ID CVE-2015-1358
Summary The remote-management module in the (1) Multi Panels, (2) Comfort Panels, and (3) RT Advanced functionality in Siemens SIMATIC WinCC (TIA Portal) before 13 SP1 and in the (4) panels and (5) runtime functionality in SIMATIC WinCC flexible before 2008 SP3 Up7 does not properly encrypt credentials in transit, which makes it easier for remote attackers to determine cleartext credentials by sniffing the network and conducting a decryption attack.
References
Vulnerable Configurations
  • cpe:2.3:a:siemens:wincc:13.0:*:*:*:*:*:*:*
    cpe:2.3:a:siemens:wincc:13.0:*:*:*:*:*:*:*
CVSS
Base: 5.0 (as of 30-11-2016 - 02:59)
Impact:
Exploitability:
CWE CWE-310
CAPEC
  • Signature Spoofing by Key Recreation
    An attacker obtains an authoritative or reputable signer's private signature key by exploiting a cryptographic weakness in the signature algorithm or pseudorandom number generation and then uses this key to forge signatures from the original signer to mislead a victim into performing actions that benefit the attacker.
Access
VectorComplexityAuthentication
NETWORK LOW NONE
Impact
ConfidentialityIntegrityAvailability
PARTIAL NONE NONE
cvss-vector via4 AV:N/AC:L/Au:N/C:P/I:N/A:N
refmap via4
bid 72625
confirm
misc https://ics-cert.us-cert.gov/advisories/ICSA-16-161-02
sectrack 1036090
Last major update 30-11-2016 - 02:59
Published 18-02-2015 - 02:59
Last modified 30-11-2016 - 02:59