Vulnerabilites related to Danfoss - AK-SM8xxA Series
CVE-2025-41452 (GCVE-0-2025-41452)
Vulnerability from cvelistv5
Published
2025-08-22 02:40
Modified
2025-08-22 10:52
CWE
  • CWE-15 - External Control of System or Configuration Setting
Summary
Post-authenticated external control of system web interface configuration setting vulnerability in Danfoss AK-SM8xxA Series prior to 4.3.1, which could allow for a denial of service attack induced by improper handling of exceptional conditions
Impacted products
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-41452",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "partial"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-08-22T10:52:01.090719Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-08-22T10:52:36.122Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "AK-SM8xxA Series",
          "vendor": "Danfoss",
          "versions": [
            {
              "lessThan": "4.3.1",
              "status": "affected",
              "version": "0",
              "versionType": "cpe"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "Post-authenticated external control of system web interface configuration setting vulnerability in Danfoss AK-SM8xxA Series prior to 4.3.1, which\u0026nbsp;could allow for a denial of service attack induced by improper handling of exceptional conditions"
            }
          ],
          "value": "Post-authenticated external control of system web interface configuration setting vulnerability in Danfoss AK-SM8xxA Series prior to 4.3.1, which\u00a0could allow for a denial of service attack induced by improper handling of exceptional conditions"
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "HIGH",
            "attackRequirements": "PRESENT",
            "attackVector": "NETWORK",
            "baseScore": 6.8,
            "baseSeverity": "MEDIUM",
            "privilegesRequired": "HIGH",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "HIGH",
            "subConfidentialityImpact": "NONE",
            "subIntegrityImpact": "NONE",
            "userInteraction": "ACTIVE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:H/AT:P/PR:H/UI:A/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "NONE",
            "vulnIntegrityImpact": "NONE",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-15",
              "description": "CWE-15: External Control of System or Configuration Setting",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-08-22T02:40:53.563Z",
        "orgId": "d7ff35af-cf88-454c-bab9-af60602f10f8",
        "shortName": "Danfoss"
      },
      "references": [
        {
          "url": "https://www.danfoss.com/en/service-and-support/downloads/dcs/adap-kool-software/ak-sm-800a/#tab-overview"
        }
      ],
      "source": {
        "discovery": "EXTERNAL"
      },
      "title": "Post auth nginx configuration injection in Danfoss AK-SM8xxA Series",
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "d7ff35af-cf88-454c-bab9-af60602f10f8",
    "assignerShortName": "Danfoss",
    "cveId": "CVE-2025-41452",
    "datePublished": "2025-08-22T02:40:53.563Z",
    "dateReserved": "2025-04-16T10:32:42.818Z",
    "dateUpdated": "2025-08-22T10:52:36.122Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}

CVE-2025-41451 (GCVE-0-2025-41451)
Vulnerability from cvelistv5
Published
2025-08-22 02:40
Modified
2025-08-22 11:25
CWE
  • CWE-77 - Improper Neutralization of Special Elements used in a Command ('Command Injection')
Summary
Improper neutralization of alarm-to-mail configuration fields used in an OS shell Command ('Command Injection') in Danfoss AK-SM8xxA Series prior to version 4.3.1, leading to a potential post-authenticated remote code execution on an attacked system.
