19.113Z",
"state": "PUBLISHED"
},
"dataType": "CVE_RECORD",
"dataVersion": "5.2"
}