Impacted products
Show details on NVD website


{
  "containers": {
    "adp": [
      {
        "metrics": [
          {
            "other": {
              "content": {
                "id": "CVE-2025-41451",
                "options": [
                  {
                    "Exploitation": "none"
                  },
                  {
                    "Automatable": "no"
                  },
                  {
                    "Technical Impact": "total"
                  }
                ],
                "role": "CISA Coordinator",
                "timestamp": "2025-08-22T10:59:49.161150Z",
                "version": "2.0.3"
              },
              "type": "ssvc"
            }
          }
        ],
        "providerMetadata": {
          "dateUpdated": "2025-08-22T11:25:28.640Z",
          "orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
          "shortName": "CISA-ADP"
        },
        "title": "CISA ADP Vulnrichment"
      }
    ],
    "cna": {
      "affected": [
        {
          "defaultStatus": "unaffected",
          "product": "AK-SM8xxA Series",
          "vendor": "Danfoss",
          "versions": [
            {
              "lessThan": "4.3.1",
              "status": "affected",
              "version": "0",
              "versionType": "cpe"
            }
          ]
        }
      ],
      "descriptions": [
        {
          "lang": "en",
          "supportingMedia": [
            {
              "base64": false,
              "type": "text/html",
              "value": "Improper neutralization of alarm-to-mail configuration fields used in an OS shell Command (\u0027Command Injection\u0027) in Danfoss AK-SM8xxA Series\u0026nbsp;prior to version 4.3.1, leading to a potential post-authenticated remote code execution on an attacked system."
            }
          ],
          "value": "Improper neutralization of alarm-to-mail configuration fields used in an OS shell Command (\u0027Command Injection\u0027) in Danfoss AK-SM8xxA Series\u00a0prior to version 4.3.1, leading to a potential post-authenticated remote code execution on an attacked system."
        }
      ],
      "metrics": [
        {
          "cvssV4_0": {
            "Automatable": "NOT_DEFINED",
            "Recovery": "NOT_DEFINED",
            "Safety": "NOT_DEFINED",
            "attackComplexity": "HIGH",
            "attackRequirements": "PRESENT",
            "attackVector": "NETWORK",
            "baseScore": 8.7,
            "baseSeverity": "HIGH",
            "privilegesRequired": "HIGH",
            "providerUrgency": "NOT_DEFINED",
            "subAvailabilityImpact": "HIGH",
            "subConfidentialityImpact": "HIGH",
            "subIntegrityImpact": "HIGH",
            "userInteraction": "ACTIVE",
            "valueDensity": "NOT_DEFINED",
            "vectorString": "CVSS:4.0/AV:N/AC:H/AT:P/PR:H/UI:A/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H",
            "version": "4.0",
            "vulnAvailabilityImpact": "HIGH",
            "vulnConfidentialityImpact": "HIGH",
            "vulnIntegrityImpact": "HIGH",
            "vulnerabilityResponseEffort": "NOT_DEFINED"
          },
          "format": "CVSS",
          "scenarios": [
            {
              "lang": "en",
              "value": "GENERAL"
            }
          ]
        }
      ],
      "problemTypes": [
        {
          "descriptions": [
            {
              "cweId": "CWE-77",
              "description": "CWE-77 Improper Neutralization of Special Elements used in a Command (\u0027Command Injection\u0027)",
              "lang": "en",
              "type": "CWE"
            }
          ]
        }
      ],
      "providerMetadata": {
        "dateUpdated": "2025-08-22T02:40:46.216Z",
        "orgId": "d7ff35af-cf88-454c-bab9-af60602f10f8",
        "shortName": "Danfoss"
      },
      "references": [
        {
          "url": "https://www.danfoss.com/en/service-and-support/downloads/dcs/adap-kool-software/ak-sm-800a/#tab-overview"
        }
      ],
      "source": {
        "discovery": "EXTERNAL"
      },
      "title": "Post-Authentication OS Command Injection RCE in Danfoss AK-SM8xxA Series",
      "x_generator": {
        "engine": "Vulnogram 0.2.0"
      }
    }
  },
  "cveMetadata": {
    "assignerOrgId": "d7ff35af-cf88-454c-bab9-af60602f10f8",
    "assignerShortName": "Danfoss",
    "cveId": "CVE-2025-41451",
    "datePublished": "2025-08-22T02:40:46.216Z",
    "dateReserved": "2025-04-16T10:32:42.818Z",
    "dateUpdated": "2025-08-22T11:25:28.640Z",
    "state": "PUBLISHED"
  },
  "dataType": "CVE_RECORD",
  "dataVersion": "5.1"
}